DIR-2018-04b ATT Roof top
PROJECT DESCRIPTION CONSTRUCTION OF AN UNMANNED TELECOMMUNICATIONS FACILITY. 1. INSTALL (8) PANEL ANTENNAS 2. INSTALL (21) RRHS 3. INSTALL (2) PURCELL CABINETS STRUCTURAL NOTES 1. X-RAY SCAN ALL SLABS FOR REBAR AND POST -TENSIONING TENDONS PRIOR TO INSTALLING ANY ANCHORS (FOR EXAMPLE, EQUIPMENT RACK ANCHORS). IT IS NOT ACCEPTABLE TO CUT OR DAMAGE ANY TENDONS OR REBAR IN THE SLAB. 2. THIS SUBMITTAL IS REVIEWED FOR IMPACT TO PRIMARY STRUCTURE ONLY. CODE COMPLIANCE ALL WORK AND MATERIALS SHALL BE PERFORMED AND INSTALLED IN ACCORDANCE WITH THE CURRENT EDITIONS OF THE FOLLOWING CODES AS ADOPTED BY THE LOCAL GOVERNING AUTHORITIES. NOTHING IN THESE PLANS IS TO BE CONSTRUED TO PERMIT WORK NOT CONFORMING TO THESE CODES. 1. CALIFORNIA ADMINISTRATIVE CODES (INCL. TITLES 24 & 25) 2016 2. CALIFORNIA BUILDING CODE 2016 3. CALIFORNIA ELECTRICAL CODE 2016 4. CALIFORNIA MECHANICAL CODE 2016 5. CALIFORNIA PLUMBING CODE 2016 6. CALIFORNIA FIRE CODE 2016 7. LOCAL BUILDING CODE AMENDMENTS TO THE ABOVE. 8. CITY/ COUNTY ORDINANCES ALONG WITH ANY OTHER APPLICABLE LOCAL AND STATE LAWS AND REGULATIONS DISABLED ACCESS REQUIREMENTS FACILITY IS UNMANNED AND NOT FOR HUMAN HABITATION, ACCESSIBILITY REQUIREMENTS ARE NOT REQUIRED, IN ACCORDANCE WITH CALIFORNIA BUILDING CODE, CODE OF REGULATIONS, TITLE 24, PART 2, VOLUME 1, CHAPTER 11B, DIVISION 2, SECTION 116-203.5 OCCUPANCY AND CONSTRUCTION TYPE OCCUPANCY: U (UNMANNED) CONSTRUCTION TYPE: V -B FA:14290836 PTN: 3701AODMAW USID: TBD VICINITY MAP SITE NUMBER: CCL( SITE NAME: TA09 ROC 10335 TANTAU AVE CUPERTINO, CA 95014 Jurisdiction: CITY OF CUPER- SITE TYPE: ROOF TOP / DIRECTIONS FROM AT&T's OFFICE DIRECTIONS FROM. AT&Ts OFFICE AT 5001 EXECUTIVE PARKWAY, SAN RAMON, CA 1. HEAD NORTHEAST ON BISHOP DR TOWARD SUNSET DR 2. TURN RIGHT AT THE 1ST CROSS STREET ONTO SUNSET DR 3. USE THE RIGHT 2 LANES TO TURN RIGHT ONTO BOLLINGER CANYON RD 4. USE THE RIGHT LANE TO MERGE ONTO 1-680 S VIA THE RAMP TO SAN JOSE 5. MERGE ONTO 1-680 S 6. TAKE EXIT 12 FOR MISSION BLVD/STATE ROUTE 262 TOWARD 1-880 7. KEEP RIGHT AT THE FORK, FOLLOW SIGNS FOR MISSION BLVD W AND MERGE ONTO MISSION BLVD 8. KEEP LEFT AT THE FORK, FOLLOW SIGNS FOR INTERSTATE 880 S/SAN JOSE AND MERGE ONTO 1-880 S 9. USE THE RIGHT 2 LANES TO TAKE THE CALIFORNIA 237 W EXIT TOWARD MTN VIEW 10. CONTINUE ONTO CA -237 W 11. TAKE THE LAWRENCE EXPWY/CARIBBEAN DRIVE EXIT 12. KEEP LEFT, FOLLOW SIGNS FOR LAWRENCE EXPY 13. KEEP RIGHT TO CONTINUE TOWARD LAWRENCE EXPY 14. CONTINUE ONTO LAWRENCE EXPY 15. TURN RIGHT ONTO E HOMESTEAD RD (SIGNS FOR HOMESTEAD ROAD) 16. TURN LEFT ONTO N TANTAU AVE 17. TURN RIGHT DESTINATION WILL BE ON THE RIGHT PROJECT INFORMATION Property Information: Power Agency: Site Name: TA09 ROOFTOP PG&E Site Number: CCLO4410 1 MARKET STREET, SPEAR TOWER Site Address: 10335 TANTAU AVE SAN FRANCISCO, CA 94105 CUPERTINO, CA 95014 ph: (800) 743.5000 A.P.N. Number. 316-06-064 email: b6an@1borgesarch.com Current Zoning: P (MP)- PLANNED INDUSTRICAL ph: (916) 782-7200 ZONE Tax: (916) 773-3037 Jurisdiction: CITY OF CUPERTINO Telephone Agency: Latitude Sector A: 37'20' 6.594" 37.3351550 AT&T Longitude Sector A:-122'0' 34.9848 -122.0097180 525 MARKET STREET Latitude Sector B: 37'20' 41.00" 37.328056 SAN FRANCISCO, CA 94105 Longitude Sector B: -122.0' 24.50" -122.006806 ph: (800) 310-2355 Latitude Sector C: 37° 19' 38.54" 37.327372 Longitude Sector C:-122.0'23.83" -122.006619 Elevation: 169' AMSL Property Owner: APPLE ROBERT COLLEDGE RCOLLEDGE@APPLE.COM ph: 201-312-5076 PROJECT TEAM Applicant! Lessee: Architect: AT&T BORGES ARCHITECTURAL GROUP, INC. contact: TY EDDY 1478 STONE POINT DRIVE, SUITE 350 5001 EXECUTIVE PARKWAY ROSEVILLE, CA 95661 SAN RAMON, CA 94583 contact: BRIAN K. WINSLOW email: te1501@att.com email: b6an@1borgesarch.com ph: (925)337.0760 ph: (916) 782-7200 Tax: (916) 773-3037 Site Acquisition: J5 INFRASTRUCTURE PARTNERS contact: MASAKO HILL email: mhill@j5ip.com ph: (415) 533-2540 Construction Design Manager - RF Engineer: NSB: AT&T VINCULUMS SERVICES, INC. contact: GIL SHAHZADA contact: DAN RICO email: GS262U@atl.com email: drico@vinculums.com ph: (925) 353-6078 ph: (925) 876-6227 GENERAL CONTRACTOR NOTES DO NOT SCALE DRAWINGS THESE DRAWINGS ARE FORMATTED TO BE FULL SIZE AT 30"x24" (DI). CONTRACTOR SHALL VERIFY ALL PLANS AND EXISTING DIMENSIONS AND CONDITIONS ON THE JOBSITE AND SHALL IMMEDIATELY NOTIFY THE ARCHITECTIENGINEER IN WRITING OF ANY DISCREPANCIES BEFORI PROCEEDING WITH THE WORK OR MATERIAL ORDERS OR BE RESPONSIBLE FOR THE SAME. m O r T m O D O ----An RnAn APPLE TA09 BUILDING 9 ENLARGED -9 AOU BASEMENT GARAGE PLAN T7 ENLARGED TA09 A011 ROOFTOP PLAN 1478 STONE POINT DRIVE, SUITE 350 ROSEVILLE CA 95891 9187827200 TEL 91877330]7 FAX 115 J5 INFRASTRUCTURE PARTNERS 1150 BALLENA BLVD, 0259 ALANEDA, CA 94501 l4qj4�wm;;w;'-4,at&t 6001 EXECUTIVE PARKWAY SAN RAMON, CA 94683 1 1012WZ017 100%CDSubni 1 0 WllV2017 W%CDSubmIMI A 00/07/2017 100%ZD Subm l REV DATE DESCRIPPON STAMP -ARC SASl Byi m5 !.09-39 0 F - DRAWN BY: JVM PROJECT NO.: T -1B501-7 CHECK BY: D.K.W. SHEETTITLE !�\ (P) (P) RF-FRIENDI TO MATCH AD. STEALTH SCRE BY APPLE -TYF HVAC STEALTI I ROOFTOP POWER & FIBER RUNS: IWER PLANT TO PURCELLS: CONDUIT FROM AT&T POWER PLANT TO ANTENNA TYP. OF (3) CONDUIT FROM AT&T POWER PLANT TO PURCELLS ONDUIT FROM AT&T POWER PLANT TO PURCELLS RUNK FROM PURCELLS TO ANTENNA SECTORS, TYP. TING TO BE VERIFIED IN FIELD AND PROVIDED BY BUILDING MPOE ROOM (P) AT&T FIBER EXTENSION FROM BUILDING MPOE ROOM TO ROOFTOP EQUIPMENT - CONDUIT & ROUTING PROVIDED BY APPLE (P) AT&T INTERIOR EQUIPMENT RACK IN (E) 02D2 ROOM - RACK PROVIDED BY APPLE - NO POWER PROVIDED FOR AT&T PER CURRENT EQUIPMENT LAYOUT �Q�ryryy I —— na19 N N AT&T A-03 AasS 30' 15' 0 30' 60' 30' 15' 0 30' 60' SECTOR C 6 ENLAROOF PLAN 1 =30'-0" ENLARGED BASEMENT GARAGE PLAN 1" 30' 0" 30'-0'RGED 1478 STONE POINT DRIVE. SUITE 350 ROSEVILLE CA 05001 010 782 72110 TEL 018779337 FAX lj�s J5 INFRASTRUCTURE PARTNERS 1150 BALLENA BLVD. 4259 ALAMEDA. CA 94501 at&t 6001 EXECUTIVE PARKWAY SAN RAMON. CA 0463 1 10/2912017 100%CD Submitlal 0 001141M17 90% CD Submitlal A 0010712017 —% ZD Submittal REV DATE DESCRIPTION STAMP 4.�C0ARCM± `�y0 SA Buc�,f4 •A. 1575 A n, 09-30• '17i-CFkff'o0 DRAWN BY: JVM PROJECTNO.:T-10501-7 CHECK BY: B.K.W. SHEET TIRE ENLARGED SITE PLAN SHEET NO. 1.00O IR ON .N T .i .19 1 0 1 1 0 1 I .N EIIIII 01111111111111 oil 0 0 MIR 0 0 .N j1 0n \ an son om NEU e 0 a .N IORIEII! .N NWII I .w IN �■ 0 0 oil 0 0 ORO 0 0 .� 0 0 Eli 0 0 .N 0 .l0 0 0 0 MAI 0 0 0 .l0 0 0 .IW 0 0 .l9 0 .w �mi I I .o 00 .lo 0 i►\\\\\\\\R1 .. NEIllrtn oil 0n MEN no 0 11111110 MIR 0 ELNR� .. my 0 0 .IR 1 1 1 1 I MIR .O 0 0 ow 1 ■� �I■I■II■I■■I■ 77 I�I■■I■I�I■I■•I�I. BUILDING MPOE ROOM (P) AT&T FIBER EXTENSION FROM BUILDING MPOE ROOM TO ROOFTOP EQUIPMENT - CONDUIT & ROUTING PROVIDED BY APPLE (P) AT&T INTERIOR EQUIPMENT RACK IN (E) 02D2 ROOM - RACK PROVIDED BY APPLE - NO POWER PROVIDED FOR AT&T PER CURRENT EQUIPMENT LAYOUT �Q�ryryy I —— na19 N N AT&T A-03 AasS 30' 15' 0 30' 60' 30' 15' 0 30' 60' SECTOR C 6 ENLAROOF PLAN 1 =30'-0" ENLARGED BASEMENT GARAGE PLAN 1" 30' 0" 30'-0'RGED 1478 STONE POINT DRIVE. SUITE 350 ROSEVILLE CA 05001 010 782 72110 TEL 018779337 FAX lj�s J5 INFRASTRUCTURE PARTNERS 1150 BALLENA BLVD. 4259 ALAMEDA. CA 94501 at&t 6001 EXECUTIVE PARKWAY SAN RAMON. CA 0463 1 10/2912017 100%CD Submitlal 0 001141M17 90% CD Submitlal A 0010712017 —% ZD Submittal REV DATE DESCRIPTION STAMP 4.�C0ARCM± `�y0 SA Buc�,f4 •A. 1575 A n, 09-30• '17i-CFkff'o0 DRAWN BY: JVM PROJECTNO.:T-10501-7 CHECK BY: B.K.W. SHEET TIRE ENLARGED SITE PLAN SHEET NO. 1.00O ERICSSON RRUS 11 REMOTE RADIO UNIT COLOR: WHITE DIMENSIONS: 19.7" TALL X 17" WIDE X 7.25" DEEP (INCLUDING SUNSHIELD) WIEGHT: +1•50LBS, (INCLUDING MOUNTING HARDWARE) MFR'S STANDARD BRACKETS RRUS 11 WITH P1000 UNISTRUT AS ALTERNATE TOP VIEW RAYCAP DC648-60-18 FIBER DC POWER CONNECTION COLOR: LIGHTTAN DIMENSIONS: 18.17' WIDE X 20.06' TALL X 6.37' DEEP WIEGHT:-1-43.5LBS. (INCLUDING MOUNTING HARDWARE) t6114* l it' -B" '14' P-1000 UNISTRUT, TYP t1-61 • .,-Fr • SIDE VIEW FRONT VIEW U -BOLT ATTACHMENTS @ PIPE MOUNTS. LAG SCREWS @WOOD FRAMING. MACH BOLTS@ METAL FRAMING. WEDGE ANCHORS @ CONC. 16 DC6 SURGE SUPPRESSION 431256' =1'41' MFR'S STANDARD2,- 3.3" ,- ,- 8.8" MOUNTING •'{�I •I{'�I -------------� BRACKETS ANTENNA = CCI TPA-65R-BU4AA WINDAREA= 3.9s1 17" I m i3 7.25" 10 314' =1'-0' P1000 UNISTRUT AS ALTERNATE .n y✓",S ATTACHMENT � ,✓ ), SUNSHIELD I � 1 FRONT SIDE O I ANTENNA = CCI HPA-33R-BUU-H4-K —_----------) SIDE VIEW WINDAREA= 5.054 FRONTVIEW WEIGHT = 52.Ibs/23.7kg ERICSSON RRUS II REMOTE RADIO UNIT CCI HPA-33R-BUU-H4-K 19 1 112'=1'-0' 15 314' =1'-0' ERICSSON RRUS-E2 REMOTE RADIO UNIT ERICSSON WCS RRU-32 COLOR: GRAY DIMENSIONS: 20.39" TALL X 18.50" WIDE X 7.48" DEEP (INCLUDING SUNSHIELD) MODEL: RRUS 32 B30 WIEGHT: +/- 53 LBS. (INCLUDING MOUNTING HARDWARE) COLOR: WHITE DIMENSIONS: 26.7' TALL X 12.1" WIDE X 6.7" DEEP (INCLUDING SUNSHIELD) ANTENNA (WHEN RRUS-E2 IS MOUNTED BEHIND) WIEGHT: +/-69 LBS. (INCLUDING MOUNTING HARDWARE) MFR'S STANDARD MOUNTING BRACKETS MFRS STANDARD MOUNTING 811 RRUS-E2 WITH SUNSHIELD BRACKETS V 1, RRUS 32 WITH SUNSHIELD PIOOO UNISTRUT AS ALTERNATEATTACHMENT --� ANTENNA (WHEN RRUS-32 IS MOUNTED BEHIND) — — — — — — — — — — — TOPVIEW 6.7" U i i MFR'S STANDAR MOUNTING BRACKETS I I P1000 UNISTR--\\ ALTERNATEAS ATTACHMENT Lh I � I iv D I ----- — J SIDE VIEW FRONT VIEW MFR'S STANDARD MOUNTING BRACKETS M 0 N (V J ------------- FRONT VIEW TOP VIEW SIDE VIEW ERICSSON WCS RRUS-32 REMOTE RADIO UNIT ERICSSON RRUS-E2 REMOTE RADIO UNIT 1� ti i FRONT SIDE ANTENNA = CCI TPA-65R-BU4AA WINDAREA= 3.9s1 WEIGHT = 69.4lbs/31.5kg CCI-TPA-65R-BU4AA 10 314' =1'-0' AC CONNECTION PANEL DC DISTRIBUTION CABINET ACU+ CONTROLLER RECTIFIERS / CONVERTORS DC -12 SURGE SUPPRESSOR (TYP. OF 2) CIENA (P) AT&T 200A ELEC — PANEL & AC FEEDS TO AT&T EQUIPMENT - PROVIDED BY APPLE (P) 23"WX20"D AT&T EQUIPMENT RACK EMERSON NETSURE 721 DC POWER SYSTEM: • AC CONNECTION PANEL • DC DISTRIBUTION CABINET y • ACU CONTROLLER Aau • RECTIFIERS I CONVERTERS • CIENA • (2) DC -12 SURGE SUPPRESSORS • (4) BATTERIES (+/- 9.6 GALLONS OF ELECTROLYTE) :13 (P) QUAD GFCI FOR PURCELLS MOUNTED TO 1 -BEAM (P) 15'-6"L STEEL I -BEAM, SPANNING H -FRAME STRUCTURE BEAMS, TYP. OF (2) FOR CABINET MOUNTING 12 (4) BATTERIES (1 STRING) �.. N 1/2" DIA. "HILTI" (KB -TZ) KWIK BOLT CONCRETE EXPANSION ANCHOR MIN. EMB. (TOTAL s: SLAB FLOOR OF 6) (6 REO'D IN EARTHQUAKE QUAKEE ZONES) 41 21 0 41 81 NOTE: ALL ANCHORS TO MEET ICC -ES 1/4"=l 1_x,1 9 AT&T POWER PLANT RACK ESR -1917 SPECIFICATIONS 6 ROOFTOP EQUIPMENT ROOM ur = r -o• v4•= r-0• 1478 STONE POINT DRIVE, SUITE 350 ROSEVILLE CA 85061 0167827200 TEL 9107733037 FAX 11 sb J5 INFRASTRUCTURE PARTNERS II OBALLENA BLVD,#259 ALAMEDA.CA94501 at&t 5001 EXECUTIVE PARKWAY SAN RAMON, CA 84583 1 10/23/2017 100% CID SObmi9sl 0 0WIQW17 00% CD S,bmM l A 09107/2017 .% ZD S6bmAWl REV DATE DESCRIPTION STAMP ANC 4�tp SA ' 1195 9 DRAWN BY: NM PROJECT NO.: T-16501-7 CHECK BY: B.K.W. SHEETTITLE ENLARGED EQUIPMENT LAYOUT SHEETNO. A-012 PROPOSED AT&T EQUIPMENT LEGEND O AT&T ANTENNA (CCI HPA-65R-BUU-H4-K) Qz AT&T ANTENNA (CCI HPA-33R-BUU-H4-K) O AT&TANTENNA(CCI TPA-65R-BU4AA) sO RRH (RRUS-32) ps RRH(RRUS-11) © PIPE MOUNT O STANDOFF ANTENNA MOUNT, SITE PRO SBWM-312 Q3 SURGE SUPPRESSOR (RAYCAP DC -6-46-60-8F) (D RRH(RRUS-E2) Emil., c meE+a7 •E,eA. ,ea-9.1691./Za:>=+¢vesov:c'sx[ •BWaF 44en-lural b.'t aalrMAt Ftle s,.nr- . ue.nmo Ggleea •Sxle9 rai-0.120'^13.0 rmswY •Cmmm i±ssn+]Wdpnb4 •F:lea-�prsapbtpaaNAsc'+'W+'itinwut •AFe rant laiMvm lnw rine-Nrrre m.�! •Ivb!:a'�-inlu,rm laitvcMW:-.a.`.. •(i{m:eBzlrtN m'•n:ABdw�h •9a+s-frua�rs abauvssee»1 •Pm lwxOn-(elbc)aNe •DoatNgn-�•tqH Wed., a = 011 RFSCHEDULE TsseaaicSprYN brfi OUd23'nifv oatorrarixPrdtleR�Pm;•'t •fMV2T eta-;ym,e:ilse{COW:,riN<ant SECTOR ANTENNA MODEL NO. 1--IMUTF1 RAD CENTE A Al TPA-65R-BU4AA 40 65'-9" L p A2 TPA-65R-BU4AA 40 65-9" A • t wlJztemawunMt vi:erg par •C.yiULK irolraWa*ewaaeonciue ULTSn)-110y:OZ" IxiGSAL"IOW5473 VJCS •Ca'T� wcVC aitav psr •J101000, FCC x:ES [sp6bnu%,IBaW:o2aaaciev •WI TdWt4e Gfi0] Bl HPA-33R-BUU-H4-K 300 651-9" B E 82 HPA-33R-BUU-H4-K 300 65'9" T A B3 HPA-33R-BUU-H4-K 300 65'9" B4 HPA-33ft-BUU-H4-K 300 6519" G Cl TPA-65R-BU4AA 225 6519" A M C2 TPA-65R-BU4AA 225 659" M A Emil., c meE+a7 •E,eA. ,ea-9.1691./Za:>=+¢vesov:c'sx[ •BWaF 44en-lural b.'t aalrMAt Ftle s,.nr- . ue.nmo Ggleea •Sxle9 rai-0.120'^13.0 rmswY •Cmmm i±ssn+]Wdpnb4 •F:lea-�prsapbtpaaNAsc'+'W+'itinwut •AFe rant laiMvm lnw rine-Nrrre m.�! •Ivb!:a'�-inlu,rm laitvcMW:-.a.`.. •(i{m:eBzlrtN m'•n:ABdw�h •9a+s-frua�rs abauvssee»1 •Pm lwxOn-(elbc)aNe •DoatNgn-�•tqH Wed., a = 011 •0aumm,xl �aavnroWmEm59i5 �xlS'e•565•atlFiaa T•vr>r.�faen'es TsseaaicSprYN brfi OUd23'nifv oatorrarixPrdtleR�Pm;•'t •fMV2T eta-;ym,e:ilse{COW:,riN<ant 4rcq prdwF • t00Akeevv faetth WOs,Y so-mP �w�'-eu�wwrswaoxarav:+amisN.q vrtl,2TewaomxaMWlon •tive>*«-Pemswi'sp�swmzmeys .4n�>,-cmnmeri.s N9bepeo E,reutlten rns.»ea+leY:a, x.M 23' epPyrwnt etii ¢tia, •Fpa-T-al;labryb4saimF.wb]5:ags wish 23' a W a,:an iai cpar. anlpriry}B-¢lgreatvutylW 11 P'-S� . �.x pyo �y,� •Ga,ccan:wrnllauwe za»aria,Vaa 'nveT .ca;e.,ei„3-3,amvtmv.da>r n>t remsa• cam aa. o,.�... +/-247 LBS. (NOT LOADED) ACP—Termbgiee—OimboOmr �PavvRfry o-'saHRa�4e4 45(STACKED) nviaW lWAtlokl /(E)K.VA. $13rldnrlTS • t wlJztemawunMt vi:erg par •C.yiULK irolraWa*ewaaeonciue ULTSn)-110y:OZ" IxiGSAL"IOW5473 VJCS •Ca'T� wcVC aitav psr •J101000, FCC x:ES [sp6bnu%,IBaW:o2aaaciev •WI TdWt4e Gfi0] •to,c1a,11oevRa�ara:leri•abxupl •ReHSarap46it rrw.3B ULCS<fdi4CWA-t .umrad l4lrs�I yai,o �,�.�l at.rrt!sde _ PURCELL LTE CONDITIONED CABINET VAULT -FLEX 2 -TIER COLOR LIGHT TAN A/C READ: NONE -DC POWER ONLY DIMENSIONS: 2'-1" WIDE x 5'-4" TALL x 2'-4" DEEP WEIGHT: +/-247 LBS. (NOT LOADED) 45(STACKED) /(E)K.VA. 40 1/2" 2.6" 2'-6" 2'-2112` 1 1 - 1 1 I \\ BOLTING PATTERN TOP VIEW \\ CLEARANCES UNISTRUT MOUNTED TO (E) SCREEN STRUCTURE ) I 8 A -01J 36"CLEAR ACCESS Twa Tien s.-- PURCELL � ( CABINET � J u Y p@Iilpma'7l4Ptt4TY0?. 13 (E)ROOFTOP ASR A -01B A/C DOOR ENLARGED PANEL SECTOR ELEVATION (SIM.) sds— ,tu PI INTH -41 RF -FRIENDLY FRP PANELS -PROVIDED BYAPPLE r I T T-w»L {\ Nm� /) SIDE VIEW FRONT VIEW W 2' 1' 0 2' 4' PURCELL LTE CONDITIONED CABINET ANTENNA PLAN - SECTOR A 1/2"=1'-0" 15 yr=r9" 011 -1 - RF -FRIENDLY FRP PANE -PROVIDED BY APPLE S AZi,�� yR a (E)RVAC SCREEN (E) WAC SCREEN STRUCTURE Z(E)ROOFTOP (E) HVI (E) ROOFTOP (E) HVAC SCREEN 5�G J�ryryS 1478 STONE POINT DRNE, SUITE 350 ROSEVILLE CA 95081 9107027200 TEL 0167733037 FAX 3 J5 INFRASTRUCTURE PARTNERS 1150 BALLENA BLVD, #359 ALAMEDACA94501 at&t 5001 EXECUTIVE PARKWAY SAN RAMON, CA 04503 1 10/23/2017 100%CD SubmiOal 0 0011412017 0% CD Sub dW A 09107/2017 100%ZDSubm'Blel REV DATE DESCRIPTION STAMP S1 -Q ARCyIi \QiA R F^ IAS 114 IF OF CAl6 DRAWN BY: JVM PROJECT NO.; T-16501-7 CHECK BY: B.KW. SHEET TITLE ENLARGED EQUIPMENT LAYOUT STRUCTURE N RF DATA SHEET: CCL04410 2' 1' 0 2' 4' W SHEET NO ISSUE: 1.0 AT&T RF SCHEDULE ANTENNA PLAN — SECTOR B 1/2"=V-0.1ANTENNA PLAN — SECTOR C 13 5 2=ro 17 NOT TO SCALE 112•=1'-0' _- A-013 e. 45(STACKED) /(E)K.VA. (E)HVAC SCREEN 11 r I T T-w»L {\ Nm� /) SIDE VIEW FRONT VIEW W 2' 1' 0 2' 4' PURCELL LTE CONDITIONED CABINET ANTENNA PLAN - SECTOR A 1/2"=1'-0" 15 yr=r9" 011 -1 - RF -FRIENDLY FRP PANE -PROVIDED BY APPLE S AZi,�� yR a (E)RVAC SCREEN (E) WAC SCREEN STRUCTURE Z(E)ROOFTOP (E) HVI (E) ROOFTOP (E) HVAC SCREEN 5�G J�ryryS 1478 STONE POINT DRNE, SUITE 350 ROSEVILLE CA 95081 9107027200 TEL 0167733037 FAX 3 J5 INFRASTRUCTURE PARTNERS 1150 BALLENA BLVD, #359 ALAMEDACA94501 at&t 5001 EXECUTIVE PARKWAY SAN RAMON, CA 04503 1 10/23/2017 100%CD SubmiOal 0 0011412017 0% CD Sub dW A 09107/2017 100%ZDSubm'Blel REV DATE DESCRIPTION STAMP S1 -Q ARCyIi \QiA R F^ IAS 114 IF OF CAl6 DRAWN BY: JVM PROJECT NO.; T-16501-7 CHECK BY: B.KW. SHEET TITLE ENLARGED EQUIPMENT LAYOUT STRUCTURE N RF DATA SHEET: CCL04410 2' 1' 0 2' 4' W SHEET NO ISSUE: 1.0 AT&T RF SCHEDULE ANTENNA PLAN — SECTOR B 1/2"=V-0.1ANTENNA PLAN — SECTOR C 13 5 2=ro 17 NOT TO SCALE 112•=1'-0' _- A-013 (C� (E) SECTION OF HVAC SCREEN TO BE REMOVED AND REPLACED BY 67'-g• TOP OF (E) PENTH1.OU (E) PAREPET LEVEL -Y" (E)LEVEL OS (ROOF) -- —_412A (E) LEVEL 04Y _____ 28�24I, (E)LEEL0 1__5'2' � (E)LEVELO ° (E)GRADE LEVEL NORTH VIEW ANTENNA ELEVATION -EXISTING 15 (P) AT&T EQUIPMENT BEHIND STEALTH SCREEN, TYP. K J N 1 �� (P)A7&TRRH, TYP.OF (C � p)SECTOR'A' F �\�`\ E /}7 D C J7\ STEALTH 16 (P)AT&T TPA-65RBU4AA (E)HVAC SCREEN — t1-67'8' TOP OF (E)SCRE (P)RF-FRIENDLY PANEL, BY APPLE ^ \ ANTENNA, TYP.OF (2) SECTOR'A' I +1-6T11'�,_ ___ /(� TOP OF (P) AT&T ANTENN—AS+ 55'-8'/ _ (E) PARAPET LEV—ELY 5 (E)LEVEL 05 (ROOO F) ___—_ )LEL 04"-2+(EEV LEVEL A_ (E)LEVEL�03 (ELEVEL 0 --° (E) GRADE LEVEL 13 NORTH VIEW ANTENNA ELEVATION -PROPOSED 1478 STONE POINT DRIVE, SUITE 356 ROSEVILLE CA 95661 016]827200 TEL 9167733037 FAX J5 INFRASTRUCTURE PARTNERS 1150 BALLENA BLVD. H259 ALANEDA CA 94501 i �ti 1 ia"-&t a� 500 EXECUTIVE PARKWAY SAN RAMON. CA 94563 1 10/23/2017 100%CD Submittal 0 09/1412017 9G% CD Submittol A 09107/2017 100% ZD Submittal REV DATE DESCRIPTION O-ABL•y7 v PQ SL @dl' fC> tt Q 09-50� qrf OF 11 . DRAWN BY: JVM PROJECT NO.: T-16501-7 CHECK BY: B.K.W. SHEETTITLE ELEVATIONS SECTOR A BHEET NO 14 I REFER TO it FOR ENLARGED A-016 ELEVATION i 1 —mss; 1117�'T lm— , q_nEST ELEVATION TO SCALE ENLARGED WEST ELEVATION - EXISTING 9 ENLARGED WEST ELEVATION - PROPOSED 3132' = i'-0" /- 6r-8. TOP OF (E) SCREEN tAVW �F (P) AT&T ANTENNAS al- EgR NTENNA RAD CENT _ S5'iB' t (E)ARAPE-L)* (E) LEVEL OS ROOF _ 41'-Y �E)LEVEL04 r J2Y (E) LEF03 15'-2+ (E)LEVEL. (E)GRADE LEVEL—+ 1478 STONE POINT DRIVE, SUITE 350 ROSEVILLE CA SMI 918 ]82 R00 TEL S1B 7733037 FAX J5 INFRASTRUCTURE PARTNERS 1 I50 BALLENA BLVD, #259 ALAMEDA,CA94501 07-r�voo,',,, at&t 5001 EXECUTIVE PARKWAY SAN RAMON, CA 94- 1 10133/2017 100%CDSub [ 0 0114IM17 W%CDSubmilel A 00/07/2017 100%ZDSubm l REV DATE DESCRIPTION STAMP . SB -AB H% Ly�0.0 5L 8'... 1535 0 ^09-SO.O TAUS. DRAWN BY: JVM PROJECTNO.:T-18501-7 CHECK BY: B.KW. SHEETTNLE ELEVATION SECTOR B SHEET NO. 0 00CE) vi j o 0 (E) SECTION OF HVAC SCREEN TO BE / REMOVED AND REPLACED BY -_-_ H_fiT-B'w_ TOP OF (E) PENTHOUSE (E) PARAPET LEV� 52_ A (E) LEVEL 05 (ROOF) ,E) 1011 04 IN'* (E)LEVEL03 15� (E)LEVEL 02 -_-_-D� (E)GRADE LEVEL 15 SOUTH VIEW ANTENNA ELEVATION - EXISTING 3132• =1'-0' (P) AT&T EQUIPMENT BEHIND STEALTH SCREEN, TYP. I n l t (P)AT&T RRH, TYP.OF (G� nH (�J) (K) l 13 SOUTH VIEW ANTENNA ELEVATION -PROPOSED TOP OF (E) SCRSCREEN 11 6T-0-0'� // TOPOF(P) AT&T ANTENNAST .__ it -S5' _/, (AT&T ANTENNA RAD CENTE-RY (E)PARAPETLEVEL r 52� (E) LEVEL 05 (ROOF) (E) LEVEL 04T (E)LEVE. (E)LEVELO (E) GRADE LEVEL* 1478 STONE POINT DRIVE, SUITE 350 ROSENILLE CA 95901 918 782 ]200 TEL 8197733037 FAX J5 INFRASTRUCTURE PARTNERS I I50 BALLENA BLVD, #259 ALAMEDA, CA94501 c- at&t 5001 EXECUTIVE PARKWAY SAN RAMON, CA 94583 1 10/23/2017 100%CD Submi9nl 0 09/14!2017 90% CD Submi l A MM7/2017 100%ZOSubmi841 REV DATE DESCRIPTION STAMP (IVAROy� tO SL 842. i 535 FD DRAWN BY: NM PROJECT NO.: T-18501-7 CHECK BY: B.KW. SHEETTITLE ELEVATIONS SECTOR C SHEET NO. A-016 L (E) HIS 6X6X1/4', l U.O.N. (P) 1/2' A307 BOLT, OF (4) EA. CONNE( A307 BOLT. NP. (P) W6X9 A992 STEEL BEAM CONNECTION ON 3' iCELL CABINET (E) SCREEN N (E) HSS (P)11- SBWM- STAND-OFF M 6X6X1/4', NP. U.O.N.—� fm"21:.""' GALVANIZED PURCELL MOUNTED TO STEEL I -BEAM - SECTION MOUNTING SITE -PRO 20 SBWM-312, FASTENED TO(E)6"STEEL BEAM PROVIDED BY APPLE PER STRUCTURAL (E) HIS 6X6X1/4-, NP. DRAWINGS NP. (2) AT EA. ANTENNA 8 ANTENNA PLAN, MOUNTPER U.O.N. MANUFACTURER'S Aon (P)1/2' A307 BOLT, NP. (E) HSS6z6 PER SECTOR OF (4) EA. CONNECTION 2��\ F' 8" MIN. 19 17 13 GALVANIZED INSIDE CABINET (P) W6X9 A992 STEEL BEAM B.O. (E) BEAM Irk (P) e 1' 1• (P) 8" STAND-OFF (P) RRH, PER PER e e 1 RFSCHEDULE, ri. MOUNTING ANTENNA PLAN, (P) (4)1/2" HOLLO BOLT A-017 (P) FASTENING AT MOUNPER SITE -PRO MMO1, MOUNT PER A —_� 19 MANUFACTURER'S FASTENED TO (E) 6- MANUFACTURER'S ABANDONED HOLES IN MM01, SPECS DO NOT USE FOR MOUNT STEEL BEAM, NP. /1 SPECS, NP. OF (7) (P)THICK 4X9X7/4'A36 I I STEEL PLATE 19 STEEL BEAM MOUNTED TO H -FRAME B -B - SECTION 3' = T-0' (P)(P)1/2' A307 BOLT OF (4) EA. CONNE( (P) (2)1/2' HO BOLT LHBM12 INSTALLED PE ESR -3330 (P) THICK 4X9X7/4" A36 STEEL PLATE STEEL BEAM MOUNTED TO H -FRAME A -A - SECTION SBWM-312 STAND OFF MOUNT - SECTION 12 3'=1-0• $ 112•=1,-0• (P)11- STAND-OFF MOUNTING SITE -PRO (P) (4)1/2' HOLLO BOLT LHBM12#1, INSTALLED PER ESR -3330 SBWM-312, FASTENED TO(E)6"STEEL BEAM PROVIDED BY APPLE PER STRUCTURAL (p) RRH, PER DRAWINGS NP. (2) AT EA. ANTENNA 8 ANTENNA PLAN, MOUNTPER MANUFACTURER'S Aon SPECS, NP. OF (7) (E) HSS6z6 PER SECTOR STAND-OFF MOUNT 8" MIN. 19 17 13 GALVANIZED INSIDE CABINET B.O. (E) BEAM Irk (P) e (P) PURCELL CABINET, NP. OF (2) (P)ANTENNA PER (E) 6' STEEL PER e e 1 RFSCHEDULE, ri. BETWEEN H -FRAME STRUCTURE BEAM ASSEMBLY (P) (4)1/2" HOLLO BOLT A-017 (P) FASTENING AT MOUNPER ;. _�J LHBM12#1, INSTALLED A —_� 19 MANUFACTURER'S ABANDONED HOLES IN MM01, SPECS DO NOT USE FOR MOUNT SECTION A 10 15 OFF MOUNT - SECTION 1112'=1'-0' A-012 A-012 Q Z A-017 (P) W6X9, NP. 8. MI -1-81/2" CUR i BETWEEN (t ANTENNA & ` SCREEN (E) RF -FRIENDLY SCREEN PROVIDED BY APPLE — (P) U -BOLTS AT PIPE MOUNT (P) PIPE MOUNT (E) 6- STEEL BEAM, NP. (P)11" SBWM-312 STAND-OFF MOUNT (E)HS ft6 GALVANIZED 6 BLV 0 (P) (2)1/2' HOLLO BOLT LHBM12#1, INSTALLED PER ESR -3330 SECTION A NP. I I I I ROOFTOP PROPOSED EQUIPMENT WEIGHT ROOFTOP PURCELL CABINET = 2471bs (X2) SIAD = 401bs 6601 = 401bS (X3) AIR PLENUM = 201bS I -BEAM = 3881bs (x2) TOTAL = 1,4501bS -"'\ ( 13 RRH MOUNT AT SCREEN - SECTION �ANTENNA MOUNT ATSCREEN -SECTION PURCELLS AT SCREEN -ENLARGED ELEVATION 314'=1-0' ' 1478 STONE POINT DRIVE. SUITE 350 ROSEVILLE CA 05681 0167827200 TEL 010 773 3037 FAX 113� 5 J5 INFRASTRUCTURE PARTNERS 1150 BALLENA BLVD, #259 ALAMEDA. CA 94501 at&t 6001 EXECURVE PARKWAY SAN RAMON, CA 04503 1 10/23/2017 100%CD SubmNel i 0 MlIV2017 90% DO SOb.l A 00107/2017 100%ZDSu.m] REV DATE DESCRIPTION STAMP �SC9 Ah'Cg7l �`p S BBC fi No.Cll OF CIL6O DRAWN BY: NM PROJECT NO.: T-10501-7 CHECK BY: B.K.W. SHEETTITLE ENLARGED ELEVATION & DETAILS SHEET NO. A-017 (P) PIPE MOUNT (P) (4)1/2' HOLLO BOLT LHBM12#1, INSTALLED PER ESR -3330 (E) SCREEN PROVIDED BY APPLE WALL 710 (P)6601 INSIDE (P) 8' MM01 STAND-OFF MOUNT (E)fi'STEEL CABINET, NP. OF (3) (P) 8' MM01 (E) HSS6z6 (E) HSS6z6 STAND-OFF MOUNT GALVANIZED GALVANIZED INSIDE CABINET (P) e (P) PURCELL CABINET, NP. OF (2) U -BOLTS (E) 6' STEEL PER e e BETWEEN H -FRAME STRUCTURE BEAM ASSEMBLY (P) (4)1/2" HOLLO BOLT A-017 (P) FASTENING AT ;. _�J LHBM12#1, INSTALLED A —_� 19 PER ESR -3330 ABANDONED HOLES IN MM01, DO NOT USE FOR MOUNT SECTION A MM01 STAND OFF MOUNT - SECTION 1112'=1'-0' 20 (P) PURCELL (E) 5' STEEL NP. I I I I ROOFTOP PROPOSED EQUIPMENT WEIGHT ROOFTOP PURCELL CABINET = 2471bs (X2) SIAD = 401bs 6601 = 401bS (X3) AIR PLENUM = 201bS I -BEAM = 3881bs (x2) TOTAL = 1,4501bS -"'\ ( 13 RRH MOUNT AT SCREEN - SECTION �ANTENNA MOUNT ATSCREEN -SECTION PURCELLS AT SCREEN -ENLARGED ELEVATION 314'=1-0' ' 1478 STONE POINT DRIVE. SUITE 350 ROSEVILLE CA 05681 0167827200 TEL 010 773 3037 FAX 113� 5 J5 INFRASTRUCTURE PARTNERS 1150 BALLENA BLVD, #259 ALAMEDA. CA 94501 at&t 6001 EXECURVE PARKWAY SAN RAMON, CA 04503 1 10/23/2017 100%CD SubmNel i 0 MlIV2017 90% DO SOb.l A 00107/2017 100%ZDSu.m] REV DATE DESCRIPTION STAMP �SC9 Ah'Cg7l �`p S BBC fi No.Cll OF CIL6O DRAWN BY: NM PROJECT NO.: T-10501-7 CHECK BY: B.K.W. SHEETTITLE ENLARGED ELEVATION & DETAILS SHEET NO. A-017 (E) TA09 SCREEN PROVIDED BY APPLE (P)6601 INSIDE I (E)fi'STEEL CABINET, NP. OF (3) BEAM, TVP. (P) SIAD & (P) AIR PLENUM INSIDE CABINET (P) PURCELL CABINET, NP. OF (2) (E) 6' STEEL (P) 15'-6'L STEEL I -BEAM, SPANNED BEAM' NP. BETWEEN H -FRAME STRUCTURE BEAM 12 8,(P) STEEL I -BEAM, NP. OF (2) A-017 (P) FASTENING AT ;. _�J CONNECTIONS, —_� 19 P PWT' P R— FIB 20 (P) PURCELL (E) 5' STEEL CONNECTION TO BEAM. NP, A-017 (P) W6X9, NP. NP. I I I I ROOFTOP PROPOSED EQUIPMENT WEIGHT ROOFTOP PURCELL CABINET = 2471bs (X2) SIAD = 401bs 6601 = 401bS (X3) AIR PLENUM = 201bS I -BEAM = 3881bs (x2) TOTAL = 1,4501bS -"'\ ( 13 RRH MOUNT AT SCREEN - SECTION �ANTENNA MOUNT ATSCREEN -SECTION PURCELLS AT SCREEN -ENLARGED ELEVATION 314'=1-0' ' 1478 STONE POINT DRIVE. SUITE 350 ROSEVILLE CA 05681 0167827200 TEL 010 773 3037 FAX 113� 5 J5 INFRASTRUCTURE PARTNERS 1150 BALLENA BLVD, #259 ALAMEDA. CA 94501 at&t 6001 EXECURVE PARKWAY SAN RAMON, CA 04503 1 10/23/2017 100%CD SubmNel i 0 MlIV2017 90% DO SOb.l A 00107/2017 100%ZDSu.m] REV DATE DESCRIPTION STAMP �SC9 Ah'Cg7l �`p S BBC fi No.Cll OF CIL6O DRAWN BY: NM PROJECT NO.: T-10501-7 CHECK BY: B.K.W. SHEETTITLE ENLARGED ELEVATION & DETAILS SHEET NO. A-017 (P) DC -6 SURGE SUPPRESSOR MOUNTED TO (P) UNISTRUT ON (E) H -FRAME (P) RRUS32, MOUNT PER MANUFACTURER'S SPECS, TYP. OF (4) PER SECTOR ndl (P) (3) 2' POWER CONDUIT FROM; POWER PLANT IN PENTHOUSE TO SECTOR, ROUTE TO BE VERIFIED 4'-0" 4'-Y (P) RRUSE2, MOUNT (P) 8' STAND-OFF MOUNTING PWPWR— PER MANUFACTURER'S SITE -PRO MM01, FASTENED ( I SPECS, TYP. OF (1) PER TO (E) 6' STEEL BEAM, TYP. IB ( SECTOR 13 A-012 ) (2) AT RRH MOUNTS I Adt] 4'4' Y •/-1'-8" I I I I ROOFTOP - 13 ENLARGED SECTOR ELEVATION -SECTOR B 1478 STONE POINT DRIVE. SUITE 350 ROSEVILLE CA 9501 9187827200 TEL 9107]33037 FAX 115 J5 INFRASTRUCTURE PARTNERS I IM BALLENA BLVD. #259 ALAM@DA. CA 94501 ._. _ at&t 5001 EXECUTIVE PARKWAY SAN RAMON. CA 04583 1 10123/2017 100%Co submetal 0 091141201] 0% CD SubAimal A 09107/2017 100%ZD Submdtal REV DATE DESCRIPTION STAMP _ EB A@Ch7ji yooSA eu 535 f,7 • C3_3� 4 !f OF CAUL DRAWN BY: NM PROJECT NO.: T-10501.7 CHECK BY: B.K.W. SHEETTITLE ENLARGED ELEVATIONS SHEET NO. A-01 _I PWPWR— PW PWR— PWR PW PWR— PW IB — FIB B I FIB FIB IB FIB o a _ ( (P) RRUSit, MOUNT PER MANUFACTURER'S SPECS, TYP. OF (3) PER SECTOR 19 A-012 4 Z 3 � I 3 0 0 (E) 6" STEEL BEAM, 3 TYP f&T I (P) (3) 2' FIBER CONDUIT FROM PURCELLS TO J FIELD 3 SECTOR, ROUTE TO BE VERIFIED IN FIELD (P) ANTENNA PER RF SCHEDULE, MOUNTPER MANUFACTURER'S SPECS, TYP. OF (4) THIS SECTOR Aa6z — PWFPW IB (E)6- STEEL BEAM, TYR I I I I ROOFTOP - 13 ENLARGED SECTOR ELEVATION -SECTOR B 1478 STONE POINT DRIVE. SUITE 350 ROSEVILLE CA 9501 9187827200 TEL 9107]33037 FAX 115 J5 INFRASTRUCTURE PARTNERS I IM BALLENA BLVD. #259 ALAM@DA. CA 94501 ._. _ at&t 5001 EXECUTIVE PARKWAY SAN RAMON. CA 04583 1 10123/2017 100%Co submetal 0 091141201] 0% CD SubAimal A 09107/2017 100%ZD Submdtal REV DATE DESCRIPTION STAMP _ EB A@Ch7ji yooSA eu 535 f,7 • C3_3� 4 !f OF CAUL DRAWN BY: NM PROJECT NO.: T-10501.7 CHECK BY: B.K.W. SHEETTITLE ENLARGED ELEVATIONS SHEET NO. A-01 _I (P) RRUS11, MOUNT PER MANUFACTURER'S SPEC! TYP. OF (3) PER SECTOR (P)RRUS32, MOUNT PER MANUFACTURER'S SPEC'. TYP. OF (4) PER SECTOR (P) (3) 2- POWER CONDUIT FF POWER PLANT IN PENTHOUE SECTOR, ROUTE TO BE VERI 4''-W 1 (P) RRUSE2, MOUNT (P) 8• STAND-OFF MOUNTING I PER MANUFACTURER'S SITE -PRO MM01, FASTENED TO corse TVR _ 111 PFR (E) 6" STEEL BEAM, TYP. (2) AT 4'-T 13 ENLARGED SECTOR ELEVATION - SECTOR C SECTOR A SIMILAR 1470 STONE POINT OPINE, SUITE 350 ROSEVILLE CA 85091 0107027200 TEL 9107733037 FAX rets J5 INFRASTRUCTURE PARTNERS 1150 BALLENA BLVD, 4259 ALAMEJA CA 94501 at&t 5001 EXECUTNE PARKWAY SAN RAMON, CA 04503 1 10/2312017 100%CDSobm l 0 00114!2017 W%CDSub.i.1 A 000NM17 100%ZDSubmM.1 REV DATE DESCRIPTION STAMP E,�SL0 ARCyA o�4y5A BOC f' P l 9_)U POf CA DRAWN BY: NM PROJECT NO.: T-16501-7 CHECK BY: B.N.W. SHEET TITLE ENLARGED ELEVATIONS SHEET NO. FxAlllpe ELECTRICAL NOTES GENERAL REQUIREMENTS: 1. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE LATEST RULES AND REGULATIONS OF THE NATIONAL ELECTRICAL CODE AND ALL STATE AND LOCAL CODES. NOTHING IN THESE PLANS OR SPECIFICATIONS SHALL BE CONSTRUED AS TO PERMIT WORK NOT CONFORMING TO THE MOST STRINGENT OF THESE CODES. SHOULD CHANGES BE NECESSARY IN THE DRAWINGS OR SPECIFICATIONS TO MAKE THE WORK COMPLY WITH THESE REQUIREMENTS, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING AND CEASE WORK ON PARTS OF THE CONTRACT WHICH ARE AFFECTED. 2. THE CONTRACTOR SHALL MAKE A SITE VISIT PRIOR TO BIDDING AND CONSTRUCTION TO VERIFY ALL EXISTING CONDITIONS AND SHALL NOTIFY ARCHITECT IMMEDIATELY UPON DISCOVERY OF ANY DISCREPANCIES. THE CONTRACTOR ASSUMES ALL LIABILITY FOR FAILURETO COMPLY WITH THIS PROVISION. 3. THE EXTENT OF THE WORK IS INDICATED BY THE DRAWINGS, SCHEDULES, AND SPECIFICATIONS AND IS SUBJECT TO THE TERMS AND CONDITIONS OF THE CONTRACT. THE WORK SHALL CONSIST OF FURNISHING ALL LABOR, EQUIPMENT, MATERIALS, AND SUPPLIES NECESSARY FOR A COMPLETE AND OPERATIONAL ELECTRICAL SYSTEM. THE WORK SHALL ALSO INCLUDE THE COMPLETION OF ALL ELECTRICAL WORK NOT MENTIONED OR SHOWN WHICH IS NECESSARY FOR SUCCESSFUL OPERATION OF ALL SYSTEMS. 4. THE CONTRACTOR SHALL PREPARE A BID FOR A COMPLETE AND OPERATIONAL SYSTEM, WHICH INCLUDES THE COST FOR MATERIAL AND LABOR. 5. WORKMANSHIP AND NEAT APPEARANCE SHALL BE AS IMPORTANT AS THE OPERATION. DEFECTIVE OR DAMAGED MATERIALS SHALL BE REPLACED OR REPAIRED PRIOR TO FINAL ACCEPTANCE IN A MANNER ACCEPTABLETO OWNER AND ENGINEER. 6. COMPLETE THE ENTIRE INSTALLATION AS SOON AS THE PROGRESS OF THE WORK WILL PERMIT. ARRANGE ANY OUTAGE OF SERVICE WITH THE OWNER AND BUILDING MANAGER IN ADVANCE. MINIMIZE DOWNTIME ON THE BUILDING ELECTRICAL SYSTEM. 7. THE ENTIRE ELECTRICAL SYSTEM INSTALLED UNDER THIS CONTRACT SHALL BE DELIVERED IN PROPER WORKING ORDER. REPLACE WITHOUT ADDITIONAL COST TO THE OWNER, ANY DEFECTIVE MATERIAL AND EQUIPMENT WITHIN ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE 8. ANY ERROR, OMISSION OR DESIGN DESCREPANCY ON THE DRWINGS SHALL BE BROUGHT TO THE ATIENBON OF THE ENGINEER FOR CLARIFICATION OR CORRECTION BEFORE CONSTRUCTION. 9. 'PROVIDE' INDICATES THAT ALL ITEMS ARETO BE FURNISHED, INSTALLED AND CONNECTED IN PLACE 10. CONTRACTOR SHALL SECURE ALL NECESSARY BUILDING PERMITS AND PAY ALL REQUIRED FEES. EQUIPMENT LOCATION: 1. THE DRAWINGS INDICATE DIAGRAMMATICALLY THE DESIRED LOCATIONS OR ARRANGEMENTS OF CONDUIT RUNS, OUTLETS, EQUIPMENT, ETC., AND ARE TO BE FOLLOWED AS CLOSELY AS POSSIBLE PROPER JUDGEMENT MUST BE EXERCISED IN EXECUTING THE WORK SO AS TO SECURETHE BEST POSSIBLE INSTALLATION IN THE AVAILABLE SPACE LIMITATIONS OR INTERFERENCE OF STRUCTURE CONDITIONS ENCOUNTERED. 2 IN THE EVENT CHANGES IN THE INDICATED LOCATIONS OR ARRANGEMENTS ARE NECESSARY, DUE TO FIELD CONDITIONS IN THE BUILDING CONSTRUCTION OR REARRANGEMENT OF FURNISHINGS OR EQUIPMENT, SUCH CHANGES SHALL BE MADE WITHOUT COST. PROVIDING THE CHANGE IS ORDERED BEFORE THE CONDUIT RUNS, ETC., AND WORK DIRECTLY CONNECTED TO THE SAME IS INSTALLED AND NO EXTRA MATERIALS ARE REQUIRED. 3. LIGHTING FIXTURES ARE SHOWN IN THEIR APPROXIMATE LOCATIONS ONLY.COORDINATE THE FIXTURE LOCATION WITH MECHANICAL EQUIPMENT TO AVOID INTERFERENCE 4. COORDINATE THE WORK OF THIS SECTION WITH THAT OF ALL OTHER TRADES, WHERE CONFLICTS OCCUR, CONSULT WITH THE RESPECTIVE CONTRACTOR AND COME TO AGREEMENT AS TO CHANGES NECESSARY, OBTAIN WRITTEN ACCEPTANCE FROM ENGINEER FOR THE PROPOSED CHANGES BEFORE PROCEEDING. SHOP DRAWINGS: 1. N/A UNLESS NOTED OTHERWISE SUBSTITUTIONS: I. NO SUBSTITUTIONS ARE ALLOWED TESTS: 1. BEFORE FINAL ACCEPTANCE OF WORK, THE CONTRACTOR SHALL INSURE THAT ALL EQUIPMENT, SYSTEMS, FIXTURES, ETC., ARE WORKING SATISFACTORILY AND TO THE INTENT OF THE DRAWINGS. PERMITS: 1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR TAKING OUT AND PAYING FOR ALL REQUIRED PERMITS, INSPECTION AND EXAMINATION WITHOUT ADDITIONAL EXPENSETO THE OWNER. GROUNDING: I. THE CONTRACTOR SHALL PROVIDE A COMPLETE, AND APPROVED GROUNDING SYSTEM INCLUDING ELECTRODES, ELECTRODE CONDUCTOR, BONDING CONDUCTORS, AND EQUIPMENT CONDUCTORS AS REQUIRED BY ARTICLE 250 OF THE NATIONAL ELECTRICAL CODE. 2. CONDUITS CONNECTED TO EQUIPMENT AND DEVICES SHALL BE METALICALY JOINED TOGETHER TO PROVIDE EFFECTIVE ELECTRICAL CONTINUITY. 3. FEEDERS AND BRANCH CIRCUIT WIRING INSTALLED IN A NONMETALLIC CONDUIT SHALL INCLUDE A CODE SIZED GROUNDING CONDUCTOR HAVING GREEN INSULATION. THE GROUND CONDUCTOR SHALL BE PROPERLY CONNECTED AT BOTH ENDS TO MAINTAIN ELECTRICAL CONTINUITY. 4. REFER TO GROUND BUS DETAILS. PROVIDE NEW GROUND SYSTEM COMPLETE WITH CONDUCTORS, GROUND ROD AND DESCRIBED TERMINATIONS. 5. ALL GROUNDING CONDUCTORS SHALL BE SOLID TINNED COPPER AND ANNEALED#2 UNLESS NOTED OTHERWISE, 6. ALL NON -DIRECT BURIED TELEPHONE EQUIPMENT GROUND CONDUCTORS SHALL BE #2 STRANDED THHN )GREEN) INSULATION. 7. ALL GROUND CONNECTIONS SHALL BE MADE WITH'HYGROUND" COMPRESSION SYSTEM BURNDY CONNECTORS EXCEPT WHERE NOTED OTHERWISE. B. PAINT AT ALL GROUND CONNECTIONS SHALL BE REMOVED. 9. GROUNDING SYSTEM RESISTANCE SHALL NOT EXCEED 5 OHMS. IF THE RESISTANCE VALUE IS EXCEEDED, NOTIFY THE OWNER FOR FUTURE INSTRUCTION ON METHODS FOR REDUCING THE RESISTANCE VALUE SUBMIT TEST REPORTS AND FURNISH TO SMART SMR ONE COMPLETE SET OF PRINTS SHOWING "INSTALLED WORK'. UTILITY SERVICE: 1. TELEPHONE AND ELECTRICAL METERING FACILITIES SHALL CONFORM TO THE REQUIREMENTS OF THE SERVING UTILITY COMPANIES. CONTRACTOR SHALL VERIFY SERVICE LOCATIONS AND REQUIREMENTS. SERVICE INFORMATION WILL BE FURNISHED BY THE SERVING UTILITIES. 2. CONFORM TO ALL REQUIREMENTS OF THE SERVING UTILITY COMPANIES. PRODUCTS: 1. ALL MATERIALS SHALL BE NEW. CONFORMING WITH NEC, ANSI, NEMA, AND THEY SHALL BE U.L. LISTED AND LABELED. 2. CONDUIT: A) RIGID CONDUIT SHALL BE U.L. LABEL GALVANIZED ZINC COATED WITH ZINC INTERIOR AND SHALL BE USED WHEN INSTALLED IN OR UNDER CONCRETE SLABS, IN CONTACT WITH THE EARTH, UNDER PUBLIC ROADWAYS, IN MASONRY WALLS OR EXPOSED ON BUILDING EXTERIOR, RIGID CONDUIT IN CONTACT W BH EARTH SHALL BE 1/2 LAPPED WRAPPED WITH HUMS WRAP PROCESS NO. 3. B) ELECTRICAL METALLIC TUBING SHALL U.L LABEL FITTINGS SHALL BE COMPRESSION TYPE. EMT SHALL BE USED ONLY FOR INTERIOR RUNS. C) FLEXIBLE METALLIC CONDUIT SHALL HAVE U.L LISTED LABEL AND MAY BE USED WHERE PERMITTED BY CODE FITTINGS SHALL BE "JAKE' OR "SQUEEZE' TYPE. SEAL TIGHT FLEXIBLE CONDUIT. ALL CONDUIT EXCESS OF SIX FEET IN LENGTH SHALL HAVE FULL SIZE GROUND WIRE D CONDUIT RUNS MAY BE SURFACE MOUNTED IN GEEING OR WALLS UNLESS INDICATED OTHERWISE CONDUIT INDICATED SHALL RUN PARALLEL OR AT RIGHT ANGLES TO CEILING, FLOOR OR BEAMS. VERIFY EXACT ROUTING OF ALL EXPOSED CONDUIT WITH ARCHITECT PRIOR TO INSTALLING. E) ALL UNDERGROUND CONDUITS SHALL BE PVC SCHEDULE 40 )UNLEES NOTED OTHERWISE) AT A MINIMUM DEPTH OF 24" BELOW GRADE F) ALL CONDUIT ONLY )C.O.) SHALL HAVE PULL ROPE. G) CONDUITS RUN ON ROOFS SHALL BE INSTALLED ON 44 REDWOOD SLEEPERS, 6'4Y' ON CENTER, SET IN NON -HARDENING MASTIC. 3. ALL WIRE AND CABLE SHALL BE COPPER, 600 VOLT,#12 AWG MINIMUM UNLESS SPECIFICALLY NOTED OTHERWISE ON THE DRAWINGS. CONDUCTORS #10 AWG AND SMALLER SHALL BE SOLID. CONDUCTORS #8 AWG AND LARGER SHALL BE STRANDED. TYPE THHN INSULATION USED UNLESS CONDUCTORS INSTALLED IN CONDUIT EXPOSED TO WEATHER, IN WHICH CASE TYPE THW N INSULATION SHALL BE USED. 4. PROVIDE GALVANIZED COATED STEEL BOXES AND ACCESSORIES SIZED PER CODE TO ACCOMMODATE ALL DEVICES AND WIRING. 5. DUPLEX RECEPTACLES SHALL BE SPECIFICATION GRADE WITH WHITE FINISH )UNLESS NOTED BY ENGINEER), 20 AMP, 125 VOLT, THREE WIRE GROUNDING TYPE NEMA 5-20R. MOUNT RECEPTACLE AT+12' ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED ON DRAWINGS OR IN DETAILS. WEATHERPROOF RECEPTACLES SHALL BE GROUND FAULT INTERRUPTER TYPE WITH SIERRA #W PD -8 UFT COVERPLATES. 6. TOGGLE SWITCHES SHALL BE 20 AMP, 120 VOLT AC, SPECIFICATION GRADE WHITE )UNLESS NOTED OTHERWISE) FINISH. MOUNT SWITCHES AT 149- ABOVE FINISHED FLOOR. 7. PANELBOARDS SHALL BE DEAD FROM SAFETY TYPE WITH AMI -BURN SOLDERLFSS COMPRESSION APPROVED FOR COPPER CONDUCTORS, COPPER BUS BARS, FULL SIZED NEUTRAL BUS, GROUND BUS AND EQUIPPED WITH QUICK -MAKE QUICK -BREAK BOLT -IN TYPE THERMAL MAGNETIC CIRCUIT BREAKERS. MOUNT TOP OF THE PANELBOARDS AT 6'J" ABOVE FINISHED FLOOR. PROVIDE TYPE WRITTEN CIRCUIT DIRECTORY. 8. ALL CIRCUIT BREAKERS, MAGNETIC STARTERS AND OTHER ELECTRICAL EQUIPMENT SHALL HAVE AN INTERRUPTING RATING NOT LESS THAN MAXIMUM SHORT CIRCUIT CURRENT TO WHICH THEY MAY BE SUBJECTED. 9. GROUND RODS SHALL BE COPPER CLAD STEEL, 5/8" ROUND AND 10' LONG. COPPERWELD OR APPROVED EQUAL INSTALLATION: 1. PROVIDE SUPPORTING DEVICES FOR ALL ELECTRICAL EQUIPMENT, FIXTURES, BOXES, PANEL. ETC., SUPPORT WMINARIES FROM UNDERSIDE OF STRUCTURAL CEILING, EQUIPMENT SHALL BE BRACED TO WITHSTAND HORIZONTAL FORCES IN ACCORDANCE WITH STATE AND LOCAL CODE REQUIREMENTS. PROVIDE PRIOR AUGNMENT AND LEVELING OF ALL DEVICES AND FIXTURES. 2 CUTTING, PATCHING, CHASES, OPENINGS: PROVIDE LAYOUT IN ADVANCE TO ELIMINATE UNNECESSARY CUTTING OR DRILLING OF WALLS, FLOORS CEILINGS, AND ROOFS. ANY DAMAGE TO BUILDING STRUCTURE OR EQUIPMENT SHALL BE REPAIRED BY THE CONTRACTOR. OBTAIN PERMISSION FROM THE ENGINEER BEFORE CORING. 3. IN DRILLING HOLES INTO CONCRETE WHETHER FOR FASTENING OR ANCHORING PURPOSES, OR PENETRATIONS THROUGH THE FLOOR FOR CONDUIT RUNS, PIPE RUNS, ETC., IT MUST BE CLEARLY UNDERSTOOD THATTENDONS AND/OR REINFORCING STEEL WILL NOT BE DRILLED INTO, CUT OR DAMAED UNDER THE CIRCUMSTANCES. 4. LOCATION OF TENDONS AND/OR REINFORCING STEEL ARE NOT DEFINITELY KNOWN AND THEREFORE MUST BE SEARCHED FOR BY APPROPRIATE METHODS AND EQUIPMENT VIA X-RAY OR OTHER DEVICES THAT CAN ACCURATELY LOCATE THE REINFORCING AND/OR STEEL TENDONS. 5. PENETRATIONS IN RRE RATED WALLS SHALL BE FIRE STOPPED IN ACCORDANCE WITH THE REQUIREMENTS OF THE C.B.C. PROJECT CLOSEOUT: 1. UPON COMPLETION OF WORK, CONDUCT CONTINUITY, SHORT CIRCUIT, AND FALL POTENTIAL GROUNDING TESTS FOR APPROVAL SUBMIT TEST REPORTS TO PROJECT MANAGER. CLEAN PREMISES OF ALLS DEBRIS RESULTING FROM WORK AND LEAVE WORK IN A COMPLETE AND UNDAMAGED CONDITION. 2 PROVIDE PROJECT MANAGER WITH ONE SET OF COMPLETE ELECTRICAL"AS INSTALLED" DRAWINGS AT THE COMPLETION OF THE JOB, SHOWING ACTUAL DIMENSIONS, ROUTINGS AND CIRCUITS. - 3. ALL BROCHURES, OPERATING MANUALS, CATALOG, SHOP DRAWINGS, ETC., SHALL BE TURNED OVER TO OWNER AT JOB COMPLETION. GROUNDING NOTES: I. ALL DETAILS ARE SHOWN IN GENERALTERMS. ACTUAL GROUNDING INSTALLATION REQUIREMENTS AND CONSTRUCTION ACCORDING TO SITE CONDITIONS. 2. ALL GROUNDING CONDUCTORS:#2 AWG SOLID BARE TINNED COPPER WIRE UNLESS OTHERWISE NOTED. 3. GROUND BAR LOCATED IN BASE OF EQUIPMENT WILL BE PROVIDED, FURNISHED AND INSTALLED BY THE VENDOR. 4. GROUND BARS: A) EQUIPMENT GROUND BUS BAR )EGB) LOCATED AT THE BOTTOM OF ANTENNA POLE/MAST FOR MAKING GROUNDING JUMPER CONNECTIONS TO COAX FEEDER CABLES SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR. JUMPERS )FURNISHED BY OWNERS) SHALL BE INSTALLED AND CONNECTED BY ELECTRICAL CONTRACTOR. 5. ALL GROUNDING INSTALLATIONS AND CONNECTIONS SHALL BE MADE BY ELECTRICAL CONTRACTOR. 6. OBSERVE N.E.C. AND LOCAL UTILITY REQUIREMENTS FOR ELECTRICAL SERVICE GROUNDING. 7. GROUNDING ATTACHMENT TO TOWER SHALL BE AS PER MANUFACTURER'S RECOMMENDATIONS OR AT GROUNDING POINTS PROVIDED )2 MINIMUM). 8. GROUNDING AT PPC CABINET SHALL BE VERTICALLY INSTALLED. 9. ALL GROUNDING FOR ANTENNAS SHALL BE CONNECTED SO THAT IT WILL BY-PASS MAIN BUSS BAR. 10. ALL EMT RUNS SHALL BE GROUNDED AND HAVE A BUSHING, NO PVC ABOVEGROUND. 11. USE SEPARATE HOLES FOR GROUNDING AT BUSS BAR. NO "DOUBLE -UP" OF LUGS. 12. POWER AND TELCO CABINETS SHALL BE GROUNDED )BONDED)TOGETHER. 13. NO LB'S ALLOWED ON GROUNDING. 14. PROVIDE STAINLESS STEEL CLAMP AND BRASS TAGS ON COAX AT ANTENNAS AND DOGHOUSE 1476 STONE POINT DRIVE, SUITE 350 ROSEVILLE CA 95881 010 782 7200 TEL 9187733037 FAX loo li 5 J5 INFRASTRUCTURE PARTNERS I ISO BALLENA BLVD. 9159 ALAMEDACA94501 at&t :l 5001 EXECUTNE PARKWAY SAN RAMON, CA 04583 1 10/23/2017 100%CD SubmeNl 0 W11412017 00%CDSubrt l A 00107/2017 100%ZDSubmk WI REV DATE DESCRIPTION DRAWN BY: JVM PROJECT NO.: T-10501.7 CHECK BY: B.K.W. SHEET TITLE GENERAL ELECTRICAL NOTES SHEET NO. E-1 DOTES: 1. ALL WIRE TO BE#12 THHNRHWN UNLESS NOTED OTHERWISE. COLOR CODE: • AO = BLACK .IO =RED . NEUTRAL= WHITE • GROUND = GREEN 2. ALL WORK TO CONFORM TO N.E.C. LATEST STATE ADOPTED EDITION. 3. LABEL SERVICE DISCONNECT WITH A RED TAG. 4. SWITCH LEG CONDUCTORS SHALL BE THE SAME COLOR AS CIRCUIT CONDUCTORS. 5. PULL WIRES TO END OF FLEXIBLE NONMETALLIC CONDUIT. COIL 3'-0' AT END OF FLEXIBLE NONMETALLIC CONDUIT & TAG. S. PULL ONE GROUND CONDUCTOR PER FLEXIBLE NONMETALLIC CONDUIT. FOR ALL OTHER CIRCUITS PULL A SEPARATE CONDUCTOR. 7. ALL GFCI RECEPTACLES TO HAVE A DEDICATED GROUND WIRE. B. EQUIPMENT TERMINATION LUGS AND CONDUCTORS ARE RATED ATA MINIMUM OF 75'C. KEY: - PHOTOCELL M =MOTION DETECTOR • =CONDUIT GROUND # = NON -DEDICATED GROUND it = DEDICATED GROUND <0 = ISOLATED GROUND 19 OUTDOOR EQUIPMENT A/C POWER SCHEDULE N.T.S. ELECTRICAL INSTALLATION METHODS: Providehere distribution 1. This inslallalion shall comply with the currently adopted edition of LOAD PER w 23. The subcontractor shall review and Inspect the existing facility code requirements. 2. Install sufficient lengths of LFMC Including all conduit fittings (nuts, LOAD PER reducing bushings, elbows, couplings, etc) necessary for LOAD connection from IMC or PVC conduit to the Interior of the BTS and TIA grounding standards. The subcontractor shall report any LOAD PHASE (VA) p > > a D a w 3 3 O N ozQ. O PHASE (VA) Z t0 0 (wet and dry) operation; listed or labeled for the location and conductors in accordance with the NEC. raceway system used. 4. Cul, coil and tape a 3 foot pigtail from end of LFMC for terminating25. Perform IEEE fall -of -potential resistance to earth testing (per IEEE 1100 and 81) for new ground electrode systems. The by BTS equipment manufacturer. subcontractor shalland install supplemental ground O z o O7 off y Ow 2N 0_ ZN s 26. Metal raceway shall not be used as the NEC required equipment q ¢F ¢Z U ground conductor. Stranded copper conductors with green 90°C (wet and dry) operation, listed or labeled for the location and Insulation sized in accordance with the NEC shall be furnished and raceway system used. 8. Supplemenid equipment ground wiring located outdoors or installed with the power circuits to BTS equipment. 27• Each indoor BTS ca net frame shall be directly connected to the below grade shall be single conductor #2 AWG solid, tinned, w O F o p n ¢ z rn z W o: O o 0 i w PHASE resistant THHN or THWN-2, Class copper listed labeled 29• Approved antioxidant coatings (i.e. conduclive gel or paste) shall for 90°C (Wet or Dry) operation, with outer locket or be used on all compression and bolted ground connections. for the location used. 8. Cables shall not be routed through ladder -style cable tray rungs. UNIT ,PHASE ZO J O 00 3 > > 3 0 '' O 0 UNIT DESCRIPTION 11. All power and grounding connections shell be crimp style, steel hardware. Installation torque shall be per manufacturer's DESCRIPTION KVA 3 0 Zo a 0 0 shall be labeled with color coded insulation or electrical tape. The 0 a 3 A B KVA a exisling installation requirements. 13. Al electrical components shall be clearly labeled with engraved laminated plastic labels. Al equipment shall be labeled with their A B Z O 0 O ampacily rating and branch dreuil ID numbers (panelboard and circuit identification). z 14. All tie wraps shall be cut flush with approved cutting tool to remove 20A sharp edges. iLK 15. Rigid nonmetallic conduit (PVC Schedule 40 or PVC Schedule 80) 4200 BE light vehicle traffic or encased In reinforced concrete in areas of 0 SPACE 2 3 RECTIFIER 2 8.400 X 4200 e (70) 30 outdoors where vibration occurs or flexibility is needed. E 0 I ( SPACE 4 5 20. Cabinets, boxes and wireways shalt be listed or labeled for 4200 BLK electrical use in accordance with NEMA, UL, ANSWEEE and NEC. NOTE: FOR GROUNDING 21. Cabinets, boxes and wireways Shell match the existing installation LK SPACE 6 7 RECTIFIER 2 8.400 X 4.200 E 8 (10) 30 20 (10) 12 1 1 X IE 0.400 0.200 2 GFCI RECEPTACLES 8 g 4.200 BLK20 (10) 12 X 1. 0.010 0.010 1 BATTERY CHARGER 10 11 RECTIFIER 2 8.400 4200 E X 8 (10) 30 E SPACE 12 13 4200 LK SPACE 14 75 RECTIFIER 2 8.400 4200 El X 8 (10) 30 E SPACE 16 17 SPACE BLK LK SPACE 18 SPACE E E SPACE 20 SPACE BLK LK SPACE 22 SPACE E SPACE 24 K SPACE 26 SPACE BLK [27 SPACE E E SPACE 28 SPACE BLK LK SPACE 30 SPACE E E SPACE 32 LK SPACE 34 SPACE BLK SPACE E E SPACE 36 37 SPACE BLK LK SPACE 38 39 SPACE E E SPACE 40 41 SPACE SLK LK SPACE 42 SUBTOTAL - 0.400 SUBTOTAL TOTALKVA 42.50 CONTINUOUS 18.80 18.80 CONTINUOUS CONTINUOUS x 1.25 SUBTOTAL NON CONTINUOUS 0.010 - SUBTOTAL NON -CONTINUOUS TOTAL KVA NON -CONTINUOUS 0.010 SUBTOTAL - - SUBTOTAL SUB -PANEL _ SUB -PANEL SUB -PANEL SUB -PANEL PANEL DESIGNATION: ELECTRICALPANEL TOTAL KVA 42.51 MAIN LUGS: N/A MAIN BREAKER: 200 AMP MAIN BREAKER A.I.0 RATING: 22,000 A.I.0 BRANCH BREAKER A.I.0 RATING: 10,000 AA.0 VOLTAGE: 7201240 CYCLE: 80 PHASE: 1 WIRES: 3 MAIN COPPER BUS: 200 AMP NEUTRAL: 200 AMPSI BRANCH BREAKER TYPE: SQUARED -BOLTON TOTAL AMPS 177.13 19 OUTDOOR EQUIPMENT A/C POWER SCHEDULE N.T.S. ELECTRICAL INSTALLATION METHODS: Providehere distribution 1. This inslallalion shall comply with the currently adopted edition of 22. Provide necessary tagging on the breakers, cables and necessary panels in accordance with applicable codes and standards to safeguard life and property. The National Electrical Code and with utility company and local 23. The subcontractor shall review and Inspect the existing facility code requirements. 2. Install sufficient lengths of LFMC Including all conduit fittings (nuts, grounding system and lightning protection system (as designed and Installed) for strict compliance with the NEC. The site specific reducing bushings, elbows, couplings, etc) necessary for lightning protection code and general compliance with Telcortlia connection from IMC or PVC conduit to the Interior of the BTS and TIA grounding standards. The subcontractor shall report any cabinet. 3. Power, control and equipment ground wiring In tubing or conduit Molations or adverse findings to the contractor for resolution. 24. All elecirode systems (including telecommunicolion, radio, shall be single conductor (#14 AWG and larger), 600V, oil resistant lightning protection and AC power GES's) shall be bonded THHN or THWN-2, Class B stranded copper cable rated for 90°C together at or below grade by Iwo or more copper bonding (wet and dry) operation; listed or labeled for the location and conductors in accordance with the NEC. raceway system used. 4. Cul, coil and tape a 3 foot pigtail from end of LFMC for terminating25. Perform IEEE fall -of -potential resistance to earth testing (per IEEE 1100 and 81) for new ground electrode systems. The by BTS equipment manufacturer. subcontractor shalland install supplemental ground 5. Supplemental equipment ground wiring located Indoors shall be edfurto test result 5 ohms or less. electrodes as needed to achieve single conductor (#e AWG and larger), 600V, oil resistant THHN or s 26. Metal raceway shall not be used as the NEC required equipment q THWN-2 green insulation, Class B stranded copper cable rated for ground conductor. Stranded copper conductors with green 90°C (wet and dry) operation, listed or labeled for the location and Insulation sized in accordance with the NEC shall be furnished and raceway system used. 8. Supplemenid equipment ground wiring located outdoors or installed with the power circuits to BTS equipment. 27• Each indoor BTS ca net frame shall be directly connected to the below grade shall be single conductor #2 AWG solid, tinned, it Inground bar with supplemental equipment ground wires #6 copper cable. 7. Power and control wiring, not in tubing orconduil, shall be or larger. 28. Exothermic welds shall be used for all grounding connections multiconductor, Type TO. Cable (#14 AWG and larger), 600V, oil 8, Stranded cable rated below grade. resistant THHN or THWN-2, Class copper listed labeled 29• Approved antioxidant coatings (i.e. conduclive gel or paste) shall for 90°C (Wet or Dry) operation, with outer locket or be used on all compression and bolted ground connections. for the location used. 8. Cables shall not be routed through ladder -style cable tray rungs. 30• ICE bridge bonding conductors shall be exothermically bonded or bolted to the bridge and the tower ground bar. 9. Raceway and cable tray shall be listed or labeled for electrical use 31. Surfaces to be connected to ground conductors shall be cleaned in accordance with NEMA, UL, ANSVIEEE and NEC. to a bright surface at ail connections. 10. New raceway or cable tray shall match the existing installation 32. Exposed ground ccshall be made with compression where possible. connectors which are then bolted to equipment using stainless 11. All power and grounding connections shell be crimp style, steel hardware. Installation torque shall be per manufacturer's compression, wire lugs and wirenuts by Thomas and Betts (or requirements. equal). Lugs andwirenuts shall berated for operation of no less 33. DC power cables shill be Cobra COP -FLEX 2000, Flexible Class S or than 75°C. 12. Each end of every power, grounding and T7 conductor and cable approved equal. shall be labeled with color coded insulation or electrical tape. The Identification method shall conform with NEC & OSHA and match exisling installation requirements. 13. Al electrical components shall be clearly labeled with engraved laminated plastic labels. Al equipment shall be labeled with their (1)1 "IMC -(3)#8 voltage rating, phase configuration, wire configuration, power or ampacily rating and branch dreuil ID numbers (panelboard and circuit identification). THWN CU (1) 14. All tie wraps shall be cut flush with approved cutting tool to remove 20A sharp edges. 970 GROUND 15. Rigid nonmetallic conduit (PVC Schedule 40 or PVC Schedule 80) shall be used underground, direct buried In areas of occasional light vehicle traffic or encased In reinforced concrete in areas of heavy vehicle traffic. 16. All conduit run above ground or exposed shall be LFMC, IMC or Rigid Steel. 17. Electrical metallic tubing (EMT) shall be used for concealed indoor localions. 18. Liquid tight flexible metallic conduit shall be used indoors and outdoors where vibration occurs or flexibility is needed. 19. Conduit and tubing fittings shall be threaded or compression type I ( and approved for the location used. Setscrew fittings are not BY CARRIER, TYP. OF (8) acceptable. 20. Cabinets, boxes and wireways shalt be listed or labeled for #2 BOND TO BUILDING GROUND electrical use in accordance with NEMA, UL, ANSWEEE and NEC. NOTE: FOR GROUNDING 21. Cabinets, boxes and wireways Shell match the existing installation #2 AWG SUPPLEMENTAL. EQUIPMENT GROUND CONDUCTOR TO GROUND CEI PROVIDED GROUND BAR AT CARRIER RACK LOCATION 13 ELECTRICAL NOTES 9 SINGLE LINE DIAGRAM N.T.S. N.T.S. (1)1" IMC (3) #8 THWN CU (1) #10 GROUND - ABBREVIATIONS: BCW BARE COPPER WIRE ITS BASE TRANSCEIVER STATION C CONDUT (E) EXISTING EG EQUIPMENT GROUND (F) FACP FUTURE FIRE ALARM CONTROL PANEL GEN GENERATOR IG ISOLATED GROUND IMC INTERMEDIATE METAL CONDUIT LFMC LIQUID TIGHT FLEXIBLE METAL CONDUB MCM MILLION CIRCULAR MILLS MI MECHANICAL INTERLOCK MP&S SEE MECHANICAL PLANS & SPECIFICATIONS INI NEMA NEW NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION NL NIGHT LIGHT- FIXTURE TO BE UNSWITC HED PFB PROVISION FOR FUTURE BREAKER PVC POLYVINYL CHLORIDE CON DUFF (RI RG RELOCATE RE LAY TOMONITOR GENERATOR POWER RU RELAY TO MON ITOR UTILITY POWER TYP TYPICAL UON UNLESS OTHERWISE NOTED WP WEATHERPROOF GFCI GROUN D FAULT CIRC Uff INTERRUPTER NOTE: SYMBOLS INDICATED ABOVE MAY NOT N ECESSAR ILY APPEAR AS PART OF THESE DRAWINGS IF NOT REQUIRED. 0ABBREVIATIONS N.T.S. (E) BUILDING UTILITY 1478 STONE POINT DRIVE, SUITE 350 ROSEVILLE CA 05WI 8187827200 TEL 018 773 3037 FAX 115 J5 INFRASTRUCTURE PARTNERS I I SO BALLENA BLVD, #259 ALAMEDA, CA94501 a `N 6001 EXECUTIVE PARKWAY SAN RAMON. CA 04583 1 1012312017 100%CD SubrWftl 0 00)1420» 00%CDSubmi0el A 08/07/2017 100%ZDSubmittal REV DATE DESCRIPTION STAMP �,pgEO All i F L'.u•'0a DRAWN BY: JVM PROJECT NO.: T-16501-7 CHECK BY: B.K.W. SHEETTITLE ELEC SINGLE LINE DIAGRAM SHEET NO. E-2 aU NOTE: EFOR SHOWN ARE NUMBFOR FIRMS NUMBER ELECTRODE CONDUCTOR ALL BREAKERS AND PANELS PANEL BOARD RACKS EXISTING UNLESS NOTED AS (P) PROPOSED DISTRIBUTION PANEL 200 AMP, i PHASE, 120240V AC SLIDE BAR TRANSFER DEVICE. 42 POSITION LOAD CENTER, 4- IMC 20 AMP OR RECEPTACLE. (1)#2 GROUND AC SURGE ARRESTOR BY CARRIER (IF NEEDED) WITH ALARMS 1478 STONE POINT DRIVE, SUITE 350 ROSEVILLE CA 05WI 8187827200 TEL 018 773 3037 FAX 115 J5 INFRASTRUCTURE PARTNERS I I SO BALLENA BLVD, #259 ALAMEDA, CA94501 a `N 6001 EXECUTIVE PARKWAY SAN RAMON. CA 04583 1 1012312017 100%CD SubrWftl 0 00)1420» 00%CDSubmi0el A 08/07/2017 100%ZDSubmittal REV DATE DESCRIPTION STAMP �,pgEO All i F L'.u•'0a DRAWN BY: JVM PROJECT NO.: T-16501-7 CHECK BY: B.K.W. SHEETTITLE ELEC SINGLE LINE DIAGRAM SHEET NO. E-2 aU 92 GROUNDING ELECTRODE CONDUCTOR 30A 1_ SURGE ARRESTER BY 30A CARRIER (IF NEEDED) (P)PURCEL CABINET 30A LEGEND: 2UA M1 - MECHANICAL INTERLOCK 30A RU= RELAY TO MONITOR UTILITY POWER RG =RELAY TO MONITOR GENERATOR POWER 30A (1)1 "IMC -(3)#8 THWN CU (1) 20A 970 GROUND 30A (P) 20 AMP BREAKER, BY CARRIER, TVP. OF (2) 30A 30A (P) 30 AMP 2 -POLE BREAKER. I ( BY CARRIER, TYP. OF (8) I ( #2 BOND TO BUILDING GROUND NOTE: FOR GROUNDING SYSTEM GEE SHEET 13-1 \ CARRIERPROVIDEDGROUND BAR AT CARRIER PURCELL LOCATION 1478 STONE POINT DRIVE, SUITE 350 ROSEVILLE CA 05WI 8187827200 TEL 018 773 3037 FAX 115 J5 INFRASTRUCTURE PARTNERS I I SO BALLENA BLVD, #259 ALAMEDA, CA94501 a `N 6001 EXECUTIVE PARKWAY SAN RAMON. CA 04583 1 1012312017 100%CD SubrWftl 0 00)1420» 00%CDSubmi0el A 08/07/2017 100%ZDSubmittal REV DATE DESCRIPTION STAMP �,pgEO All i F L'.u•'0a DRAWN BY: JVM PROJECT NO.: T-16501-7 CHECK BY: B.K.W. SHEETTITLE ELEC SINGLE LINE DIAGRAM SHEET NO. E-2 1 ( (P)46 AWG, nP. (P) GROUND BAR, VERIFY LOCATION IN FIELD GROUNDTO(E) SECTORW BUILDING STEEL jCZ31111a \ 1 `\ 1 \1 \ 1 \ 1 1 1 1 1 \ , 1 (P) GROUND BAR VERIFY 1' / LOCATION IN FIELD GROUND TO (E) BUILDING STEEL ; ' � I / 1 F SECTOR V GROUND TO (E) `BUILDING STEEL `\ (P) #6 AWG, nP. � I � elgk� / E6, GROUND TO (E BUILDING STEE PROVIDED BY CARRIER GROUNDING PER CEI PLANS, CARRIERS TO EXTEND THEIR SECTOR PURCELL MOUNT J(P)GROUND BAR, VERIFY N LOCATION IN FIELD 2' 1' 0 2' 4' SECTOR'C' 9 AT&T EQUIPMENT GROUNDING PLAN 117•=r-0• 1478 STONE POINT DRIVE, SUITE 350 ROSEVILLE CA 85881 0187827]0) TEL 0187733037 FAX J5 INFRASTRUCTURE PARTNERS 1150 BALLENA BLVD, #259 AIAMEDA, CA 94501 _ aut 5001 EXECUTIVE PARKWAY SAN RAMON, CA 04583 1 IW=2017 100%CD Submi tal 0 0811412017 0% CD Su ftfN l A W1071M17 103% ZD Submittal REV _ DATE DESCRIPTION STAMP ARCN,/ Cit 4 0 F CA1�O DRAWN BY: NM PROJECT NO.: T-18501-7 CHECK BY: B.K.W. SHEETTITLE GROUNDING PLANS SHEET NO. G®1 PROVIDED BY CARRIER GROUNDING PER CEI PLANS CARRIERS TO EXTEND THEIR SECTOR GPS ANTENNA GROUNDING 12" TO 24" 1° ANTENNA CABLE NOTES: NEW GPS ANTENN #6 AWG STRANDED COPPER 1. DO NOT INSTALL CABLE GROUND KIT AT A BEND AND GROUND WIRE (GROUNDED ® ALWAYS DIRECT GROUND WIRE DOWN TO GROUND BAR CABLE GROUNDING KIT (SEE NOTE 1 & 2) 2. GROUNDING KIT SHALL BE TYPE AND PART NUMBER AS TYPE SS TYPE TA SUPPLIED OR RECOMMENDED BY CABLE MFR CABLE TO PIPE CAST T SPLICER 1 BOLT PARALLEL SPLICER CONNECTSURNDY 3. WEATHER PROOFING SHALL BE TYPE AND PART NUMBER TYPE GAR, TYP. (2) #2 AWG BCW, TYP. AS SUPPLIED OR RECOMMENDED BY THE CABLE MFR PLACES (2)PLACES MOUNTING BRACKET CABLE 1/2"G COAXGROUNDING Na AWG GROUNDING KIT CABLE /� STRIP OUTER JACKET AWAY / USING APPROVED TOOLS GROUNDING KIT �.t #2 AWG BCW TO ��\CIGBE #2AWGBCWTO (CIGBE) AOXIAL =CABLE #2 AWG BCW �\�)TOMGS...r._._._._. GPS ANTENNA GROUNDING 12" TO 24" 1° ANTENNA CABLE EXISTING GROUND RING WEATHERPROOFING #6 AWG STRANDED COPPER KIT (SEE NOTE 3) GROUND WIRE (GROUNDED ® TO GROUND BAR) CABLE GROUNDING KIT (SEE NOTE 1 & 2) NOTE: 100 NOT INSTALL CABLE GROUND KIT AT A BEND AND ALWAYS DIRECT WIRE DOWN TO GROUND BAR. 2. GROUNDING KIT SHALL BE TYPE AND PART NUMBER AS SUPPLIED OR RECOMMENDED BY CABLE MANUFACTURER. 3. WEATHER PROOFING SHALL BE (TYPE AND PART NUMBER AS SUPPLIED OR RECOMMENDED BY CABLE MANUFACTURER.) O 0 GROUND KIT CLAMP PER MFR SPECIFICATIONS #8 AWG STRANDED COPPER GROUND WIRE (GROUNDED TO GROUND BAR PER NOTES 1 AND 2) WEATHERPROOFING PER MFR SEE NOTE 3 #6 AWG STRANDED COPPER GROUND WIRE (GROUNDED TO GROUND BAR PER NOTES 1 AND 2) #2 AWG FROM BE GROUNDED GROUNDBAR DUAL CADW ELDS. TO BE USCO'" H / (� SILICON SEAL AT WITH#2 AWGBCWTO TOP GROUNDRING 1' OVC SEALTITE NOTE: 1. CONTRACTOR TO UTILIZE KOPRSHIELD(THANS 8 BETTS) ON ALL LUG CONNECTIONS OR APPROVED EQUAL 2. ALL LUGS TO BE DUAL HOLE LONG BARREL AND CRIMPED TWICE WITH MFR'S RECOMMENDED TOOL 0_-\.�,RZIUND BAR CONNECTION DETAIL CALE 5 2 4 ® 4" ohm z .°°.•° 3 �. I' LEGEND I. COPPER GROUND BAR, -X 114-X20^, NEWTON INSTRUMENT= CAT. NO. B-42 OR EQUAL. HOLE CENTERS TO MATCH NEMA DOUBLE LUG CONFIGURATION. (ACTUAL GROUND BAR SIZE WILL VARY BASED ON NUMBER OF GROUND CONNECTIONS) 2- INSULATORS, NEWTON INSTRUMENT CAT. N0.3001-0 OR EQUAL 3- 518- LOCKWASHERS, NEWTON INSTRUMENT CO. CAT. NO. WI -OR EQUAL 4- WALL MOUNTING BRACKET, NEWTON INSTRUMENT CO. CAT NO. A-50 OR EQUAL 6- SI&11 X V HHCS BOLTS, NEWTON INSTRUMENT CO. CAT NO. n12 OR EQUAL & INSULATORS SHALL BE ELIMINATED W HEN BONDING DIRECTLY TO TOWERIMONOPOLE STRUCTURE. CONNECTION TO TOW ERIMONOPOLE STRUCTURE SHALL BE PER MANUFACTURERS RECOMMENDATIONS. NOTE: ALL HARDWARE SHALL BE STAINLESS STEEL GROUNDING NOTES FOR ADDITIONAL GROUNDING INFORMATION SEE AT&T GROUND STANDARDS ATT -TP -76416 1 ALL ELECTRICAL AND GROUNDING AT THE CELL SITE SHALL COMPLY WITH THE NATIONAL ELECTRICAL CODE (NEC), NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 780 (LATEST EDITION), AND MANUFACTURER SPECIFICATION. 2 IF THE AC PANEL IN THE POWER CABINET IS WIRED AS SERVICE ENTRANCE, THE AC SERVICE GROUND CONDUCTOR SHALL BE CONNECTED TO GROUND ELECTRODE SYSTEM. WHEN THE AC PANEL IN THE POWER CABINET IS CONSIDERED A SUB -PANEL, THE GROUND WIRE SHALL BE INSTALLED IN THE AC POWER CONDUIT. THE INSTALLATION SHALL BE PER LOCAL AND NATIONAL ELECTRIC CODE (NFPA-70). 3 MADE USING COMPRESSION TYPEM2 HOLES.ENDED LONG R GROUNDING CONNECTION HPRACTICAL. OTHERWISE, E EXOTHERMIC WELDING IS LONG BARREL LUGS OR DOUBLE ERE AMPC" CLAMPTHE COPPER CABLES SHALL BE COATED WITH ANTIOXIDANT (COPPER SHIELD) BEFORE MAKING THE CONNECTIONS. THE MANUFACTURER'S TORQUING RECOMMENDATIONS ON THE BOLT ASSEMBLY TO SECURE CONNECTIONS SHALL BE FOLLOWED. 4 THE ANTENNA CABLES SHALL BE GROUNDED AT THE TOP AND BOTTOM OF THE VERTICAL RUN FOR LIGHTING PROTECTION. THE ANTENNA CABLE SHIELD SHALL BE BONDED TO A COPPER GROUND BUSS AT THE LOWER MOST POINT OF A VERTICAL RUN JUST BEFORE IT BEGINS TO BEND TOWARD THE HORIZONTAL PLANE. WIRE RUNS TO GROUND SHALL BE KEPT AS STRAIGHT AND SHORT AS POSSIBLE. ANTENNA CABLE SHIELD SHALL BE GROUNDED JUST BEFORE ENTERING THE CELL CABINET. ANY ANTENNA CABLES OVER 200 FEET IN LENGTH SHALL ALSO BE EQUIPPED WITH ADDITIONAL GROUNDING AT MID -POINT. 5 ALL GROUNDING CONDUCTORS INSIDE THE BUILDING SHALL BE RUN IN CONDUIT RACEWAY SYSTEM, AND SHALL BE INSTALLED AS STRAIGHT AS PRACTICAL WITH MINOR BENDS TO AVOID OBSTRUCTIONS. THE BENDING RADIUS OF ANY #2 GROUNDING CONDUCTOR IS 8". PVC RACEWAY MAY BE FLEXIBLE OR RIGID PER THE FIELD CONDITIONS. GROUNDING CONDUCTORS SHALL NOT MAKE CONTACT WITH ANY METALLIC CONDUITS, SURFACES OR EQUIPMENT. 6 PROVIDE PVC SLEEVES WHERE GROUNDING CONDUCTORS PASS THROUGH THE BUILDING WALLS AND /OR CEILINGS. 7. INSTALL GROUND BUSHINGS ON ALL METALLIC CONDUITS AND BOND TO THE EQUIPMENT GROUND BUSS IN THE PANEL BOARD. 8 GROUND ES, CABLE RACKS AND OTHER METALLIC COMPONENTS WITH #2 GROUNDING CONDUCTORS AND CONNECT TO INSULATED SURFACE MOUNTED ENNA BASES, MGROUND BARS. CONNECTION DETAILS SHALL FOLLOW MANUFACTURER'S SPECIFICATIONS FOR GROUNDING. 9. ALL PROPOSED GROUNDING CONDUCTORS SHALL BE ROUTED AND CONNECTED TO THE MAIN GROUND BAR OR EXISTING GROUND RING. GROUNDING LEGEND ---� EXISTING GROUND RING BOLT GROUND ROD CLAMP CADWELD CONNECTION (EXOTHERMIC WELD) AL MECHANICAL CONNECTION ® GROUND ROD TYPE NXt TYPE RR TYPE No TYPE PG BOLT GROUND ROD CLAMP 2 BOLT PARALLEL SPLICER CROSS RUN CLAMP TYPE SS TYPE TA TYPE TYPE VB 2 HOLE LUG CAST T SPLICER 1 BOLT PARALLEL SPLICER CONNECTION OF GRND KIT TO ANTENNA CABLE GROUND KIT 1 GROUND BAR DETAIL 14 NOT TO SCALE 112'=P-0" TYPE XA TYPE GT TYPE GL LUG 18 112"=1'-0' TO ANTENNA n TXl tf It( RX, COAX JUMPER, TYP.� WEATHERPROOFING KIT, TYP. CONNECTOR ANDREW WEATHERPROOFING SUREGROUNDTYPE GROUNDING KIT, TYP., KIT, TYP. SEE NOTE (2) SEE NOTE �? I1� #6 AWG ANTENNA O — ANTENNA GROUND BAR. BTS EQUIPMENT,ENT,TYTYP. SIMILAR TO DETAIL 10 WITHOUT INSULATORS. e e o e e e o e e 0 BOUNDED DIRECTLYTO TOP OF POLE OR TOWER 1. DO NOT INSTALL CABLE GROUND KIT AT A BEND AND ALWAYS DIRECT GROUND WIRE DOWN TO ANTENNA GROUND BAR. 2. WEATHERPROOFING SHALL BE ANDREW TWO-PART TAPE KIT. COLD SHRINK SHALL NOT BE USED OGRND CONNECTION TO GRND BAR pi TYPE LJ TYPE HA TYPE VS TYPE PC " -0, '�4 T-'�P\\\2'0 01w - TYPE ND U "�0' TYPE GY TYPE NX7 TYPE GR TYPICAL CADWELD TYPE CONNECTIONS NO SCALE FIUP INTO tr� 0 UNIVERSAL PIPE CLAMP 7511.25 0 UNIVERSAL PIPE CLAMP 50H2 TYPICAL MECHANICAL TYPE CONNECTIONS NO SCALE 1478 STONE POINT DRIVE, SUITE 350 ROSEVILLE CA 95501 0107827200 TEL 11 Es J5 INFRASTRUCTURE PARTNERS 1150 BALLENA BLVD, #259 ALAMEDA CA 94501 ..._ at&t 5001 EXECUTIVE PARKWAY SAN RAMON, CA 04583 1 IWMIN17 100%CDSub W l 0 00/1412017 00% CD Submi I A 00107/2017 100%ZDSubmiO! REV DATE DESCRIPTION STAMP y,45E0-ARCyry �tO SL BU i e e.Og-30'0 4-C DRAWN BY: JVM PROJECT NO.: T-18501.7 CHECK BY: B.K.W. SHEETTITLE GROUNDING NOTES & DETAILS SHEET NO. G-2