11070002 - MISC i
ALPHA AIR BALANCING AGENCY/INC.
TEST AND BALANCE REPORT
1052 DeAnza Blvd. T.I.
I U5LO2 C)e An--7A - ► I O-7 ODU2
CUPERTINO, CALIFORNIA
PRESENTED TO: KIMBERT SHEET METAL, INC.
SUBMITTED BY: ROMY A. GONZALES
PROJECT NUMBER: 2011-3193
r
1 .
TEST
AND
BALANCE
REPORT
PROJECT: 10562 DeAnza Blvd. T.I.
LOCATION: 10562 DeAnza Blvd.,
CUPERTINO, CALIFORNIA
ARCHITECT: BETTA GROUP
MECHANICAL ENGINEER: KIMBERT SHEET METAL, INC.
MECHANICAL CONTRACTOR: KIMBERT SHEET METAL, INC.
TESTED AND BALANCED BY: ALPHA AIR BALANCING AGENCY, INC.
P.O. BOX 3948
CARMEL, CALIFORNIA 93921
TEL. # (831) 625-8195
FAX. # (831) 625-8196
PROJECT CERTIFICATION
THIS IS TO CERTIFY THAT ALPHA AIR BALANCING AGENCY, INC. HAS BALw-
®r
SYSTEM DESCRIBED HEREIN TO THEIR OPTIMUM PERFORMANCE AND CAD
BALANCING HAVE BEEN PERFORMED IN ACCORDANCE WITH THE PLANSE
RESULTS OF THESE TESTS ARE HEREIN LISTED.PROJECT NO: 2011-3193 CERTIFIED BY: F�DATE• 12/2/2011 R L . GOND
SUPERVISING NGINEER
Table of Contents
General Notes & Abbreviations
AIR BALANCE 1-3
Air Moving Equipment Sheet AC 1 1
Air Distribution Report (Flow Hood) AC 1 Supply and Return Air 2
Air Register Locations AC 1 3
GENERAL NOTES
1. Unless otherwise noted, indicated CFM (Cubic Feet per minute) is at standard conditions.
2. Where no number is indicated under the velocity or FPM column, test readings were
measured with Alno� Balometer flowhood model 6461 which reads in direct CFM.
3. Flow instruments used for velocity and pressure readings:
• Rotating vane anemometer by Air Flow Model EDRA-6E.
• Air data multi-meter electronic micro manometer by Shortridge Instruments Model ADM-
870.
• Dwyer Magnehelic gauges& pitot tubes.
4. Any variances from design quantities are noted on the remarks column throughout this report.
ABBREVIATIONS USED
AC - AIR CONDITIONING
CEF - CEILING EXHAUST FAN
CFM - CUBIC FEET PER MINUTE
CRR - CEILING RETURN REGISTER
CSD - CEILING SUPPLY DIFFUSER
CSR - CEILING SUPPLY REGISTER
EF - EXHAUST FAN
FC - FAN COIL
FPM - FEET PER MINUTE
HP/BHP - HORSEPOWER/BRAKE HORSEPOWER
N.S. - NOT SPECIFIED
OSA - OUTSIDE AIR
RD. - ROUND
RPM - REVOLUTIONS PER MINUTE
ALPHA AIR BALANCING AGENCY, INC.
P.O. BOX 3948, CARMEL, CALIFORNIA 93921-3948
Phone#(831)625-8195 Contractor's License# 708453
AIR MOVING EQUIPMENT SHEET
DATE: 1212/2011
PAGE: 1 OF 3
PROJECT NAME: TOb62 OE ANZA-BLVO'T.I.
ADDRESS: 10562 DE ANZA BLVD.
CUPERTINO, CALIFORNIA
SYSTEM. AIR CONDITIONING AC-1
EQUIPMENT NUMBER AC-1
LOCATION ROOF
MANUFACTURER PAYNE
MODEL NUMBER D3CG120N15625ST6
SERIAL NUMBER NFDN1048628
SPACE,SERVED SUITE & FIDELITY TITLE
FAN DATA DESIGN ACTUAL
TOTAL CFM-FAN 3,996 3,899
TOTAL CFM- OUTLET/INLET 3,900 3,910
RETURN AIR CFM 3,880 3,874
OUTSIDE AIR CFM 390 395
TOTAL STATIC PRESSURE NOT SPECIFIED 0.737"
INLET PRESSURE NOT SPECIFIED -0.556"
DISCHARGE PRESSURE NOT SPECIFIED 0.181"
FAN RPM DIRECT DRIVE DIRECT DRIVE
MOTOR DATA DESIGN ACTUAL
MOTOR MANUFACTURER NOT SPECIFIED NOT SPECIFIED
MOTOR HP/BHP NOT SPECIFIED 1 - 1/2
PHASE 3 3
VOLTAGE 208 210
AMPERAGE NOT SPECIFIED 2.4
MOTOR RPM DIRECT DRIVE DIRECT DRIVE
BELT SIZE NONE, DIRECT DRIVE
MOTOR SHEAVEIGROOVES NONE, DIRECT DRIVE
FAN SHEAVE/GROOVES NONE, DIRECT DRIVE
REMARKS:
OSA 100% shut.
ALPHA AIR BALANCING AGENCY, INC.
P.O. BOX 3948, CARMEL, CALIFORNIA 93921
Phone#(831)625-8195 Contractor's License#708453
AIR DISTRIBUTION REPORT (FLOW HOOD)
DATE: 12/2/2011
PAGE: 2 OF 3
PROJECT NAME: 10562 DE ANZA BLVD. T.I.
ADDRESS: 10562 DE ANZA BLVD.
CUPERTINO. CALIFORNIA
SYSTEM: AC-1
ROOM OUT/ INLET DIFFUSER/ NECK DESIGN PRELIM. FINAL
NUMBER NUMBER SIZES, TYPE CFM CFM CFM NOTE
AC-1 SUPPLY AIR
1 1 14 x14 CSD 600 550 590
2 2 8 x 8 CSD 200 155 210
3 3 8 x 8 CSD 200 1 185 200
4 4 10 x 10 CSD 300 280 305
5 5 8 x 8 CSD 200 220 195
6 6 8 x 8 CSD 200 180 205
7 11 14x14 CSD 600 515 585
7 12 14 x14 CSD 200 620 615
8 7 8 x 8 CSD 300 200 200
9 8 10 x 10 CSD 300 1 325 310
10 9 8 x 8 CSD 200 205 205
11 10 10 x 10 CSD 300 290 290
TOTAL 3900 3910
AC-1 RETURN AIR
2 1 8 x 8 CRR 190 160 192
3 2 8 x 8 CRR 190 165 197
4 3 8 x 8 CRR 190 178 185
5 4 8 x 8 CRR 190 189 189
6 5 8 x 8 CRR 190 187 187
7 6 12 x 12 CRR 400 315 391
7 7 14 x 14 CRR 590 610 610
7 8 14 x 14 CRR 590 570 585
7 9 8 x 8 CRR 590 581 589
8 10 8 x 8 CRR 190 190 190
9 11 8 x 8 CRR 190 175 185
10 12 8 x 8 CRR 190 162 179
11 13 8 x 8 CRR 190 180 195
TOTAL 3,880 3,874
ALPHA AIR BALANCING AGENCY, INC.
P.O. BOX 3948, CARMEL, CALIFORNIA 93921-3948
Phone#(831) 625-8195 Contractor's License#708453
REGISTER LOCATIONS
DATE: 12/2/2011
PAGE. 3 OF 3
PROJECT NAME: 10562 DE ANZA BLVD. T.I.
ADDRESS: 10562 DE ANZA BLVD.
CUPERTINO, CALIFORNIA
SYSTEM: AIR CONDITIONING AC-1
4 ® 300 CFM 5200 CFM. ®200 CFM +�0.
8" DIA. 8" DIA. ' I w
10" DIA. I ROOM 5 ROOM 6 6 � Its
_8" DIA. MR 400 CFM
ROOM 4 3 190 CFM � 8 DIA. n 8" DIA.— 12"DIA.
q 190 CFM $ 190 CFM
7 2590 CFM
'ROOM 3 8" DIA. 1v4" DIA.
l V190 CFM
590 CFM
8" DIA. 11 12
® 200 CFM IN CFM ®600 CFM 11
14" DIA. 14" DIA. 14" DIA.
-"0190 CFM
ROOM 78" DIA.
I -
ROOM 8
ROOM 2 8' DIA. I
—14" DIA. 7 200 CFM
9 590 CFM
L200 CFM 190 CFM �}2 1 {� �o f � 190CFM
DIA. 8®II 13 -190 CFM 12- 190 CFM 8" DIA. I —
1F. 1® 8" DIA. 8" DIA. D.
ROOM 1
=ROOM 11 ROOM 10 ROOM 9
11
600 CFM
1 ® 10" DIA. �' 8" DIA. :�' w 10" DIA.
14" DIA.0 666'10 ®300 CFM al 9 2200 CFM 8 ® 300 CFF
161 Jf
• W! 4.�1../LV �YJVaA• LLLV.�VYI'�L � V'Y• '+