11070002 - MISC i ALPHA AIR BALANCING AGENCY/INC. TEST AND BALANCE REPORT 1052 DeAnza Blvd. T.I. I U5LO2 C)e An--7A - ► I O-7 ODU2 CUPERTINO, CALIFORNIA PRESENTED TO: KIMBERT SHEET METAL, INC. SUBMITTED BY: ROMY A. GONZALES PROJECT NUMBER: 2011-3193 r 1 . TEST AND BALANCE REPORT PROJECT: 10562 DeAnza Blvd. T.I. LOCATION: 10562 DeAnza Blvd., CUPERTINO, CALIFORNIA ARCHITECT: BETTA GROUP MECHANICAL ENGINEER: KIMBERT SHEET METAL, INC. MECHANICAL CONTRACTOR: KIMBERT SHEET METAL, INC. TESTED AND BALANCED BY: ALPHA AIR BALANCING AGENCY, INC. P.O. BOX 3948 CARMEL, CALIFORNIA 93921 TEL. # (831) 625-8195 FAX. # (831) 625-8196 PROJECT CERTIFICATION THIS IS TO CERTIFY THAT ALPHA AIR BALANCING AGENCY, INC. HAS BALw- ®r SYSTEM DESCRIBED HEREIN TO THEIR OPTIMUM PERFORMANCE AND CAD BALANCING HAVE BEEN PERFORMED IN ACCORDANCE WITH THE PLANSE RESULTS OF THESE TESTS ARE HEREIN LISTED.PROJECT NO: 2011-3193 CERTIFIED BY: F�DATE• 12/2/2011 R L . GOND SUPERVISING NGINEER Table of Contents General Notes & Abbreviations AIR BALANCE 1-3 Air Moving Equipment Sheet AC 1 1 Air Distribution Report (Flow Hood) AC 1 Supply and Return Air 2 Air Register Locations AC 1 3 GENERAL NOTES 1. Unless otherwise noted, indicated CFM (Cubic Feet per minute) is at standard conditions. 2. Where no number is indicated under the velocity or FPM column, test readings were measured with Alno� Balometer flowhood model 6461 which reads in direct CFM. 3. Flow instruments used for velocity and pressure readings: • Rotating vane anemometer by Air Flow Model EDRA-6E. • Air data multi-meter electronic micro manometer by Shortridge Instruments Model ADM- 870. • Dwyer Magnehelic gauges& pitot tubes. 4. Any variances from design quantities are noted on the remarks column throughout this report. ABBREVIATIONS USED AC - AIR CONDITIONING CEF - CEILING EXHAUST FAN CFM - CUBIC FEET PER MINUTE CRR - CEILING RETURN REGISTER CSD - CEILING SUPPLY DIFFUSER CSR - CEILING SUPPLY REGISTER EF - EXHAUST FAN FC - FAN COIL FPM - FEET PER MINUTE HP/BHP - HORSEPOWER/BRAKE HORSEPOWER N.S. - NOT SPECIFIED OSA - OUTSIDE AIR RD. - ROUND RPM - REVOLUTIONS PER MINUTE ALPHA AIR BALANCING AGENCY, INC. P.O. BOX 3948, CARMEL, CALIFORNIA 93921-3948 Phone#(831)625-8195 Contractor's License# 708453 AIR MOVING EQUIPMENT SHEET DATE: 1212/2011 PAGE: 1 OF 3 PROJECT NAME: TOb62 OE ANZA-BLVO'T.I. ADDRESS: 10562 DE ANZA BLVD. CUPERTINO, CALIFORNIA SYSTEM. AIR CONDITIONING AC-1 EQUIPMENT NUMBER AC-1 LOCATION ROOF MANUFACTURER PAYNE MODEL NUMBER D3CG120N15625ST6 SERIAL NUMBER NFDN1048628 SPACE,SERVED SUITE & FIDELITY TITLE FAN DATA DESIGN ACTUAL TOTAL CFM-FAN 3,996 3,899 TOTAL CFM- OUTLET/INLET 3,900 3,910 RETURN AIR CFM 3,880 3,874 OUTSIDE AIR CFM 390 395 TOTAL STATIC PRESSURE NOT SPECIFIED 0.737" INLET PRESSURE NOT SPECIFIED -0.556" DISCHARGE PRESSURE NOT SPECIFIED 0.181" FAN RPM DIRECT DRIVE DIRECT DRIVE MOTOR DATA DESIGN ACTUAL MOTOR MANUFACTURER NOT SPECIFIED NOT SPECIFIED MOTOR HP/BHP NOT SPECIFIED 1 - 1/2 PHASE 3 3 VOLTAGE 208 210 AMPERAGE NOT SPECIFIED 2.4 MOTOR RPM DIRECT DRIVE DIRECT DRIVE BELT SIZE NONE, DIRECT DRIVE MOTOR SHEAVEIGROOVES NONE, DIRECT DRIVE FAN SHEAVE/GROOVES NONE, DIRECT DRIVE REMARKS: OSA 100% shut. ALPHA AIR BALANCING AGENCY, INC. P.O. BOX 3948, CARMEL, CALIFORNIA 93921 Phone#(831)625-8195 Contractor's License#708453 AIR DISTRIBUTION REPORT (FLOW HOOD) DATE: 12/2/2011 PAGE: 2 OF 3 PROJECT NAME: 10562 DE ANZA BLVD. T.I. ADDRESS: 10562 DE ANZA BLVD. CUPERTINO. CALIFORNIA SYSTEM: AC-1 ROOM OUT/ INLET DIFFUSER/ NECK DESIGN PRELIM. FINAL NUMBER NUMBER SIZES, TYPE CFM CFM CFM NOTE AC-1 SUPPLY AIR 1 1 14 x14 CSD 600 550 590 2 2 8 x 8 CSD 200 155 210 3 3 8 x 8 CSD 200 1 185 200 4 4 10 x 10 CSD 300 280 305 5 5 8 x 8 CSD 200 220 195 6 6 8 x 8 CSD 200 180 205 7 11 14x14 CSD 600 515 585 7 12 14 x14 CSD 200 620 615 8 7 8 x 8 CSD 300 200 200 9 8 10 x 10 CSD 300 1 325 310 10 9 8 x 8 CSD 200 205 205 11 10 10 x 10 CSD 300 290 290 TOTAL 3900 3910 AC-1 RETURN AIR 2 1 8 x 8 CRR 190 160 192 3 2 8 x 8 CRR 190 165 197 4 3 8 x 8 CRR 190 178 185 5 4 8 x 8 CRR 190 189 189 6 5 8 x 8 CRR 190 187 187 7 6 12 x 12 CRR 400 315 391 7 7 14 x 14 CRR 590 610 610 7 8 14 x 14 CRR 590 570 585 7 9 8 x 8 CRR 590 581 589 8 10 8 x 8 CRR 190 190 190 9 11 8 x 8 CRR 190 175 185 10 12 8 x 8 CRR 190 162 179 11 13 8 x 8 CRR 190 180 195 TOTAL 3,880 3,874 ALPHA AIR BALANCING AGENCY, INC. P.O. BOX 3948, CARMEL, CALIFORNIA 93921-3948 Phone#(831) 625-8195 Contractor's License#708453 REGISTER LOCATIONS DATE: 12/2/2011 PAGE. 3 OF 3 PROJECT NAME: 10562 DE ANZA BLVD. T.I. ADDRESS: 10562 DE ANZA BLVD. CUPERTINO, CALIFORNIA SYSTEM: AIR CONDITIONING AC-1 4 ® 300 CFM 5200 CFM. ®200 CFM +�0. 8" DIA. 8" DIA. ' I w 10" DIA. I ROOM 5 ROOM 6 6 � Its _8" DIA. MR 400 CFM ROOM 4 3 190 CFM � 8 DIA. n 8" DIA.— 12"DIA. q 190 CFM $ 190 CFM 7 2590 CFM 'ROOM 3 8" DIA. 1v4" DIA. l V190 CFM 590 CFM 8" DIA. 11 12 ® 200 CFM IN CFM ®600 CFM 11 14" DIA. 14" DIA. 14" DIA. -"0190 CFM ROOM 78" DIA. I - ROOM 8 ROOM 2 8' DIA. I —14" DIA. 7 200 CFM 9 590 CFM L200 CFM 190 CFM �}2 1 {� �o f � 190CFM DIA. 8®II 13 -190 CFM 12- 190 CFM 8" DIA. I — 1F. 1® 8" DIA. 8" DIA. D. ROOM 1 =ROOM 11 ROOM 10 ROOM 9 11 600 CFM 1 ® 10" DIA. �' 8" DIA. :�' w 10" DIA. 14" DIA.0 666'10 ®300 CFM al 9 2200 CFM 8 ® 300 CFF 161 Jf • W! 4.�1../LV �YJVaA• LLLV.�VYI'�L � V'Y• '+