B-2016-1982CITY OF CUPERTINO BUILDING PERMIT
BUILDING ADDRESS: CONTRACTOR: PERMIT NO: B-2016-1982
20888 FARGO DR CUPERTINO, CA 95014-1806 (326 30 116) SUNRUN
INSTALLATION
SERVICES INC
SAN LUIS OBISPO, CA
93401
OWNER'S NAME: LIU YOUZHONG AND ZHAO WEIYING DATE ISSUED: 05/19/2016
OWNER'S PHONE: 408-462-1188 PHONE NO: (888) 657-6527
LICENSED CONTRACTOR'S DECLARATION
License Class C-46 Lic. #750184
Contractor SUNRUN INSTALLATION SERVICES INC Date 06/30/2016
I hereby affirm that I am licensed under the provisions of Chapter 9 (commencing
with Section 7000) of Division 3 of the Business & Professions Code and that my
license is in full force and effect.
I hereby affirm under penalty of perjury one of the following two declarations:
1. I have and will maintain a certificate of consent to self -insure for Worker's
Compensation, as provided for by Section 3700 of the Labor Code, for the
performance of the work for which this permit is issued.
,I have and will maintain Worker's Compensation Insurance, as provided for by
Section 3700 of the Labor Code, for the performance of the work for which this
permit is issued.
APPLICANT CERTIFICATION
I certify that I have read this application and state that the above
information is correct. I agree to comply with all city and county ordinances
and state laws relating to building construction, and hereby authorize
representatives of this city to enter upon the above mentioned property for
inspection purposes. (We) agree to save indemnify and keep harmless the
City of Cupertino against liabilities, judgments, costs, and expenses which
may accrue against said City in consequence of the granting of this permit.
Additionally, the applicant understands and will comply with all non -point
source regulations per the Cupertino
Municipal Code, Section 9.18.
Signature d thDate 5/19/2016
BUILDING PERMIT INFO:
X BLDG —ELECT —PLUMB
_ MECH X RESIDENTIAL _ COMMERCIAL
JOB DESCRIPTION:
(I) 25-PANEL ROOF -MOUNTED PV SYSTEM (6.0 KW)
Sq. Ft Floor Area: I Valuation: $12300.00
"N Number: Occupancy Type:
32630 116
PERMIT EXPIRES IF WORK IS NOT STARTED
WITHIN 180 DAYS OF PERMIT ISSUANCE OR
180 DAYS FROM LAST CALLUD ,i S-PECTION.
Issued by: Alex Vallelunea
Date: 05/19/2016
I hereby affirm that I am exempt from the Contractor's License Law for one of the RE -ROOFS:
following two reasons: All roofs shall be inspected prior to any roofing material being installed. If a roof is
1. I, as owner of the property, or my employees with wages as their sole installed without first obtaining an inspection, I agree to remove all new materials for
compensation, will do the work, and the structure is not intended or offered for inspection.
sale (Sec.7044, Business & Professions Code)
I, as owner of the property, am exclusively contracting with licensed
contractors to construct the project (Sec.7044, Business & Professions Code).
hereby affirm under penalty of perjury one of the following three declarations:
1. I have and will maintain a Certificate of Consent to self -insure for Worker's
Compensation, as provided for by Section 3700 of the Labor Code, for the
performance of the work for which this permit is issued.
2. I have and will maintain Worker's Compensation Insurance, as provided for by
Section 3700 of the Labor Code, for the performance of the work for which this
permit is issued.
3. I certify that in the performance of the work for which this permit is issued, I
shall not employ any person in any manner so as to become subject to the
Worker's Compensation laws of California. If, after making this certificate of
exemption, I become subject to the Worker's Compensation provisions of the
Labor Code, I must forthwith comply with such provisions or this permit shall
be deemed revoked.
APPLICANT CERTIFICATION
I certify that I have read this application and state that the above information is
correct. I agree to comply with all city and county ordinances and state laws
relating to building construction, and hereby authorize representatives of this city
to enter upon the above mentioned property for inspection purposes. (We) agree
to save indemnify and keep harmless the City of Cupertino against liabilities,
judgments, costs, and expenses which may accrue against said City in
consequence of the granting of this permit. Additionally, the applicant understands
and will comply with all non -point source regulations per the Cupertino Municipal
Code, Section 9.18.
Signature ofApl
Date: 5/19/2016
ALL ROOF COVERINGS TO BE CLASS "A" OR BETTER
HAZARDOUS MATERIALS DISCLOSURE
I have read the hazardous materials requirements under Chapter 6.95 of the
California Health & Safety Code, Sections 25505, 25533, and 25534. I will
maintain compliance with the Cupertino Municipal Code, Chapter 9.12 and the
Health & Safety Code, Section 25532(a) should I store or handle hazardous
material. Additionally, should I use equipment or devices which emit hazardous
air contaminants as defined by the Bay Area Air Quality Management District I
will maintain compliance with the Cupertino Municipal Code, Chapter 9.12 and
the Health & Safety Code, Sections 25505, 25533, and 25534.
Owner or authorized agent:
Date: 5/19/2016
CONSTRUCTION LENDING AGENCY
I hereby affirm that there is a construction lending agency for the performance
of work's for which this permit is issued (Sec. 3097, Civ C.)
Lender's Name
Lender's Address
ARCHITECT'S DECLARATION
I understand my plans shall be used as public records.
Signature
Licensed
Date 5/19/2016
CUPERTINO
AI
COMMUNITY DEVELOPMENT DEPARTMENT • BUILDING DIVISION
10300 TORRE AVENUE • CUPERTINO, CA 95014-3255
(408) 777-3228 •FAX (408) 777-3333 • building
(a)cupertino.org
iPs 20! C�
PROJECT ADDRESS 0 2 � `3� � � r` jl J � p �� � � APN #
OWNER NAME ��•V6�_"o' Nt & Lj U 1 Ci1� PHONE LW b7 1�/�_� E-MAIL
STREET AD e v ��O Y ®• TY STATE,ZIP�J � FAX
CONTACT NAME � ;�„ E-MAIL
i � V
STRfxgT FAX
❑ OWNER ❑ OWNER -BUILDER ❑ OWNER AGENT CONTRACTOR ❑ CONTRACTOR AGENT ❑ ARCHITECT ❑ ENGINEER ❑ DEVELOPER ❑ TENANT
CONTRACTOR NA �- !� . L I� LICFrE ICE BUS. LTC # / /
COMPANY E, , 1Y ,�,, 411 •► o�
2
ARCHITECT/ENGINEF.R NAME LICENSE NUMBER BUS. LTC #
COMPANY NAME E-MAIL FAX
STREET ADDRESS CITY, STATE, ZIP PHONE
USE OF SFD Or Duplex ❑ Multi -Family PROJECT IN WILDLAND PROJECT IN
STRUCTURE: ❑ Commercial URBAN INTERFACE AREA ❑ Yes ❑ NO FLOOD ZONE ❑ Yes ❑ No
SOLAR PANELS ❑ ELECTRIC VEHICLE CHARGING STATION 1 ❑ SOLAR WATER HEATING ❑ OTHER:
FOR SOLAR PANELS. NUMBER OF PANELS/UNITS: KILOWATTS (COMMERCIAL ONLY): r� TOTAL VALUATION:
DESCRIPTION OF WORK
By my signature below, I certify to each of the following: I am the property owner or authorized agent to act on the property owner's behalf. I have read it Ii S
application and the information I have provided is correct. I have read the Description of Work and verify it is accurate. I agree to comply with all applicable local
ordinances and state laws relating to building construction. I authorize representatives of Cupertino to enter the above -id fified roperty for inspection purposes.
Signature of Applicant/Agent: RAADate:
SUPPLEMENTAL INFORMATION REQUIRED n> F"ri FncF nNl.v
PVApp_2011.doc revised 03116111
i O
RECEIVED
.r n ianS®lar
Canadian Solar's new Quartech modules have
significantly raised the standard of module
efficiency in the solar industry. They introduced
innovative four busbar cell technology, which
demonstrates higher power output and higher
system reliability. Worldwide, our customers have
embraced this next generation of modules for
their excellent performance, superior reliability
and enhanced value.
NEW TECHNOLOGY
Reduces cell series resistance
Reduces stress between cell interconnectors
Improves module conversion efficiency
Improves product reliability
KEY FEATURES
ck frame
Juct can be
Tided upon
request.
insurance -backed warranty
25
years non -cancelable, immediate warranty insurance
linear power output warranty
10 1 product warranty on materials
=; years ; and workmanship
Higher energy yield MANAGEMENT SYSTEM CERTIFICATES
Outstanding performance at low irradiance ISO 9001:2008 / Quality management system
Maximum energy yield at low NOCT ISO/TS 16949:2009 /The automotive industry quality management system
Improved energy production through ISO 14001:2004/ Standards for environmental management system
reduced cell series resistance OHSAS 18001:2007 / International standards for occupational health & safety
Increased system reliability PRODUCT CERTIFICATES
Long-term system reliability with IP67 IEC 61215/IEC 61730: VDE/MCS/CE /JET/SII/CECAU/INMETRO/CQC
junction box UL 1703 /IEC 61215 performance: CEC listed (US) / FSEC (US Florida)
Enhanced system reliability in extreme UL 1703: CSA / IEC 61701 ED2: VDE / IEC 62716: VDE / IEC 60068-2-68: SGS
temperature environment with special PV CYCLE (EU) / UNI 9177 Reaction to Fire: Class 1
cell level stress release technology
Extra value to customers
Positive power tolerance up to 5 W
Stronger 40 mm robust frame to hold
snow load up to 5400 Pa and
wind load up to 2400 Pa
Anti -glare project evaluation
Salt mist, ammonia and blowing sand
resistance apply to seaside, farm and
desert environments
x i
D E OBWt; PV CYCL e )E +�
J --
CANADIAN SOLAR INC. is committed to providing high quality
solar products, solar system solutions and services to customers
around the world. As a leading manufacturer of solar modules and
PV project developerwith about 10 GW of premium quality modules
deployed around the world since 2001, Canadian Solar Inc. (NAS—
DAQ: CSIQ) is one of the most bankable solar companies worldwide.
CANADIAN SOLAR INC.
545 Speedvale Avenue West, Guelph, Ontario N1 K 1 E6, Canada, www.canadiansolar.com, support@canadiansolar.com
MODULE / ENGINEERING DRAWING (mm)
Rear View
Frame Cross Section A -A
35
11
Mounting Hole
F
R
0,__
ELECTRICAL DATA / STC*
Electrical Data CS6P 260P 265P
Nominal Max. Power (Pmax)
260 W 265 W _
Opt. Operating Voltage (Vmp)
Opt. Operating Current (Imp)
30A V 30.6 V
8.56 A_ 8.66 A
�37.7
Open Circuit Voltage (Voc) —
37.5 V V____
Short Circuit Current (Isc)
Module Efficiency_! __ _
9.12 A 9.23 A
16.16% 16.47% _
Operating Temperature_
-40°C — +85°C
Max. System Voltage
1000 V (IEC) or 1000 V (UQ
Module Fire Performance
TYPE 1 (UL 1703) or
CLASS C (IEC61730)
Max. Series Fuse Rating
15 A
—
Application Classification __
Power Tolerance
Class A _
0 — + 5 W
* Under Standard Test Conditions (STC) of irradiance of
1000 W/m2, spectrum AM 1.5 and cell temperature of 25°C.
ELECTRICAL DATA / NOCT*
Electrical Data CS6P _
260P
265_P_ _
Nominal Max. Power (Pmax)
189 W
_ 192 W _
Opt. Operating Voltage (Vmp)
27.7 V
27.9 V
Opt. Operating Current (Imp)
6.80 V
6.88 A
Open Circuit Voltage (Voc)
34.5 V
34.7 V _
Short Circuit Current (Isc)
7.39 A
7.48 A
* Under Nominal Operating Cell Temperature (NOCT), irradiance
of 800 W/m2, spectrum AM 1.5, ambient temperature 20°C,
wind speed 1 m/s.
PERFORMANCE AT LOW IRRADIANCE
Industry leading performance at low irradiation, average
+96.5% relative efficiency from an irradiance of
1000 W/m2 to 200 W/m2 (AM 1.5, 25°C).
The specification and key features described in this datasheet may deviate slightly
and are not guaranteed. Due to on -going innovation, research and product
enhancement, Canadian Solar Inc. reserves the right to make any adjustment
to the information described herein at any time without notice. Please always
obtain the most recent version of the datasheet which shall be duly incorporated
into the binding contract made by the parties governing all transactions related
to the purchase and sale of the products described herein.
Caution: For professional use only. The installation and handling of PV modules
requires professional skills and should only be performed by qualified professionals.
Please read the safety and installation instructions before using the modules.
CS6P-260P / I-V CURVES
A
10
9
a
7
6
5
4
3
2
6
4
3
2
1
V 0
5 10
15 20
25
30
35
40
A
5 10 15 20 25 30 35 40
IM 1000 W/m' S°c ❑
Ci 300 W/m' 25°C
Ci 600 W/m' 45°C ❑
Efl 400 W/m' 65°C ❑
MODULE / MECHANICAL DATA
specification Data
Cell Type ______Poly
-crystalline, 6 inch
Cell Arrangement,
60 (6x10)
Dimensions
1638x982x40 mm (64.5 x38,7x1.57 in)
_
Weight--
18 kg (39_7 Ibs) T
Front Cover
3.2 mm tempered glass _
Frame
Anodized aluminium alloy_____
-Material
J-Box
IP67, 3 diodes
Cable
4 mm2 (IEC) or 4 mm2 & 12AWG
1000 V (UL), 1000 mm (39.4 in)
(650 mm (25.6 in) is optional)
Connectors
Friends PV2a (IEC),
Friends PV2b (IEC / UQ
Standard
26 pieces, 515 kg (1135.4 Ibs)
Packaging
(quantity & w_eight per [let)
Module Pieces
per Container
728 pieces (40' HQ)
TEMPERATURE CHARACTERISTICS
Specification
Data
T_emperature_Coe_fficient (Pmax)
`=0.41%/ °C
_
Temperature Coefficient (Voc)_
_ -0.31 % / °C
Temperature Coefficient (Isc) _
0.053%/ °C
Nominal Operating -Cell Temperature_ 45±21
PARTNER SECTION
Scan this QR-code to discover solar M.
projects built with this module ;1.
CANADIAN SOLAR INC. August 2015. All rights reserved, PV Module Product Datasheet V5.3EN C. .
C$A
' Group
Certificate of Compliance
Certificate:
Proj ect:
2284121
70048197
Issued to: Canadian Solar Inc
545 Speedvale Ave West
Guelph, Ontario NIK IE6
CANADA
Attention: dean -Nicolas Jaubert
Faster Contract: 249143
Date Issued: 2015-10-05
The products listed below are eligible to bear the CSA Marls shown
with adjacent indicators 'C' and 'US'for Canada and US or with adjacent
indicator 'US' for US only or without either indicator for Canada only.
CP ® Issued by: A 4''lv (A rL4)
C US N"e4,v
Anh (Andy) Nguyen
PRODUCTS
CLASS - C531110 - POWER SUPPLIES -Photovoltaic Modules and Panels
CLASS - C531190 - POWER SUPPLIES -Photovoltaic Modules and Panels - Certified to US Standards
Photovoltaic Modules with maximum system voltage of 600 V do or 1000 V do and Type 1 module fire
performance, Model Series CS6X-XXXP, CS6X-XXXPX, where'XXX' is the power output from 250 W to 330
W with the following electrical ratings typical at 305 W @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 44.8 V
Short Circuit Current (Isc): 8.97 A
Operating Voltage (Vpmax): 36.3 V
Current at Operating Voltage (Ipmax): 8.41 A
Photovoltaic Modules with maximum system voltage of 600 V do or 1000 V do and Type 1 module fire
performance, Model Series CS6X-XXXM, where'XXX' is the power output from 260 W to 350 W with the
following electrical ratings typical at 350 W @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 46.6 V
Short Circuit Current (Isc): 9.67 A
Operating Voltage (Vpmax): 38.3 V
Current at Operating Voltage (Ipmax): 9.14 A
`&WIM
n SSA
Croup
Certif Cate: 2284121
Project: 70048197
Master Contract: 249143
Date Issued: 2015-10-05
Photovoltaic Modules with maximum system voltage of 600 V do or 1000 V do and Type 1 module fire
performance, Model Series CS6P-XXXP, CS6P-XXXP-S, CS6P-XXXPX where'XXX' is the power output from
200 W to 275 W with the following electrical ratings typical at 260 W for CS6P-XXXP/ CS6P-XXXP-S, and
CS6P-XXXPX series respectively @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 37.5 V
Short Circuit Current (Isc): 9.12 A
Operating Voltage (Vpmax): 30.4 V
Current at Operating Voltage (Ipmax): 8.56 A
Photovoltaic Modules with maximum system voltage of 600 V do or 1000 V do and Type 1 module fire
performance, Model Series CS6P-XXXM and CS6P-XXXMX where'XXX' is the power output from 200 W to
290 W with the following electrical ratings typical at 290 W for CS6P-XXXM and CS6P-XXXMX series
respectively @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 38.7 V
Short Circuit Current (Isc): 9.59 A
Operating Voltage (Vpmax): 31.9 V
Current at Operating Voltage (Ipmax): 9.09 A
Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 module fire performance, Model
Series CS5A-XXXM, , where 'XXX' is the power output from 170 W to 210 W with the following electrical
ratings typical at 210 W @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 45.6 V
Short Circuit Current (Isc): 5.90 A
Operating Voltage (Vpmax): 38.1 V
Current at Operating Voltage (Ipmax): 5.51 A
Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 module fire performance, Model
Series CS6A-XXXP, where 'XXX' is the power output from 160 W to 210 W with the following electrical ratings
typical at 210 W @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 30.0 V
Short Circuit Current (Isc): 9.19 A
Operating Voltage (Vpmax): 24.4 V
Current at Operating Voltage (Ipmax): 8.63 A
Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 module fire performance, Model
Series CS6F-XXXM, where'XXX' is the power output from 30W to 40W with the following electrical ratings
typical at 40W @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 22.8 V
Short Circuit Current (Isc): 2.28 A
Operating Voltage (Vpmax): 18.6 V
Current at Operating Voltage (Ipmax): 2.15 A
..........
I.
Certificate: 2284121
Project: 70048197
Master Contract: 249143
Date Issued: 2015-10-05
Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 module fire performance, Model
Series CS6F-XXXP, where'XXX' is the power output from 30W to 40W with the following electrical ratings
typical at 40W @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 22.6 V
Short Circuit Current (Isc): 2.32 A
Operating Voltage (Vpmax): 18.4 V
Current at Operating Voltage (Ipmax): 2.17 A
Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 module fire performance, Model
Series CS6H-XXXM, where 'XXX' is the power output from 20W to 26W with the following electrical ratings
typical at 26W @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 22.7 V
Short Circuit Current (Ise): 1.5 A
Operating Voltage (Vpmax): 18.4 V
Current at Operating Voltage (Ipmax): 1.41 A
Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 module fire performance, Model
Series CS6H-XXXP, where 'XXX' is the power output from 20 W to 26 W with the following electrical ratings
typical at 26 W @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 22.5 V
Short Circuit Current (Ise): 1.52 A
Operating Voltage (Vpmax): 18.2 V
Current at Operating Voltage (Ipmax): 1.43A
Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 module fire performance, Model
Series CS6E-XXXM, where'XXX' is the power output from 45 W to 60 W with the following electrical ratings
typical at 60 W @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 22.8 V
Short Circuit Current (Ise): 3.42 A
Operating Voltage (Vpmax): 18.6 V
Current at Operating Voltage (Ipmax): 3.23 A
Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 module fire performance, Model
Series CS6E-XXXP, where 'XXX' is the power output from 45 W to 60 W with the following electrical ratings
typical at 60 W @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 22.6 V
Short Circuit Current (Ise): 3.47 A
Operating Voltage (Vpmax): 18.4 V
Current at Operating Voltage (Ipmax): 3.26 A
CSA
Group
Certificate: 2284121
Project: 70048197
Master Contract: 249143
Date Issued: 2015-10-05
Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 module fire performance, Model
Series CS6D-XXXM, where'XXX' is the power output from 60 W to 75 W with the following electrical ratings
typical at 75 W @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 22.5 V
Short Circuit Current (Ise): 4.37 A
Operating Voltage (Vpmax): 18.3 V
Current at Operating Voltage (Ipmax): 4.11 A
Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 module fire performance, Model
Series CS6D-XXXP, where'XXX' is the power output from 60 W to 75 W with the following electrical ratings
typical at 75 W @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 22.3 V
Short Circuit Current (Ise): 4.43 A
Operating Voltage (Vpmax): 18.1 V
Current at Operating Voltage (Ipmax): 4.15 A
Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 module fire performance, Model
Series CS6C-XXXM, where 'XXX' is the power output from 120 W to 175 W with the following electrical ratings
typical at 145 W @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 22.4 V
Short Circuit Current (Ise): 8.52 A
Operating Voltage (Vpmax): 18.1 V
Current at Operating Voltage (Ipmax): 8.01 A
Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 module fire performance, Model
Series CS6C-XXXP, where'XXX' is the power output from 120 W to 165 W with the following electrical ratings
typical at 150 W @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 22.3 V
Short Circuit Current (Ise): 8.87 A
Operating Voltage (Vpmax): 18.1 V
Current at Operating Voltage (Ipmax): 8.30 A
Photovoltaic Modules with maximum system voltage of 600 V do or 1000 V do and Type 1 module fire
performance, Model Series CS6K-XXXP, where'XXX' is the power output from 220 W to 275 W with the
following electrical ratings typical at 275 W for CS6K-XXXP series @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 38.0 V
Short Circuit Current (Ise): 9.45 A
Operating Voltage (Vpmax): 31.0 V
Current at Operating Voltage (Ipmax): 8.88 A
.P
CSA
F" ,r
Group
Certificate: 2284121
Project: 70048197
Master Contract: 249143
Date Issued: 2015-10-05
Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 module fire performance, Model
Series CS6A-XXXM, where'XXX' is the power output from 160 W to 230 W with the following electrical
ratings typical at 205 W @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 30.6 V
Short Circuit Current (Ise): 9.31 A
Operating Voltage (Vpmax): 24.8 V
Current at Operating Voltage (Ipmax): 8.87 A
Photovoltaic Modules with maximum system voltage of 600 V do or 1000 V do and Type 1 module fire
performance, Model Series CS6K-XXXM, where 'XXX' is the power output from 240 W to 290 W with the
following electrical ratings typical at 290 W for CS6K-XXXM series @ Standard Test Condition (STC):
Open Circuit Voltage (Voc): 38.7 V
Short Circuit Current (Ise): 9.59 A
Operating Voltage (Vpmax): 31.9 V
Current at Operating Voltage (Ipmax): 9.09 A
Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 module fire performance, Model
Series CS6P-XXXP-SD, and CS6K-XXXP-SD where'XXX' is the power output from 240 W to 275 W with the
following electrical ratings typical at 250 W @ Standard Test Condition (STC):
Output Voltage Range (Vout): 5 — 60 V
Maximum Output Current (Imax): 15 A
Photovoltaic Modules with maximum system voltage of 600V or 1000 V do and Type 1 module fire performance,
Model Series CS6P-XXXP-TD, where 'XXX' is the power output from 240 W to 275 W with the following
electrical ratings typical at 250 W @ Standard Test Condition (STC):
Output Voltage Range (Vout): 16 — 32 V (Voc*)
Maximum Output Current (Imax): 9.5 A
*For modules with Smart Curve function the Voc is adjustable and is programmed only at the factory based on
the PV module voltage.
Notes: Rated electrical characteristics are within +/-10% of measured values at Standard Test Conditions of
100 mW/cm2 irradiance, AM 1.5 spectrum, and cell temperature of 25°C.
APPLICABLE REQUIREMENTS
ULC/ORD- C1703-01 - Flat -Plate Photovoltaic Modules and Panels
UL 1703-3`d Edition - Flat -Plate Photovoltaic Modules and Panels
Supplement to Certificate of Compliance
Certificate: 2284121 (249143)
Project
70048197
Master Contract: 249143
The products listed, including the latest revision described below,
are eligible to be marked in accordance with the referenced Certificate.
Product Cerfi eatiou History
Date Description
2015-10-05 Update Report 2284121 for 1. Seven new cell technologies 2. Two new J-box
tested with 13 different combinations of backsheets and adhesive 3. New J-
box and frame adhesive 4. New clamping method for ZEP frame 5. Mounting
on NexTracker 6.Removal of obsolete models and materials 7. Update F1
frame for NexTracker and ATI trackers 8. Update HF10 test results for
Boviet Solar factory
70043990 2015-09-10 Provide Report Update to add BF test results
70031273 2015-05-01 Update test report no. 2284121 for 1. Alternate EVA -' Changshu Tegu New
Material Technology Co. Ltd.', types 72014" and 72053", 0.45-0.5 mm
nominal thickness, two sheets provided (T2014 type above cell strings -
superstrate side - and T2053 type below - substrate side) 2. Alternate
Substrate - (Suzhou) Sunwatt Co., Ltd.', white type "KFB-30" overall
thickness, 0.290 mm nominal. 3. Alternate Substrate -'Crown Adbanced
Material Co., Ltd.', white type "BE-D2", overall thickness, 0.390 mm
nominal 4. Add new Model Series CS6P-XXXP-TD , 240 W to 275 W range,
with Tigo DC optimizer 5. Alternate Jbox -'Changshu Friends Connector
Technology Co., Ltd', junction box type CF1108-03g, rated 600 V dc, 11A 6.
Alternate Jbox - 'Changshu Friends Connector Technology Co., Ltd', junction
box type CF1108-03g b, rated 1000 V dc, 1 IA 7. Alternate Jbox - #Tigo
energy Inc.#, junction box type MMJ-ES50, with Smart Curve function, rated
1000 dc, 9.5A 8. Alternative Cables: For use with MMJ-ES50 junction boxes
only, on CS6P-P-TD, NRTL approved type PV wire No. 12 AWG, rated 600
V minimum. Outer diameter 6.7±0.20 mm, 90°C minimum, marked sunlight
resistant 9. Add new bypass diode 30CTQ100S (For use with MMJ-ES50
junction boxes only), rated 100v, 30A 10. Alternate mounting system -
CS6X-xxxPX with ZS Peak mounting system 11. Alternate mounting system
- CS6X-xxxP with Array Technology Inc, DuraTrack# HZ Solar Tracker V3
clamps and torque tube 12. Alternate grounding method - for Brilliant Rack
Ground Mount System. 13.
70016938 2015-01-09 Update Report 2284121 to Include Vietnam Factory "Viva Solar
Technology"
70015998 2014-12-24 Update Report 2284121 to add model CS6P-P-SD (w/Solaredge Optimizer),
CS6P-P-TD(w/Tigo optimizer), four alternative cells and alternative
grounding method.
CSA
Group
Certificate. 2284121
Project: 70048197
piaster Contract: 249143
Bate Issued: 2015-10-05
70013912 2014-10-30
Update Report 2284121 to include two alternative cells and alternative
grounding methods.
2761996 2014-09-24
Update Report 2284121 to add Celestica, ON as a Factory; IFE Not
Required
2749251 2014-07-25
Update to include alternative cells, EVA, backsheet, potting compound and
grounding methods.
2725910 2014-05-15
Update Report 2284121 to include the addition of series -M and -MM and
alternative construction.
2679144 2014-01-31
Add Factory "Canadian Solar Solutions Inc, London, ON".
2676999 2013-11-13
Update to include an alternative EVA, backsheet, junction box and cells.
2633572 2013-07-08
Update to include two alternative backsheets and two cells.
2618121 2013-04-19
Update to include an alternative EVA, backsheet, junction box, junction box
adhesive and cells.
2604442 2013-02-26
Update to include changes to cells, alternative EVA and addition of series
CS6K.
2600055 2013-02-06
Update to include an alternative mounting system.
2594501 2013-01-17
Update to inlcude alternative junction box and a number of poly and mono
cells.
2584786 2013-01-03
Update to add factory "CSI Central Power".
2587786 2012-12-19
Update to include changes to cells, alternative j-box and back sheets BEC-
301 by Hangzhou First and VTPEIRW by Taiflex.
2559421 2012-09-26
Update to include the addition of Flexcon KPE backsheet.
2542034 2012-07-06
Update to include new half cell modules series PT, addition of 1000 V rating,
alternative j-boxes and adhesive.
2496460 2012-06-15
Evaluation to add backsheet from COVEME for all the module series (with
F806 EVA, CM0804 junction box and Tonsan 1527 adhesive).
2515777 2012-06-12
Update to include the evaluation of factory location in South Korea (includes
HF10 test sequence).
2532459 2012-06-05
Update to include new models (smaller modules), alternative cells and
backsheets.
2512339 2012-03-28
Update to include alternative cells.
2508436 2012-03-21
Update to include three alternative cells and an alternative Toyo back sheet.
2490216 2012-01-13
Update to add CSSP-xxxP and CSSA-XXXP Series.
2458713 2011-12-19
Evaluation for an alternative (Shunfeng) cell and j-box with Isovolta AAA
backsheet with PV744 adhesive.
2480024 2011-12-01
Evaluation for alternative JA Solar cells and to add new series.
Certificate: 2284121
Project: 70048197
2470474
2011-10-28
2455625
2011-09-02
2441645
2011-07-26
2431019 2011-06-03
2404638
2011-04-18
2390337
2011-02-08
2380821
2010-12-17
2284122
2010-10-14
2284121
2010-06-30
CSA
S A Group
Master Contract: 249143
Date Xssued: 2015-10-05
Update to add the laminates (without frame).
Update to add smaller modules with cut cells.
Update to include change in glass dimensions, black backsheet, new frame
and new j-box and edgeseal adhesive.
Update to include the addition of model series CS6A and use of alternative
mateirals and components.
Update to include an alternate lamination line, includes HF10 test sequence.
Addition of factory location in Ontario.
Update to include Model Series CS5A-XXXM and CS5T-XXXM.
Addition of 72 cell series CS6X-XXXP and CS6X-XXXM.
Evaluation of PV Panel Series for C/CSA/US Mark.
For North America
- Integrated arc fault protection for NEC 201l69O,l1compliance
- Rapid shutdown for NEC 2014S90.lZ
~ Superior efficiency (9O>6)
~ Small, lightweight and easy toinstall onprovided bracket
~ Built-in module -level monitoring
- Internet connection through Ethernet o/Wireless
~ Outdoor and indoor installation
~ Fixed voltage inverter, DC/AC conversion only
~ Pre -assembled Safety Switch for faster installation
~ Optional — revenue grade data, ANSI [12l
Sin& PhaS@ d�� rtgrS for North America
Sa rZe ®
SE300OA-US J SE380OA-US / SE5000A-US / SE600OA-US /
SE760OA-US / SE10000A-US / SE1140OA-US
�SE3000A-US SE38QQA US SE5000A-US I SE600CA US ISE7600A US j SEIQQOOA- US SE114QOA US
OUTPUT
--�--�
-Nominal
i
9980 @ 203V
AC Power Output
; 3000
f
3800
I 5000
6000
7600
10000 @240V
11400
VA
Max. AC Power Output
$ 3300
4150
5400 @ 208V
5450 @240V
( 6000
la
8350
10800 @ 208V
10950 @240V
12000
VA
AC Output Voltage Min: Nom: tVlax.t'I
I
j f
I
183 - 208 - 229 Vac
if
AC Output Voltage Min: Nom: Max.)t)
✓
d
✓
211- 240 - 264 Vac
I I
I
AC Frequency Min: Nom: Max.lal
59.3 - 60 - 60.5
Hz
Max. Continuous Output Current
12.5
16 24 @ 208V 25 32
21 @ 240V j
48 @ 208V
42 @ 240V
47.5
A
GFDI Threshold
1
A
Utility Monitoring, Islanding Protection,
Country Configurable ThresholdsYes
Yes
INPUT
Maximum DC Power(STC)
f 4050
5100 T 6750 8100 10250
13500
15350
1-W
Transformer -less, Ungrounded
S
Yes
Max. Input Voltage
i
500
Vdc
Nom. DC Input Voltage
325 @ 208V / 350 @ 240V
Vdc
III 16.5 @ 208V
33 @ 208V
Max. Input Current(')
9.5
13 18 23
15.5 @ 240V j j
30.5 @ 240V t
34.5
Adc
Max, Input Short Circuit Current
45
I Adc
Reverse -Polarity Protection
Yes
Ground -Fault Isolation Detection
600ka Sensitivity
Maximum Inverter Efficiency
97.7
98.2 98.3 98.3 98
98
98
CEC Weighted Efficiency
i !
97.5 i
98 97 @ 208V ( 97.5 97.5
97 @ 208V
97.5
30
98 @ 240V
97.5 @ 240V
Nighttime Power Consumption
< 2.5
< 4
1W
ADDITIONAL FEATURES
Supported Communication interfaces
RS485, RS232, Ethernet, ZigBee (optional)
Revenue Grade Data, ANSI C12.1
Optionallal
Rapid Shutdown -NEC 2014 690.12��^ -
Yes
STANDARD COMPLIANCE
Safety
_
UL1741, UL1699B, UL1998 , CSA 22.2
Grid Connection Standards
IEEE1547
Emissions
FCC part15 class B
I
INSTALLATIONSPECIFICATIONS
AC output conduit size / AWG range
3/4" minimum / 16-6 AWG
3/4" minimum / 8-3 AWG
DC input conduit size / # of strings /
3/4" minimum / 1-2 strings / 16-6 AWG
3/4" minimum / 1-3 strings /
AWG range
14-6 AWG
Dimensions with Safety Switch
30.5 x 12.5 x 7.2 / 775 x 315 x 184
30.5 x 12.5 x 10.5 /
in /
(HxWXD)
775 x 315 x 260
mm
Weight with Safety Switch
51.2 / 23.2 54.7 / 24.7
88 .4 / 40.1
lb / kg
Cooling
Natural
convection
Natural Convection and internal ( Fans (user replaceable)
fan (user {!i
replaceable)
Noise < 25 < 50
Min. -Max. Operating Temperature i -13 to +140 / -25 to +60 (-40 to +60 version available"))
Range
Protection Rating NEMA 311
For other regional settings please contact SolarEdge support.
A higher current source maybe used; the inverter will limit its input current to the values stated.
13j Revenue grade inverter P/N: SExxxxA-US000NNR2(for 760OW inverter.SE760OA-US002NNR2).
-40 version P/N: SExxxxA-USOOONNU4 (for 760OW mverter:5E7600A-US002NNU4).
dBA
F/"C
sola
SolarEdge Power Optimizer
Module Add -On For North America
WI I WNFAMNIII I 2 I,
PV power optimization at the module -level
— Up to 25% more energy
Superior efficiency (99.5%)
— Mitigates all types of module mismatch losses, from manufacturing tolerance to partial shading
— Flexible system design for maximum space utilization
— Fast installation with a single bolt
— Next generation maintenance with module -level monitoring
Module -level voltage shutdown for installer and firefighter safety
USA - GERMANY - ITALY - FRANCE - JAPAN - CHINA - ISRAEL - AUSTRALIA www.solaredge.us
Solar =@
Module Add -On for Forth America
P300 / P320 / P400 / P405
P300 I P320 I P400 P405
( (for high -power (for 72 & 96-cell (for thin film
(for 60-cell modules) - tin it mnrhdac) modules? I modules)
INPUT
Rated Input DC Powerl'l
300......................320...........,........,..400......................405................
W .,...
Absolute Maximum Input Voltage !
48 80 125
Vdc
(Voc at lowest temperature}
............................,..................., ...........................
...........
......
....i
MPPT Operating Range
18 - 48 I 8 ; 80 „ I 12,5 -105 1
.............,......,......
Vdc
Maximum Short Circuit Current Isc}
..............
ii 10 I.. 11....................................a_,,,_,,,,,,•_.
..........,....,.....
,,,Adc.._.
.......................................i....,,.................,....
Maximum DC Input Current
12.5 1..........13 75 125........................!
Adc
.....
Maximum Efficiency
Maximum
�................................... 99 5
e
1.............
a ........................
Weighted Efficiency........,.,,
98.8
Overvoltage Category
I II
I
OUTPUT DURING OPERATION(POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER)
Maximum Output Current 15 Adc
......................................60....................................... ............,............. ......
....... ......
Maximum Output Voltage 85 Vdc
OUTPUT DURING STANDBY (POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE4NVERT,ER OR SOLAREDGE INVERTER OFF)
Safety Output Voltage per Power I 1 Vdc
STANDARD COMPLIANCE
EMC FCC Part15 Class B, IEC61000 ,6.2: IEC61000 6-3
........................_.............................................
S* *.. IEC62109-1(class 11 safety): UL1741 i
....X..........I..................... �.... ........
RoHS I _ Yes
INSTALLATION SPECIFICATIONS
Maximum Allowed System Voltage
......................
1000
...........,........................................................................
Vdc
...........
Compatible inverters
{
All SolarEdge•Single Phase and Three Phase inverters
...................
I
128x152x27.5/
128x152x35/
128x152x48/
mm/In
Dimensions(WxLxH)
5x5.97x1.08
5x597x137
5x597x189
.........
Weight (inciudin cables
l
1.7 .......
930 / 2.05
........ .................
i 930 2 :05
In ut Connector
MC4 Compatible .........
,,.,,,
Output Wire Type /Connector
I
Double insulated; MC4 Compatible ................. ..
.......
Out ut Wlre Len th
p..............g
I
D.95 3.0 (..,., 1.2 / 3.9
I m / ft
......................I.........._...........,....�.......
OperafinBTemperatureRanBe
I ...............................
.-40-t85/ 40-+185
.................... ....................
! `C/,F
Protection Ratln
I
........ IP_....68 / ..NEMA6P
.... .............
....
Relative Humidity ................
0-100
.............
In Rated STC power of the module. Module of up to +5% power tolerance allowed.
PV SYSTEM DESIGN USING SINGLE PHASE THREE PHASE 208V THREE PHASE 480V
A SOLAREDGE INVERTERI2).
Minimum String Length^--- 8 10 18
Power Optimizers...............I..............................._.-.. ..
. . . .... . ..
Maximum String Length 25 25 50
(Power Optimizers?.. ....� ................. �.
Maximum Power per String j ._...5250 I.,... 6000..............1_ ....... 12.... i W
........ ...
Parallel Strings of Different Lengths
.. Orientations ...1................
.rOri. t t........................... e5.................................................................
R1 It is not allowed to mix P405 with P300/P400/P600/P700 in one string.
THE SNAPNRACK S TILE ROOF HOOK OFFERS A QUICK, COST EFFECTIVE
SOLUTION FOR MOUNTING ON S-TILE ROOFTOPS. THE SIMPLE DESIGN HAS BEEN
OPTIMIZED FOR SNAPNRACK AND THE HOOKS ARE BUILT INTO OUR SYSTEM
ENGINEERING AND UL LISTING, ONCE A TILE HAS BEEN REMOVED, THE BASE
PIECE IS BOLTED DOWN TO A RAFTER. ONCE THE BASE IS IN PLACE, THE TILE
HOOK ARM IS INSERTED INTO THE HOOK FEATURE IN THE BASE AND ROTATED
DOWN TOWARDS THE TRACK SO THAT THE BONDING CHANNEL NUT SNAPS INTO
THE CHANNEL. ONCE THE ARM IS ATTACHED TO THE BASE, SLIDE IT ON THE
BASE SO THAT IT ALIGNS WITH A LOW POINT IN THE S-TILES, SIMPLY TIGHTEN
IT IN PLACE AND REPLACE THE TILE THAT WAS REMOVED. WITH SOME TYPES OF
TILE YOU MAY WANT TO DO A LITTLE GRINDING TO HELP EVERYTHING FIT BACK
TOGETHER SMOOTHLY, BUT IN MANY CASES NO GRINDING IS REQUIRED.
INSTALLATIONS OF SNAPNRACK S TILE ROOF MOORS .492E LlMnTED TO A
MA)LIMUM WIND SPEED OF 12OMPH (IBC 2012) ARID A MA)aMUM
A' 7ACIHMENT SPAN OF 6FTo
SNAPNRACK
STANDARD RAIL
SNAPNRACK
BONDING
CHANNEL NUT
t" - 18 X 1.25" STAINLESS
STEEL FLANGE BOLT
SNAPNRACK BONDING
CHANNEL NUT
0
SNAPNRACK STANDARD RAIL
S-TILE, TYP
SNAPNRACK
S-TILE HOOK ARM
TILE BATTEN, TYP.-
ROOF DECKING, TYP.
A" LAG BOLTS WITH FLAT
STEP 1:
REMOVE TILES TO EXPOSE
ROOF DECKING.
SNAPNRACK S-TILE
HOOK ARM
fl�
REVISION:
SNAPNRACK
S-TILE HOOK BASE
f
ENSURE 2.5" MINIMUM
EMBEDMENT INTO
RAFTER, TYP.
RAFTER OR OTHER STRUCTURAL
ROOF MEMBER, TYP.
SNAPNRACK
STANDARD RAIL
SNAPNRACK S-TILE
HOOK BASE
STEP 3: -I
SLIDE THE S-TILE HOOK ARM
m' LAG BOLTS WITH
INTO THE HOOK ON THE BASE
AND ROTATE THE ARM TOWARDS
THE BASE TO SNAP THE CHANNEL
NUT INTO THE CAHNNEL. TIGHTEN
FLANGE BOLT HAND TIGHT. ALIGN
THE ARM WITH THE NEAREST VALLEY
IN THE TILES AND TIGHTEN BOLT TO
10-16 FT-LBS
FLAT WASHERS s ))
STEP 2: ROOF DECKING, TYP. LAG BOLTS WITH FLAT WASHERS
DRILL TWO is" PILOT HOLES INTO HOOK CAN BE OFFSET FROM
RAFTER. SEAL ROOF PENETRATIONS RAFTER UP TO 5" IN EITHER
WITH APPROPRIATE SELANT. RAFTER OR OTHER STRUCTURAL --'DIRECTION TO LINE UP WITH
FASTEN BASE TO ROOF WITH QTY. (2) ROOF MEMBER, TYP. LOW POINT IN S-TILES.
51.
36 LAG BOLTS WITH FLAT WASHERS.
n(��
S ap V �ack
pM moufflo g ftaftum
MAINSTREAM ENERGY CORP.
)BW�R6RSAN F"Y �0-0.B
""�R P �°"��°'s "`°"°�gP°'� °' "s"
_
DESIGNER: G McPheeters
D Ryan
DRAFTER: Y
APPROVED BY:
SCALE: DNS
PART NUMBER:
S100 PEN D14
DESCRIPTION:
SERIES 100 PEN DETAIL 14, S-TILE HOOK
REV
F
DATE: 031613
SCOPE OF WORK GENERAL NOTES LEGEND AND ABBREVIATIONS LE of CONTENTS
[PA7GE# DESCRIPTION
• SYSTEM SIZE: 6625W DC, 6000W AC ALL WORK SHALL COMPLY WITH CRC 2013,2013 CEC, 2013 CBC, MUNICIPAL SE SERVICE ENTRANCESOLAR MODULES COVER SHEET
• MODULES: (25) CANADIAN SOLAR: CS6P-265P CODE, AND ALL MANUFACTURERS'LISTINGS AND INSTALLATIONRAIL V-2.0 SITE PLAN
• INVERTER(S) INSTRUCTIONS.
(1) SOLAREDGE TECHNOLOGIES: SE6000 (240V) W/-ER-US • PHOTOVOLTAIC SYSTEM WILL COMPLY WITH 2013 CEC. MP MAIN PANEL PV-3.0 LAYOUT
OR A -US • ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH 2O13 CEC.. PV-3.1 LAYOUT
• RACKING: SNAPNRACK SERIES 100 UL; UNIVERSAL TILE • PHOTOVOLTAIC SYSTEM IS UNGROUNDED. NO CONDUCTORS ARE SOLIDLY - PV-4.0 ELECTRICAL
HOOK. SEE PEN D14 GROUNDED IN THE INVERTER. SYSTEM COMPLIES WITH 690.35. SP SUB -PANEL STANDOFFS &
• MODULES CONFORM TO AND ARE LISTED UNDER UL 1703. FOOTINGS PV-5.0 SIGNAGE
• INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.
• RACKING CONFORMS TO AND IS LISTED UNDER UL 2703. LC PV LOAD CENTER CHIMNEY
-_ • CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(E) AND 2012
= IFC 605.11:2. Q
= • ARRAY -DC CONDUCTORS ARE SIZED FOR DERATED CURRENT: SUNRUN METER - ATTIC VENT
• 9.23 -_AMPS MODULE SHORT CIRCUIT CURRENT. SM
• 14.42 AMPS DERATED SHORT CIRCUIT CURRENT (690.8 (a) & 690.8 (b)). FLUSH ATTIC VENT
---- - PM DEDICATED PV METER77
-- o? PVC PIPE VENT C 17 _-
N_
INVERTER(S) WITH ® = METAL PIPE VENT
IN INTEGRATED DC r!Ay 1 � Luigi
- DISCONNECT AND AFCI ® T-VENT
- _ - AC DISCONNECT(S)
ACC SATELLITE DISH
DC DISCONNECT(S) FO
FIRE SETBACKS
CB COMBINER BOX- HARDSCAPE
copy
INTERIOR EQUIPMENT — PL- PROPERTY LINE
LE a SHOWN AS DASHED SCALE: NTS sunrun
A' AMPERE
AC ALTERNATING CURRENT - _ --
AFCI ARC FAULT CIRCUIT INTERRUPTER GILBERT GORREIA, c10, cas
- AZIM AZIMUTH CA CL #750184
VICINITY -MAP - COMM-ri'!iTY DEv'ELOPMENT DEPARTMENT _ COMP COMPOSITION 2300 ZANKER ROAD, UNIT F, SAN JOSE, CA 95131
PHONE 408.746.3062
_ - BUILDINIG DIVISION - CUPERTINO _ DC DIRECT CURRENT FAx4oa.694.9zsa
i -„ t3reenleafDr
I - - - (E)
EXISTINGnry3, r;D EXT EXTERIOR CUSTOMER RESIDENCE:
ANP
69�kvArd {+ht, t of ^ians and specifications MUST be kept at the = _ FIRM FRAMING YOUZHONG LIU
Greenl'
during construction. It is unlawful io make any INT INTERIOR 20888 FARGO DR, CUPERTINO,
fir: c t�; alterations on same, or to deviate LBW LOAD BEARING WALL
v31. - : unbar D��,. . . . C 4
i �p f r +".rJ+n, �rithout approval from the Building Official. w MAG MAGNETIC
A 9501
,. p 9 P p ICE PANEL -
`otnLiar The r+ ;rn in of this Ian and's ecifications SHALL NOT
W SERVICE RO(ao ss t E
• ¢ 11 ny_+i to permit or t b an approvel of the violation MSP MA R°
pp 6gb jrq N#.
NOT TO SCALE U �I� - n
�. S8�Lf
�NTS
12
any provic. r of, .r i ity Ordinance or State Law. C ON CENTER
F. D�" i
-z s-, g�. PRE-FAB PRE -FABRICATED ;r e��F�` `DESIGNER:
— .— _
{{I` DATE ��( q'`ZGI PSF POUNDS PER SQUARE FOOT _ r� r+ TYLER KINCA�I�D.
'�� ktti ertandChlltl - + ia, . ° - RE d . D FOR CO - CE
PV PHOTOVOLTAIC +-�(I Ef htC. 949.705.3959
__Jiazelbrools:o,I-ar, • o iet9Pn�nrce��r: ,r . PERMIT NO. 1' %(il�p -' 2 TL TRANSFORMERLESS V3C U Dp
. I
TYP TYPICAL -Vic)We
d By: BIEL�j
V VOLTS
{ `' �► KE® BY W WATTS SHEET
*6;REV NAME, DATE COMMENTS COVER SHEET
i+
Garden Gate Qr`,Garclen.Gat`eUt� - ATE A
E Garden Gate Qf REV: A.4 5/12/2016
�{ !� i�Dt .., PLANNIN DEPT
° � qr I CUPERTINO PAGE PV_ 1 0
SITE PLAN - SCALE = 3/64" = 1'0"
T
AZIM
M
ZIM
PV AREA
Q
AR-01
18°
90°
76°
69.3
®
AR-02
180
180°
166°
34.7
AR-03
180
2700
2560
69.3
AR-04
18°
180°
166°
69.3
AR-05
18°
270°
2560
190.7
(N) A
(N)�
FIRE
(N)
(E
(E) FENCE
(N) ARRAY AR-01
sunrun
GILBERT CORREIA, C10, C46
(E) FENCE
CA CL #750184
2300 ZANKER ROAD, UNIT F, SAN JOSE, CA 95131
(N) ARRAY AR-02
PHONE 408.746.3062
FAX 408.894.9294
CUSTOMER RESIDENCE:
YOUZHONG LIU
20888 FARGO DR, CUPERTINO,
CA, 9501�4rz R-f,I
NOci
TEL))
CT NUMBER:
88p8WU
REVI�l�,`=�+ F
ftVClE �KrWCA�ID�I�'�1��
!
��wViOvue
f / ,7 949.705.31
. t�f�
FRAFTER.
RBIEL2
SHEET
SITE PLAN
REV: A.4 5/12/2016
PAGE PV-2.0
ROOF FRAME FRAME TYPE FRAME MAX FRAME OC ROOF EDGE MAX RAIL MAX RAIL DESIGN CRITERIA
ROOF TYPE ATTACHMENT ROOF HEIGHT
EXPOSURE MATERIAL SIZE SPAN SPACING ZONE SPAN OVERHANG MODULES:
AR-01 CONCRETE TILE [CURVED] UNIVERSAL TILE HOOK. SEE PEN D14 TWO STORY ATTIC WOOD RAFTER 2 X 8 15' - 0" 16" 3'- 0" 8' - 0" 2' - 8" CANADIAN SOLAR: CS6P-265P
AR-02 CONCRETE TILE [CURVED] UNIVERSAL TILE HOOK. SEE PEN D14 TWO STORY ATTIC WOOD RAFTER 2 X 8 15' - 0" 16" 3' - 0" 8' - 0" 2'-8" MODULE DIMS:
64.5" x 38.7" x 1.57"
AR-03 CONCRETE TILE [CURVED] UNIVERSAL TILE HOOK. SEE PEN D14 TWO STORY ATTIC WOOD RAFTER 2 X 8 15' - 0" 16" 3'- 0" 8' - 0" 2'- 8" MODULE CLAMPS:
Portrait: 13.39" - 16.14"
AR-04 CONCRETE TILE [CURVED] UNIVERSAL TILE HOOK. SEE PEN D14 = TWO STORY ATTIC WOOD RAFTER 2 X 8 15' -0 16" 3' - 0" 8' - 0" 2' - 8" Landscape: 7.87" - 9.84"
- - MAX DISTRIBUTED LOAD: 3 PSF
D1 - AR-01 - SCALE: 1/8" = 1'-0" D2 - AR-02 - SCALE: 1/8" = V-0" SNOW LOAD: 110 PSF
PITCH: 180 PITCH: 18' WIND SPEED:
AZIM:90° AZIM:180° 0 MPH 3-SEC GUST.
LAG SCREWS:
5/16"x3.5": 2.5" MIN EMBEDMENT
5'-6" I
- 5'-4" TYP
a
10'-101, I I I
I I 5' 4
5'-4" TYP
2 X 8 RAFTER 16" OC 1 I 2'-1"
2 X 8 RAFTER 16" OC ,
sunrun
D3 - AR-03 - SCALE: 1/8" = V-0" D4 - AR-04 - SCALE: 1/8" = V-0" �
PITCH: 18' PITCH: 18' GILBERT CORREIA, C10, C46
AZIM:2700 AZIM:180' CA CL #750184
® ® PHONE
E 408.7 ROAD, UNIT F, SAN JOSE, CA 98131
PHONE 408.746.3062
FAX 408.894.9294
- CUSTOMER RESIDENCE:
YOUZHONG LIU
20888 2 X 8 RAFTER 16" OC CA, 95014GO DR, CUPERTINO,
TEL. (408) 462-1188 APN #: ---
/
5' 411 TYP
4 6' I6 I iv1 I I I 1 4 5 `t r,. IWAY ! DESIGNER:
TYeER KINCAID
949.705.3959
,, -VIEWED FOR GO bRgPT�ts.lA� lCE
- i—
i�Pvis--wed H= g� L2,jj ,�/
3 7"
I SHEET
10'-9" 10'-3" 2 X 8 RAFTER 16" OC LAYOUT
REV: A.4 5/12/2016
PAGE PV-3.0
ROOF
FRAME
FRAME
MAX FRAME
OC
ROOF EDGE
MAX RAIL
MAX RAIL
DESIGN CRITERIA
MODULES:
ROOF TYPE
ATTACHMENT
ROOF HEIGHT
EXPOSURE
MATERIAL
FRAME TYPE
SIZE
SPAN
SPACING
ZONE
SPAN
OVERHANG
AR-05 CONCRETE TILE [CURVED]
UNIVERSAL TILE HOOK. SEE PEN D14
TWO STORY ATTIC WOOD
RAFTER
2 X 8 15' - 0" 16"
3' - 0" 8' - 0"
2' - 8"
CANADIAN SOLAR: CS6P-265P
MODULE DIMS:
64.5" x 38.7" x 1.57"
D5 - AR-06 - SCALE: 3/16" = 1'-0"
MODULE_CLAMPS:
PITCH:-18°
_ _ _
-- ----__—Laridscape
7:87" - 9.84"
MAX DISTRIBUTED LOAD: 3 PSF
SNOW LOAD: 0 PSF
27'
2'-5" -
-
-
WIND SPEED:
110 MPH 3-SEC GUST.
LAG SCREWS:
5/16"x3.5": 2.5" MIN EMBEDMENT
NOTE:
I
INSTALLERS TO VERIFY RAFTER
®I I I I I
I I
SIZE, SPACING AND SLOPED
I
SPANS, AND NOTIFY E.O.R. OF
ANY DISCREPANCIES BEFORE
2 X 8 RAFTER 16"
OC
i I i
i I I
PROCEEDING.
I
-�I--5'-4"ITYP I I I
ITH
6'-6"
T((
III III III
I i TIC
I;
32'-5"
—
sunrun
ROOF FRAMING DETAIL - SCALE: NTS
GILBERT CORREIA, C10, C46
CA CL #750184
2300 ZANKER ROAD, UNIT F, SAN JOSE, CA 95131
PHONE 408.746.3062
FAX 408.894.9294
RIDGE BOARD
CUSTOMER RESIDENCE:
YOUZHONG LIU
5/16" X 3.5" LAG SCREW.
20888 FARGO DR, CUPERTINO,
2 BOLTS PER PENETRATION
CA, 95014
CONCRETE TILE [CURVED] ROOF
TEL. (408) 462-1188 APN #: ---
PROJECT NUMBER:
SOLAR MODULE
y�4�2R$88LIU
TOP PLATE
C'c
SrYGhER:
RTYLER
AT"2X8
KINCAID
949.705.3959
RAFTERS, 16" O.C.
y
LOAD BEARING WALL
LAYOUT
REV: A.4 5/12/2016
PAGE PV=3.1
. 120%240VAC
SINGLE
PHASE
SERVICE
-1-009
EXISTING
200A MAIN
BREAKER
EXISTING
MAIN
FACILITY
PANEL
(END -FED)
LOADS
35APV -c-L-GROUND
BREAKER AT
OPPOSITE END `
OFBUSBAR
747
250VMBER
SOCKET
125ACONT|NUOUS
&
24OVMETER
2O0A.,FORM 28
3
(N)LOCKABLE �
BLADE TYPE
AC DISCONNECT
SQUARED
OU322RB
3R.GOA.2P
SOLARED8E
TECHNOLOG|ES:SE0000
(240V)N0'ER,USOR
A,US
GO0OWATT INVERTER
LOAD RATED DC
DISCONNECT &AFC|
2 JUNCTION BOX PVMOOULES
(25) MODULES
OPTIMIZERS WIRED IN (1) SERIES OF(15)
OPTIMIZERS AND (1) SERIES OF (10)
Lit! OPTIMIZERS
SOLAREDGE POWER OPTIMIZER
P30]
CONDUIT SC14EDULE
# CONDUIT CONDUCTOR NEUTRAL GROUND
1
NONE
(4) 10 AWG PV WIRE
NONE
(1) 10 AWG BARE COPPER.
3
3/4" EMT OR EQ UIV.
(2) 8 AWG THHNfTHWN-2
(1) 10 AWG THHNfrHWN-27(l)
8 AWG THHN/THWN-2
CANADIAN SOLAR:
OPEN CIRCUIT VOLTAGE 37.7 V
MAX POWER VOLTAGE 30.6 V
SHORT CIRCUIT CURRENT 9.23 A
OPTIMIZER CHARACTERISTICS
MIN INPUT VOLTAGE
8
VDC
MAX INPUT VOLTAGE
48
VDC
MAX OUTPUT CURRENT
1 15
ADC
SYSTEM CHARACTERISTICS''INVERTER 1
SYSTEM SIZE
6625 W
SYSTEM OPEN CIRCUIT VOLTAGE
15 V
SYSTEM OPERATING VOLTAGE
350 V
MAX ALLOWABLE DC VOLTAGE
500 V
SYSTEM OPERATING CURRENT
20.4 A
SYSTEM SHORT CIRCUIT CURRENT
1 30 A
PER CODE: 690.52
NOTES TO INSTALLER:
CIRCUIT STRING VOLTAGE.
PHONE 408.746.3062
FAX 408.894.929
6-12 AWG BARE 5116" -18 SS BOLT
CUSTOMER RESIDENCE:
COPPER WIRE SS SPLIT LOCK WASHER
YOUZHONG LIU
RROJECT NUMBER:
ND
tSS
BONDING
R KJ00AW
PINS ew
V I;_lV4
949.705.3959
NOTE:
ALL HARDWARE IS INCLUDED FROM MANUFACTURER
DRAFTER:
A MINIMUM OF ONE GROUND LUG IS TO BE INSTALLED ON EVERY
'RBIEL2
CONTINUOUS ROW OF MODULES
GROUNDING LUG MAY BE INSTALLED IN EITHER RAIL CHANNEL
GROUNDING LUG MAY BE INSTALLED SO GROUND WIRE IS PARALLEL
TO RAIL
SHEET
ELECTRICAL
~OR PERPENDICULAR
ENSURE SPLIT LOCK WASHER ISINSTALLED "" TOP ", COPPER WIRE
rPAGE
.0
LABEL LOCATION:
DC DISCONNECT, INVERTER
(PER CODE: CEC 690.35(F))
[To be used when inverter is ungrounded]
LABEL LOCATION:
AC DISCONNECT, POINT OF INTERCONNECTION
(PER CODE: CEC 690.17(E))
LABEL LOCATION:
AC DISCONNECT, POINT OF INTERCONNECTION
PER CODE: CEC 690.17(E), CB
LABEL LOCATION:
INVERTER, JUNCTION BOXES (ROOF), AC DISCONNECT
(PER CODE: CEC690.13.G.3 & CEC 690.13.G.4)
INVERTER 1
- - --------------
LABEL LOCATION: _
AC DISCONNECT, POINT OF INTERCONNECTION
(PER CODE: CEC690.54)
LABEL LOCATION:
POINT OF INTERCONNECTION
(PER CODE: CEC 705.12(D)(7))
[Not required if panelboard is rated not less than sum of ampere ratings
of all overcurrent devices supplying it]
LABEL LOCATION:
MARKINGS PLACED ON ALL INTERIOR AND EXTERIOR DC CONDUIT, RACEWAYS, ENCLOSURES,
AND CABLE ASSEMBLIES AT LEAST EVERY 10 FT, AT TURNS AND ABOVE/BELOW PENETRATIONS
AND ALL COMBINER/JUCTION BOXES. (PER CODE: IFC605.11.1.4)
'SOLAR DISCONNECT,
LABEL LOCATION:
DISCONNECT, POINT OF INTERCONNECTION
(PER CODE: CEC690.13(B))
LABEL LOCATION:
WEATHER RESISTANT MATERIAL, DURABLE ADHESIVE, UL969 AS STANDARD TO WEATHER
RATING (UL LISTING OF MARKINGS NOT REQUIRED), MIN %" LETTER HEIGHT ARIAL OR-----
SIMILAR FONT NON -BOLD, PLACED WITHIN THE MAIN SERVICE DISCONNECT, PLACED.ON.--
THE OUTSIDE OF THE COVER WHEN DISCONNECT IS OPERABLE WITH SERVICE PANEL
CLOSED. (PER CODE: CEC690.15, 690.13(B))
LABEL LOCATION:
POINT OF INTERCONNECTION
(PER CODE: CEC 705.12(D)(4))
�21 :10YA4 MIMI I
i -M
LABEL LOCATION:
CONDUIT, COMBINER BOX
(PER CODE: CEC690.31(G)(3)(4) & CEC 690.13(G)(4)
LABEL LOCATION:
DC DISCONNECT, INVERTER
(PER CODE: CEC690.53)
ADHESIVE FASTENED SIGNS:
• THE LABEL SHALL BE SUITABLE FOR THE ENVIRONMENT WHERE IT IS INSTALLED.
WHERE REQUIRED ELSEWHERE IN THIS CODE, ALL FIELD APPLIED LABELS, WARNINGS, AND
MARKINGS SHOULD COMPLY WITH ANSI Z535.4 [NEC 110.21(B) FIELD MARKING].
• ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IF PROPERLY ADHERED. VINYL SIGNS SHALL
BE WEATHER RESISTANT [IFC 605.11.1.31
PLACARD CREATION REQUIREMENTS:
• ALL SIGNAGE SHALL BE RED PLASTIC ENGRAVED WITH 1/2"
HIGH WHITE LETTERS.
CAUTION
POWER TO THIS BUILDING IS
ALSO SUPPLIED FROM THE
FOLLOWING SOURCES WITH
DISCONNECTS AS SHOWN
SOLAR PANELS ON ROOF
MAIN PANEL
SERVICE ENTRANCE AND PV �
BREAKER DISCONNECT
SUNRUN METER
AC DISCONNECT
INVERTER LOCATION
�z
RA
�E�,'IEV�IE.0 F
20888 FARGO DR, CUPERTINO, C& 95014
t ievle!wed
sunrun
GILBERT CORREIA, C10, C46
CA CL #750184
2300 ZANKER ROAD, UNIT F, SAN JOSE, CA 95131
PHONE 408.746.3062
FAX 408.894.9294
CUSTOMER RESIDENCE:
YOUZHONG LIU
20888 FARGO DR, CUPERTINO,
CA, 95014
8
Lr(488 42-1188 APN #: ---
T NUMBER:
88LIU
DESIGNER:
,� ETLfRII�AttD 949.705.3959
D -AFTER'7�'I tr
RBIEL2
SHEET
SIGNAGE
REV: A.4 5/12/2016 1
PAGE PV-5.0