INSPECTION CHECKLIST
Inspection Checklist
Address:
10861 Maxine Ave,
Cupertino, CA 95014
Approval ID:
SA20241227-7142-109-2-A
AHJ:
City of Cupertino, CA
Scope of work:
8.2 kW PV Array
27 kWH Energy Storage System
125a Load Center
General Guidelines
The installer shall follow the manufacturer's instructions for all installed equipment and shall have them available at
the time of inspection.
All wire sizes shown are, unless indicated otherwise, a minimum and the installer may upsize them at their
discretion.
All OCPD ratings shown must match the inspection checklist and be installed per the equipment manufacturer's
instructions, any ratings that do not match the inspection checklist are valid reasons for inspection failure.
Conduit sizing to be confirmed at time of inspection. Contractor to provide conduit fill calculations where requested
by inspector
Where distribution equipment, such as the main service panel or subpanel buses, are fed simultaneously by a
primary source(s) of electricity and one or more other power sources, interconnection shall have a method of
compliance at each panel board with both a primary source and other power source(s).
Diagram
MSP
A
Generation Sources Location
Location A - Main Service Panel
(N) Inverter 1
(N) Energy Storage
Systems
Main Service Panel Equipment Pass
If grounding electrode is rod, pipe or plate, then supplemental electrode is properly installed. Exception: If a
single rod, pipe, or plate grounding electrode has a resistance to earth of 25 ohms or less, the supplemental
electrode shall not be required.
EGC is installed ensuring continuity to all system components and finally to grounding electrode.
Single Phase Grid Voltage 240 V
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 1/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Busbar 1 Pass
Existing Main Service Panel
Existing Main Service Panel busbar ampere rating 200 A
Rating of the OCPD protecting the Existing Main Service Panel 200 A
The manufacturer's instructions were followed accurately and CTs are correctly installed to monitor all
sources of supply to the Existing Main Service Panel
Busbar 2 Pass
Combiner Panel
Interconnection Location Main Service Panel
Combiner Panel busbar ampere rating 125 A
Rating of the OCPD protecting the Combiner Panel 125 A
The length of the section of the Combiner Panel feeders that is inside a raceway is less than or equal to 2
feet
Conductor gauge for the Combiner Panel feeders 1 AWG
Equipment Grounding Conductor size for the Combiner Panel 6 AWG
Raceway size for the Combiner Panel feeders is compliant with 300.17 and
Chapter 9 Yes
Power Control System (PCS)Pass
The access to settings of the PCS is restricted to qualified personnel.
PCS ampacity setting 160 A
Equipment Point of Interconnection Pass
Utility Service Rating 200 A
Either the connected equipment is within line of sight and closer than 10ft to the point of interconnection or a
disconnect/isolation means are installed.
There is no existing Utility interactive power production source connected to the home's electric service. -
Only the utility interactive power production sources and/or photovoltaic modules specified on this
inspection checklist list are present on site.
DC and AC conductors are copper, Class B or Class C, and THWN-2, NM or PV Wire, or they are a
jacketed multiconductor cable assembly listed and identified for the application.
All power terminals are rated to 75°C or greater, labeled for use with Copper Class B or Class C wires, and
accept at least 8 AWG wire.
Conductors are properly terminated and wired according to the code.
Where Equipment Grounding Conductors (EGC) or Grounding Electrode Conductors (GEC) are not routed
with circuit conductors, they are a minimum of 6 AWG or they are protected from physical damage
There is a minimum working clearance according to the code; for all components that may require service,
the standing area of the workspace shall not contain obstructions, abrupt changes in grade, or irregularities.
Existing service equipment is rated for 10kAic
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 2/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Backup Initiation Device Pass
Backup Initiation Device manufacturer Tesla Inc.
Backup Initiation Device model 1624171-XX-Y
The rating of the largest load shall be less than or equal to 96
Inverter Pass
Inverter architecture String Inverter without
DC-DC Converters
EGC Wire Size Inverter 1 10 AWG
Overcurrent Protective Device rating Inverter 1 60 A
AC Wire size Inverter 1 6 AWG
Maximum number of THWN-2 conductors in a PV inverter AC output circuit
raceway, excluding any equipment grounding conductors.3 wires
Inverter 1 model number 1707000-XX-Y [240V,
11.5kW]
Inverter 1 manufacturer Tesla Inc.
Maximum number of THWN-2 DC conductors in raceway, excluding any
equipment grounding conductors.6 wires
Maximum number of DC PV wire or USE-2 conductors in raceway, excluding any
equipment grounding conductors.8 wires
Minimum DC Wire Gauge (PV Wire) for a single series string 12 AWG
Minimum DC Wire Gauge (THWN-2 Wire) for a single series string 12 AWG
Minimum DC Wire Gauge (PV Wire) for parallel strings 8 AWG
Minimum DC Wire Gauge (THWN-2 Wire) for parallel strings 10 AWG
Parallel strings are split into dedicated MPPTs at the inverter
DC strings EGC is a minimum of 10 AWG
Verify that string voltage does not exceed 600V.388.11 V
PV inverter maximum input DC open circuit voltage (Voc) on the equipment label 600 V
PV inverter maximum input DC short circuit current (Isc) on the equipment label 15 A
Presence of Rapid Shutdown switch label per Fire Bulletin
Energy Storage System Model 1 Pass
ESS Manufacturer Tesla Inc.
ESS Model Number 1707000-XX-Y
[11.5kW]
The ESS model 1 and the PV inverter are certified as a single product with a single AC output and do not
require any field wiring between the battery components and the inverter components.
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 3/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Energy Storage System Model 2 Pass
ESS Manufacturer Tesla Inc.
ESS Model Number 1707000-XX-Y
[11.5kW]
Quantity of ESS units 1
Energy Storage Equipment Location Pass
All of the Energy Storage Equipment units are installed in the following location Outdoor walls
Energy Storage Equipment units are located a minimum of 3 feet (914 mm) from doors and windows directly
entering the dwelling unit
The Energy Storage Equipment units are not installed in a location subject to vehicle damage
Individual energy storage systems are separated from each other by at least three feet of spacing unless
smaller separation distances are documented to be adequate as approved by the code official based on
large scale fire testing. Documentation shall be provided at time of inspection.
Energy Storage Architecture Pass
Number of distinct Energy Storage System Models used 2
Energy Storage Equipment Pass
Energy Storage Equipment is installed and mounted per the manufacturer's instructions.
The separation between Energy Storage Equipment units is more than 3 feet
Energy Storage Equipment is attached to the building using appropriate fasteners per the manufacturer.
Energy Storage Equipment assembly weight 290 lbs
The center of mass of the Energy Storage Equipment is located less than 4ft from the floor.
ESS Model 2 Pass
This is an AC Coupled ESS architecture
Overcurrent Protective Device rating ESS 60 A
Maximum number of THWN-2 conductors in the AC coupled ESS inverter output
circuit raceway, excluding any equipment grounding conductors.3 wires
ESS inverter output conductor gauge 6 AWG
Equipment Grounding Conductor size per ESS inverter output circuit 10 AWG
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 4/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Roof and PV Array Pass
The system will be installed on a permitted structure
Racking System Model Number ZS Comp
Racking System Manufacturer Zep Solar Inc.
The module and racking system shall be installed per the racking manufacturer's installation instructions
regarding grounding and bonding, fire, and load ratings
Attachment points of the mounting system are staggered No
Maximum spacing in inches between adjacent attachment points of the mounting
system 72 in
Roof penetration sealant method has been installed per the manufacturer's instructions.
The distance from the lowest point of the module to the roof surface does not
exceed 10 in
The roof structure appears to be structurally sound, without signs of alterations or significant structural
deterioration or sagging.
Quantity and spacing of structural attachments match the installation instructions per manufacturer.
Array conductors are secured and supported. Installed so as not to damage the cable, at intervals not
exceeding 1.4 m (4.5 ft) and within 300 mm (12 in.) of every cable entry into enclosures such as outlet
boxes, junction boxes, cabinets, or fittings.
PV Module model number Q.PEAK DUO BLK ML-
G10.a+/TS 410
PV Module manufacturer Qcells North America
PV Module quantity 20
Module fire rating type 2
Rapid Shutdown Device Manufacturer Tesla
Rapid Shutdown Device Model Number MCI-1
Method of rapid shutdown compliance Inside the Array Hazard Control System
Verify the location of RSD equipment relative to PV modules is in compliance with the hazard control
system certification document attached to the SolarAPP permit. Contractor shall provide a layout schematic
of the installed RSD equipment at the time of inspection.
All rooftop conduits are mounted at least ⅞” above the roof surface.
All conductors installed without raceway are listed as PV Wire, USE-2 or Type distributed generation (DG)
cable
Roof Plane 1 Pass
Pitch 3/12
Roof Covering Asphalt or composition
shingles
Number of coverings of comp shingle 2
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 5/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Roof Plane 2 Pass
Pitch 3/12
Roof Covering Asphalt or composition
shingles
Number of coverings of comp shingle 2
Roof Plane 3 Pass
Pitch 3/12
Roof Covering Asphalt or composition
shingles
Number of coverings of comp shingle 2
Roof Plane 4 Pass
Pitch 3/12
Roof Covering Asphalt or composition
shingles
Number of coverings of comp shingle 2
Fire Pass
Percentage of the Roof with a Solar Array 9.5 %
Fire Pathways, venting and access in accordance with the SolarAPP Fire Bulletin and/or the AHJ
requirements therein
Disconnecting Means are in compliance with the SolarAPP Fire Bulletin
Energy Storage Equipment locations are in accordance with the SolarAPP Fire Bulletin
Energy Storage Equipment capacities are in accordance with the SolarAPP Fire Bulletin
Energy Storage Equipment installations are compliant with the safety measures required in the SolarAPP
Fire Bulletin
Signage, Placards, Directories and Markings in accordance with the SolarAPP Fire Bulletin
Maximum AC operating current in labels [NEC 690.54]96 A
Maximum AC operating voltage in labels [NEC 690.54]240 V
Corrections
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 6/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
SolarAPP+™ Fire Bulletin
Disconnecting Means SolarAPP+™ Fire Bulletin
PV System
PV system disconnecting means shall be provided in accordance with the 2020 National Electrical Code® (NEC), NFPA 70.(R) [690.13]
A Rapid Shutdown switch shall be provided at a readily accessible location outside the building in accordance with the 2020 National
Electrical Code® (NEC), NFPA 70.® [690.12(C)]
Energy Storage System
A disconnecting means is required for all ungrounded conductors derived from an ESS [NEC 706.15(A)]
The disconnecting means can be integral to listed ESS equipment [NEC 706.15(A)]
The disconnecting means must be readily accessible [NEC 706.15(A)(1)]
The disconnecting means must be within sight of the ESS or as close as practicable with a marking [NEC 706.15(A)(2)]
The disconnecting means must be lockable open in accordance with 110.25 [NEC 706.15(A)(3)]
For one-family and two-family dwellings, a disconnecting means or its remote control shall be located at a readily accessible location
outside the building. [NEC 706.15(A)]
Where remote actuation of the disconnecting means is employed the controls are not within sight of the ESS, the disconnecting means
shall be capable of being locked in the open position. [NEC 706.15(B); 110.25]
Where circuits from the input or output terminals of energy storage components in an ESS pass through a wall, floor, or ceiling, a readily
accessible disconnecting means shall be provided within sight of the energy storage component. Fused disconnecting means or circuit
breakers shall be permitted to be used. [NEC 706.15(D); 706.31(F)]
The marking for the ESS must indicate whether it is open or closed and be permanently marked “ENERGY STORAGE SYSTEM
DISCONNECT.” The disconnecting means must be legibly marked with nominal ESS ac voltage, maximum ESS dc voltage. [NEC
706.15(C)]
Signs, Placards, Directories, and Markings
Guidance
SolarAPP+™ Fire Bulletin
General
All labeling shall comply with Articles 690 and 705 of the 2020 National Electrical Code® (NEC), NFPA 70
All labeling shall comply with Section 324 of the 2021 International Residential Code
All labeling shall comply with [NEC 110.21 (B)]
Rapid Shutdown Label
Buildings with more than one rapid shutdown type:A detailed plan view diagram showing each PV system and a dotted line around areas
that remain energized after the rapid shutdown switch is operated. [NEC 690.56(C)(2)]
Rapid Shutdown (PV Hazard Control) switch:This switch shall have a label not greater than 3 feet from the switch that states the following:
RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM [NEC 690.56(C)(1)]
Roof Access, Egress, and Ventilation SolarAPP+™ Fire Bulletin
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 7/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
General
Access and minimum spacing shall be provided for access to specific areas of the roof, emergency egress from the roof and opportunities
for smoke ventilation in accordance with the 2021 International Residential Code [IRC 324.6]
References:
Ridge Setbacks - [IRC R324.6.2]
Sprinklered Occupancies - [IRC R324.6.2.1]
Pathways - [IRC 324.6.1]
Emergency escape and rescue openings - [IRC R324.6.3]
Exceptions:
Detached, non-inhabitable structures [IRC R324.6 Ex. 1]
Low-slope roofs with pitch of less than or equal to 2:12; this exception may not be valid depending on the jurisdiction. [IRC R324.6 Ex. 3]
Carbon Monoxide, Smoke & Heat Detectors SolarAPP+™ Fire Bulletin
Guidance:
Where required, Carbon Monoxide and smoke detectors shall be provided in accordance with the code or an Affidavit has been provided
by the customer. 2021 International Residential Code.[R314, R315]
Rooms and areas within dwelling units, basements and attached garages in which ESS are installed shall be protected by smoke alarms in
accordance to the code. A heat detector, listed and interconnected to the smoke alarms, shall be installed in locations within dweling units
and attached garages where smoke alarms cannot be installed based on their listing. 2021 International Residential Code.[R314, R315,
R328.7]
Energy Storage System SolarAPP+™ Fire Bulletin
Special Considerations
Individual energy storage systems shall be separated from each other by at least three feet of spacing unless smaller separation distances
are documented to be adequate as approved by the code official based on large scale fire testing. [IRC R328.3.1]
Individual ESS unit ratings shall not exceed 20kWh. [IRC R328.5]
ESS shall be installed only in the following locations:1. Detached garages and detached accessory structures.2. Attached garages
separated from the dwelling unit living space in accordance with the Code.3. Outdoors or on the exterior side of exterior walls located not
less than 3 feet (914 mm) from doors and windows directly entering the dwelling unit.4. Enclosed utility closets, basements, storage or
utility spaces within dwelling units with finished or noncombustible walls and ceilings. Walls and ceilings of unfinished wood-framed
construction shall be provided with not less than 5/8 inch Type X gypsum wallboard. [IRC R328.4]
ESS shall not be installed in sleeping rooms, or closets or spaces opening directly into sleeping rooms. [IRC R328.4]
Aggregate energy ratings shall not exceed:40kWh within utility closets, basements, and storage or utility spaces80kWh in attached or
detached garages and detached accessory structures80kWh on exterior walls80kWh outdoors on the ground0kWh in habitable space [IRC
R328.4,R328.5]
When the ESS is installed in a location subject to vehicle damage it shall be protected by approved barriers. [IRC R328.8]
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 8/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
ESS installed indoors that produce hydrogen or other flammable gases during charging shall be provided with either natural or mechanical
ventilation in accordance with Section M1307.4.1 or M1307.4.2. [IRC R328.9; M1307.4]
Documentation and labeling
A copy of the manufacturer’s installation, operation, maintenance and decommissioning instructions shall be provided to the owner or
placed in a conspicuous location near the ESS equipment. [IRC R328.11]
A label on the installed system containing the contact information for the qualified maintenance and service providers. [IRC R328.11]
Fire Classification SolarAPP+™ Fire Bulletin
PV System
Rooftop-mounted PV systems shall have the same fire classification as the roof assembly required in 2021 International Residential Code.
[R902.4; R324.4.2]
Building-integrated photovoltaic products installed as the roof covering shall be tested, listed, and labeled for fire classification. [IRC
R902.3, R324.5.2]
Building-integrated photovoltaic products installed as the roof covering shall comply with the minimum requirements for fire classification
set by the jurisdiction. [IRC R902.1]
Product Certifications SolarAPP+™ Fire Bulletin
PV System
PV panels and modules shall be listed and labeled to UL 1703 and/or both UL 61730-1 and UL 61730-2 [NEC 690.4(B)] [IRC R324.3.1]
Inverters shall be listed and labeled to UL 1741 [NEC 690.4(B)] [IRC R324.3.1]
Energy Storage System
The ESS inverter, for AC Coupled systems, shall be listed and labeled to UL 1741 [IRC R328.6]
The ESS shall be listed and labeled to UL 9540 [IRC R328.2]
The ESS Microgrid Interconnection Device shall be listed and labeled to UL 1741 [IRC R328.6]
Hazard Control System
Hazard control system shall be listed and labeled to UL 3741 [NEC 90.7; 110.3(C); 690.4(B); 690.12(B)(2)(1); 690.12(D)]
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 9/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Signs, Placards, Directories, and Markings SolarAPP+™ Fire Bulletin
Service Disconnect
"SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN"
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN ARRAY.
Simple Diagram Here
Location: At each service equipment location to which the PV
systems are connected.
Code: [NEC 690.56(C)]
RSD Initiation Device
RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM
Location: Rapid shutdown initiation device.
Code: [NEC 690.56(C)(2)]
Point of Interconnection
"CAUTION: MULTIPLE SOURCES OF POWER"
(LAYOUT OR DESCRIPTION)
Location: Service location or approved readily accessible location
Code: [NEC 705.10; 706.21(A)]
WARNING:
DUAL POWER SOURCE
SECOND SOURCE IS PV SYSTEM
Location: Electrical Equipment containing overcurrent devices in
circuits supplying power to a busbar or conductor supplied from
multiple sources
Code: [NEC 705.12 (C)]
WARNING:
TRI POWER SOURCE
SECOND SOURCE IS PV SYSTEM
THIRD SOURCE IS ENERGY STORAGE SYSTEM
WARNING:
POWER SOURCE OUTPUT CONNECTION -
DO NOT RELOCATE THIS OVERCURRENT DEVICE
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 10/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Location: Electrical Equipment containing overcurrent devices in
circuits supplying power to a busbar or conductor supplied from
multiple sources
Code: [NEC 705.12 (C)]
Location: At back-feed breaker if using 120% rule (if applicable)
Code: [NEC 705.12(B)(3)(2)]
WARNING:
THIS EQUIPMENT FED BY MULTIPLE SOURCES.
TOTAL RATING OF ALL OVERCURRENT DEVICES
EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE,
SHALL NOT EXCEED AMPACITY OF BUSBAR
Location: At distribution equipment adjacent to the back-fed
breaker from the power source when using this "sum of breakers"
code compliance rule.
Code: [NEC 705.12(B)(3)(3)]
WARNING:
ELECTRIC SHOCK HAZARD
TERMINALS ON THE LINE AND LOAD
SIDES MAY BE ENERGIZED IN THE OPEN POSITION
Location: For ESS disconnecting means where the line and load
terminals may be energized in the open position.
Code: [NEC 705.15(C)]
PHOTOVOLTAIC POINT OF INTERCONNECTION
MAXIMUM AC OPERATING CURRENT:
MAXIMUM AC OPERATING VOLTAGE:
Location: All interactive system(s) points of interconnection.
Code: [NEC 690.54]
DC Circuit Raceways and Enclosures
PHOTOVOLTAIC POWER SOURCE
Location: Unless located and arranged so the purpose is evident,
labels will be required for DC Circuit Raceways and Enclosures,
conduit, and combiner/junction boxes.
Code: [NEC 690.31(D)(2)]
PV System Disconnect
WARNING: ELECTRIC SHOCK HAZARD TERMINALS ON LINE
AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN
POSITION
PV SYSTEM DISCONNECT
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 11/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Location: DC Disconnecting Means where terminals on both line
and load side may remain energized. Example language or
equivalent.
Code: [NEC 690.13(B)]
Location: Each PV System Disconnect (May be AC or DC)
Code: [NEC 690.13(B)]
DC String Inverters Equipment Disconnects
WARNING:
ELECTRIC SHOCK HAZARD
TERMINALS ON THE LINE AND LOAD
SIDES MAY BE
ENERGIZED IN THE OPEN POSITION
Location: Each PV system disconnecting means where line and
load may be energized in the open position
Code: [NEC 690.13(B)]
PHOTOVOLTAIC DC DISCONNECT
Location: Each PV system disconnecting means.
Code: [NEC 690.13(B)]
PV SYSTEM MAXIMUM VOLTAGE:
Location: At each DC PV system disconnecting means.
Code: [NEC 690.53]
Roof Access and Ventilation Diagrams SolarAPP+™ Fire Bulletin
Ridge Setbacks
PV Less Than 33% Roof Area (66% for homes with sprinkler systems) [IRC R324.6.2]
PV More Than 33% Roof Area (66% for homes with sprinkler systems) [IRC R324.6.2.1]
Hips & Valley Setbacks
PV Less Than 33% Roof Area - Street Access (66% for homes with sprinkler systems) [IRC R324.6.1]
PV More Than 33% Roof Area - Street Access (66% for homes with sprinkler systems) [IRC R324.6.1]
PV Less Than 33% Roof Area - Driveway Access (66% for homes with sprinkler systems) [IRC R324.6.1]
PV More Than 33% Roof Area - Driveway Access (66% for homes with sprinkler systems) [IRC R324.6.1]
Emergency Escape & Rescue Opening
Minimum 3' Emergency Escape Pathway [IRC R324.6.3]
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 12/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 13/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
FIRE SAFETY CODE REQUIREMENTS
Does the home have sprinkler systems?No
Percentage of Roof Area covered with PV Total Array Area / Total Roof Area 9.50%
Roof Access and Ventilation Diagrams
Fire Safety
Ridge Setbacks
PV Less Than 33% Roof Area (66% for homes with sprinkler
systems) or per AHJ appendix.
Emergency Escape & Rescue Opening
Minimum 3’ Emergency Escape Pathway
Hips and Valley Setbacks
PV Less Than 33% Roof Area - Street Access (66% for homes with
sprinkler systems) or per AHJ appendix.
PV Less Than 33% Roof Area - Driveway Access (66% for homes
with sprinkler systems) or per AHJ appendix.
Powered by TCPDF (www.tcpdf.org)
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 14/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
INPUTS
Permit Details [80.19(H) ; R105.3]
GENERAL
Project Information
Project Title JB-95023712-00
Address 10861 Maxine Ave,
Cupertino, CA 95014
Homeowner's full name Amit Verma
Confirm that you have verified the homeowner's information and right to install on
the property.
Yes
AHJ City of Cupertino, CA
This project's scope includes Photovoltaic Panels Yes
This project's scope includes Energy Storage Equipment Yes
Code Cycle 2020/2021
NEC Code Cycle 2020
IRC Code Cycle 2021
Scope of Work 8.2 kW PV Array
27 kWH Energy Storage System
125a Load Center
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 15/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Project Valuation is required for calculating the AHJ permit fee Yes
Project Valuation 32666.68
PV System Size AC (kW)11.51 kW
PV System Size DC (kW)8.2 kW
Confirm you have reviewed SolarAPP+ eligibility:Yes
The system will be installed on a permitted structure Yes
Will this system be installed on a new construction?No
Installation Applicability and Compliance
All work will comply with the 2020 National Electrical Code (NFPA 70), the
International Code Council 2021 I-Codes, Minimum Design Loads and Associated
Criteria for Buildings and Other Structures (ASCE/SEI 7-16), UL Standards,
Manufacturer's instructions, and Municipal requirements.
Yes
State License
Type state
Number 888104
City Business License
Type city
Number BL400871
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 16/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Inspection Guidelines
The installer is responsible for following the manufacturer's instructions for all installed equipment and for having them
ready for review upon inspector request.
All wire sizes shown are a minimum, unless indicated otherwise, and the installer may upsize them at their discretion.
All OCPD ratings shown must match the inspection checklist and be installed per the equipment manufacturer's
instructions, any ratings that do not match the inspection checklist are valid reasons for inspection failure.
Where distribution equipment, such as the main service panel or subpanel buses, are fed simultaneously by a primary
source(s) of electricity and one or more other power sources, interconnection shall have a method of compliance at each
panel board with both a primary source and other power source(s).
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 17/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
FIRE
I hereby affirm that I will comply with all requirements and guidelines as set out by
the SolarAPP Fire Bulletin.
Yes
Does the home have sprinkler systems?No
Total array area 413.34 sqft
Total roof area 4351 sqft
Percentage of Roof Area covered with PV Total Array Area / Total Roof Area 9.5 %
See Fire Setback Diagram attached.Less Than 33/66
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 18/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
STRUCTURAL
General
The weight of the PV system in lbs/sq ft [IRC R301.4]3 psf
The AHJ default ground snow load is [IRC Table R301.2; IRC Fig R301.2(3)
R301.2(4)]
0 lb/sqft
The site specific ground snow load will be overridden by the local design ground
snow load
Yes
The design snow load is 0 lb/sqft
Proposed maximum spacing in inches between adjacent attachment points of the
mounting system
72 in
Will attachment points of the mounting system be staggered?No
The number of roof surfaces at different slopes and/or orientations that will be used
for installation are: .Note: 1 means all roofs used have the same orientation.
4
Type of mounting for the PV system Flush mount
The AHJ default wind speed is 95 MPH
The site specifc wind speed will be overridden by the local design wind speed Yes
Design wind speed 95 MPH
Mounting Planes
Mounting Plane Type 1
Maximum distance from the lowest point of the module to the roof 4 in
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 19/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Mounting Plane Type 1
The current roof covering is [IRC Section R905; R308.4]Asphalt or composition shingles
The number of comp shingle layers that are currently present is . [R908.3.1.1]2
The pitch of the roof surface is [IRC Section R905]3/12
Mounting Plane Type 2
Maximum distance from the lowest point of the module to the roof 4 in
The current roof covering is [IRC Section R905; R308.4]Asphalt or composition shingles
The number of comp shingle layers that are currently present is . [R908.3.1.1]2
The pitch of the roof surface is [IRC Section R905]3/12
Mounting Plane Type 3
Maximum distance from the lowest point of the module to the roof 4 in
The current roof covering is [IRC Section R905; R308.4]Asphalt or composition shingles
The number of comp shingle layers that are currently present is . [R908.3.1.1]2
The pitch of the roof surface is [IRC Section R905]3/12
Mounting Plane Type 4
Maximum distance from the lowest point of the module to the roof 4 in
The current roof covering is [IRC Section R905; R308.4]Asphalt or composition shingles
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 20/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Mounting Plane Type 4
The number of comp shingle layers that are currently present is . [R908.3.1.1]2
The pitch of the roof surface is [IRC Section R905]3/12
Wind Speed
Is the solar module and mounting system rated by the manufacturer to withstand the
upward force of the local wind speed (95 MPH) and evenly distribute load into the
supporting structure at the proposed maximum spacing, and confirmed in UL 1703
or 61730 (Part 1 & 2), and 2703 listings? [IRC R324.4.1.2; R324.3.1]
Yes
Roof Condition
Does the roof structure appear to be structurally sound, without signs of alterations
or significant structural deterioration or sagging?
Yes
Energy Storage Equipment Mounting
Large Scale Fire Testing
Should SolarAPP+ disable UL 9540A Spacing Exceptions for this jurisdiction?No
Will the separation between Energy Storage Equipment units be less than 3 feet?No
Seismic Design Category
Seismic Design Category for this area (SolarAPP only covers Risk Category I-III
structures) [ASCE 7-16 Table 11.6-1]
SDC E
Will the Energy Storage Equipment be installed per the manufacturer's instructions?Yes
Is the Energy Storage Equipment attached to the building using appropriate
fasteners per the manufacturer? [ASCE 7-16 13.1.4.5.a]
Yes
How much does the Energy Storage Equipment assembly weight?290 lbs
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 21/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Seismic Design Category
Is the center of mass of the Energy Storage Equipment located less than 4ft from the
floor? [ASCE 7-16 13.1.4.6.a]
Yes
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 22/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
ELECTRICAL
Equipment
Architecture type used for all inverters in this project String Inverter without DC-DC
Converters
Inverter 1
Inverter 1 Model Number 1707000-XX-Y [240V, 11.5kW]
Datasheet for Inverter 1: See attached. [NEC 90.7; 110.3(C)]POWERWALL3_up_Nov_8_2023
.pdf
Inverter 1 Manufacturer:Tesla Inc.
Is Inverter 1 UL 1741 listed? [NEC 110.3(C); 690.4(B)]
What is the maximum fuse rating allowed on Inverter 1?60 A
Will you use a Power Control System to curtail the Maximum Continous Output
Power of the Inverter 1? [NEC 705.13]
No
Inverter 1 Maximum Continous Output Power 11.51 kW
Where will inverter 1 be interconnected?Main Service Panel
Inverter 2
Where will inverter 2 be interconnected?0
Modules
Module 1 Model Number Q.PEAK DUO BLK ML-
G10.a+/TS 410
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 23/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Modules
Datasheet for Module 1: See attached. [NEC 90.7; 110.3(C)]Q.PEAK DUO BLK ML-G10+
SERIES TS410.pdf
Module 1 Manufacturer Qcells North America
Module 1 is UL 1703 or UL 61730 (Part 1 & 2) listed [NEC 110.3(C); 690.4(B)]
Module 1 quantity 20
Module open circuit voltage with record low temperature correction 48.51 V
Module short circuit current with average high temperature correction [NEC
690.8(A)(1)(a)(1)]
14 A
Is the PV module bifacial?No
Module fire rating type 2
Racking System
Racking System Model Number ZS Comp
Racking System Manufacturer Zep Solar Inc.
Datasheet for Racking System: See attached. [NEC 90.7; 110.3(C)]ZS Comp V3.5
Flashing_UP.Oct.14.2022.pdf
Is the Racking System UL 2703 listed for grounding and bonding with the PV module
models specified in this SolarAPP project? [NEC 90.7; 110.3(C); 690.43(A)]
Yes
The combination of modules and racking system shall have the same fire
classification as the roof assembly. [IRC R324.4.2; R902.4]
Yes
Name/description of roof penetration sealant method to be used.Flashing Insert
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 24/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Racking System
You have agreed to install the sealant method per the manufacturer's instructions for
the means of accomplishing weather proofing [IRC R324.4.3]
Yes
Fire classification [IRC R324.4.2]A
Compatible roof pitch regime Pitched
Compatible module fire rating types 1,2
Maximum gap between the roof and the lowest point of the module 10 in
Compatible Roof Types Asphalt or composition shingles
Rapid Shutdown
Rapid Shutdown Device Manufacturer Tesla
Rapid Shutdown Device Model Number MCI-1
Datasheet for Rapid Shutdown Device [NEC 90.7; 110.3(C)]Solar_Shutdown_Device_UP.Jun
e.26.2023.pdf
Module open circuit voltage is below the Rapid Shutdown maximum DC input
voltage. The maximum DC input voltage for the rapid shutdown device is
600 V
Module short circuit current is below the Rapid Shutdown maximum DC input
current. The maximum DC input current for the rapid shutdown device is
19 A
Method of Rapid Shutdown Compliance Inside the Array Hazard Control System
Certification of the Hazard Control System (HCS) under UL 3741 as PV Rapid
Shutdown Array (PVRSA). See attached. [NEC 90.7; 110.3(C)]
PVRSA_June.2023.pdf
Are PV arrays UL 3741 listed? [NEC 90.7; 110.3(C); 690.4(B); 690.12(B)(2)(1);
690.12(D)]
Yes
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 25/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Energy Storage Architecture
The equipment used for energy storage is Energy Storage System
Number of distinct Energy Storage System Models used 2
Each ESS unit has a dedicated OCPD, there are no parallel connections between
AC coupled ESS units.
Yes
Energy Storage Equipment Location
Location of the Energy Storage Equipment units [IRC R328.4]Outdoor walls
Will the Energy Storage Equipment be located not less than 3 feet (914 mm) from
doors and windows directly entering the dwelling unit? [IRC R328.4(3)]
Yes
Will the energy storage equipment be installed in a location subject to vehicle
damage? [IRC R328.8]
No
Energy Storage System Model 1
ESS Manufacturer Tesla Inc.
ESS Model Number 1707000-XX-Y [11.5kW]
ESS and PV inverter are certified as a single product with a single AC output and
with no field wiring between the battery components and the inverter components.
Yes
An AC coupled ESS, with a dedicated AC output and OCPD different from the PV
inverter will be installed.
No
The ESS is certified to UL 9540 [IRC R328.2]2023-03-23
Individual ESS energy capacity [IRC R328.5]13.5 kWh
Where will Energy Storage Systems be interconnected?Main Service Panel
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 26/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Energy Storage System Model 2
ESS Manufacturer Tesla Inc.
ESS Model Number 1707000-XX-Y [11.5kW]
The Energy Storage System output voltage matches the Single Phase Grid Voltage 240
Will you use a Power Control System to curtail the Maximum Continous Output
Power of the ESS? [NEC 705.13]
No
ESS and PV inverter are certified as a single product with a single AC output and
with no field wiring between the battery components and the inverter components.
No
An AC coupled ESS, with a dedicated AC output and OCPD different from the PV
inverter will be installed.
Yes
The ESS is certified to UL 9540 [IRC R328.2]2023-03-23
Upload datasheet. See attached.Tesla Powerwall3_UP.February.2
8.2024.pdf
Quantity of ESS units 1
Individual ESS energy capacity [IRC R328.5]13.5 kWh
Where will Energy Storage Systems be interconnected?Main Service Panel
Site Conditions
Ambient Dry Bulb Extreme Record Low Temperature (°C) [NEC 690.7(A)]-0.4 °C
Ambient Dry Bulb Average High Temperature (°C)30.7 °C
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 27/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Single Phase Grid Voltage 240 V
Existing Systems
Is there an existing Utility interactive power production source connected to the
home's electric service?
No
Existing System 1
Inverter manufacturer for existing system circuit #1 N/A
Inverter model for existing system circuit #1 N/A
What is the quantity of inverters in the existing system circuit #1 N/A
Where are the existing system circuits of inverter #1 interconnected?N/A
Total output power of existing system circuit #1 0 kW
Total output current of existing system circuit #1 0 A
Installation Details
Are DC and AC conductors copper, Class B or Class C, and THWN-2, NM, USE-2,
PV Wire, or jacketed multiconductor cable assembly listed and identified for the
application? [NEC 690.8(B); 690.31(A); 690.31(C); 310.15(A);310.15(B)]
Yes
Are all rooftop conduits mounted at least 7/8" above the roof surface [NEC
310.15(B)(2)]:
Yes
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 28/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Are all conductors installed without raceway listed as PV Wire, USE-2 or Type
distributed generation (DG) cable? [NEC 690.31(C)(1)]
Yes
Are all power terminals rated to 75°C or greater, labeled for use with Copper Class
B or Class C wires, and accept at least 8 AWG wire? [NEC 110.14]
Yes
Where Equipment Grounding Conductors (EGC) or Grounding Electrode Conductors
(GEC) are not routed with circuit conductors, they are a minimum of 6 AWG or they
are protected from physical damage [NEC 250.120(C); 250.64(B)(3)]
Yes
DC strings EGC is a minimum of 10 AWG Yes
Module voltage and current DC specifications fall within allowable range of
connected equipment
Yes
All equipment is listed for the application, rated equal to or greater than the
connected overcurrent device and installed per the manufacturer's instructions.
Documentation shall be provided at time of inspection.
Yes
Is there a utility available fault current greater than 10kA at the service?No
Inverter without DC-DC Converters
Maximum PV Source Circuit Voltage
Max quantity modules in DC series string 8 modules
Maximum PV Source Circuit VoltageCalculation:For DC strings of modules, using
the Voc of proposed modules, the lowest ambient temperature entered above, and
the temperature coefficient provided by the manufacturer, calculate that maximum
voltage for the quantity of modules in a DC string entered above does not exceed
600V using the following formula:( ( pv_beta_Voc * pv_Nameplate_Voc / 100 ) * (
record_low_temperature - 25 ) + pv_Nameplate_Voc) * I24
388.11 V
PV Source Circuit
PV module series strings from solar arrays to the PV inverter are combined in
parallel
Yes
There are more than 2 PV module series strings combined in parallel.No
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 29/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
PV Source Circuit
Do each of the parallel strings have a dedicated MPPT at the inverter?Yes
PV inverter maximum input DC open circuit voltage (Voc)600 V
PV inverter maximum input DC short circuit current (Isc)15 A
Maximum number of DC PV wire or USE-2 conductors in a raceway from solar
arrays to the PV inverter, excluding any equipment grounding conductors.
8 wires
Maximum number of DC THWN-2 conductors in a raceway from solar arrays to the
PV inverter, excluding any equipment grounding conductors.
6 wires
Minimum DC Wire Gauge (PV Wire) for a single series string - See Table 1 12 AWG
Minimum DC Wire Gauge (THWN-2 Wire) for a single series string - See Table 1 12 AWG
Minimum DC Wire Gauge (PV Wire) for parallel strings - See Table 1 8 AWG
Minimum DC Wire Gauge (THWN-2 Wire) for parallel strings - See Table 1 10 AWG
Table 1 [NEC 240.4(D); Table 310.15(C)(1); Table 310.15(B)(2); Table 310.16; 690.8(A)(1); 690.8(B)]
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 30/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
PV Source Circuit
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 31/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Inverter Output Circuit
See Table 3 below for selection of minimum Inverter output wire size and inverter output overcurrent protection size
Inverter 1: Inverter Continuous Output Current = Power / Site Voltage:47.95 A
Table 3.1 [NEC 240.4(D); table 310.15(C)(1); table 310.15(B)(2); table 310.16; 690.8; 690.9; 705.30; 220.5 (B)]
Inverter 1 - See Table 3 for the minimum Overcurrent Protection Device rating. [NEC
690.9(A); 690.9(B); Table 240.6(A)]
60 A
Inverter 1 Overcurrent Protection Device rating [NEC 690.9(A); 690.9(B)]60 A
Maximum number of THWN-2 conductors in an PV inverter AC output circuit
raceway, excluding any equipment grounding conductors.
3 wires
Inverter 1 - See Table 3.2 for the selection of the AC wire size in raceway 6 AWG
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 32/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Inverter Output Circuit
Table 3.2 [NEC 240.4(D); table 310.15(C)(1); table 310.15(B)(2); table 310.16; 690.8; 690.9; 705.30; 220.5 (B)]
Grounding & Bonding
See Table 5 for selection of Equipment Grounding Conductor wire gauge.
Inverter 1 - See table 5 for Equipment Grounding Conductor (EGC) based on
overcurrent protective device
10 AWG
Table 5 [NEC Table 250.122]
ESS Model 2
ESS Architecture
This is an AC Coupled ESS
Installation Details
The ESS inverter is certified to UL 1741 [IRC R328.6]
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 33/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Individual ESS Inverter output
Maximum Continuous Discharge Power (kW)11.5 kW
Maximum Continuous Discharge Current (A) [NEC 706.30]47.92 A
ESS - See Table 3.1 for the minimum Overcurrent Protection Device rating. [NEC
705.30; Table 240.6(A)]
60 A
ESS Overcurrent Protection Device rating [NEC 690.9(A); 690.9(B)]60 A
Maximum number of THWN-2 conductors in the AC coupled ESS inverter output
circuit raceway, excluding any equipment grounding conductors.
3 wires
Based on Table 3.2, calculate ESS inverter output conductor gauge 6 AWG
Grounding
Based on Table 5, calculate Equipment Grounding Conductor size per ESS inverter
output circuit
10 AWG
Energy Storage System
Combined Capacity
Table 3.1 [NEC 240.4(D); table 310.15(C)(1); table 310.15(B)(2); table 310.16; 690.8; 690.9; 705.30; 220.5 (B)]
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 34/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Combined Capacity
Table 3.2 [NEC 240.4(D); table 310.15(C)(1); table 310.15(B)(2); table 310.16; 690.8; 690.9; 705.30; 220.5 (B)]
Table 5 [NEC Table 250.122]
Combined continuous output current of all ESS inverters.47.92 A
Total ESS Capacity 27 kWh
Backup Initiation Device
Will you install a Backup Initiation Device?Yes
Will the Energy Storage Equipment charge from the Grid?0
Backup Initiation Device type MID
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 35/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Backup Initiation Device integration method Meter Mounted
Backup Initiation Device manufacturer Tesla Inc.
Backup Initiation Device model 1624171-XX-Y
Ampere rating of the Backup Initiation Device 200 A
The MID is listed and labeled to UL1741
The Meter Socket Adapter is listed and labeled to UL414
Backup Loads
Will the Energy Storage System have adequate capacity to supply connected
equipment or backup loads in the event of a grid outage? [NEC Article 710][NEC
Article 702]
Yes
Backup capacity 96 A
The rating of the largest utilization load shall be below the backup capacity [NEC 710.15(A)]
Electrical Work
Main Panel Upgrades and Main Breaker Derates
A Main Panel Upgrade is being performed.No
A Main Breaker Derate is being performed.No
Busbars
Busbar quantity 2
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 36/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Busbar 1
Busbar name Existing Main Service Panel
Busbar name parameters passed to table 35.3 No,Yes,Main Service
Panel,-,Yes,Yes,-,-
Is this a combiner panel?No
Is this an existing busbar?Yes
Select the type of existing busbar Main Service Panel
Ratings
Existing Main Service Panel busbar ampere rating 200 A
Rating of the OCPD protecting the Existing Main Service Panel 200 A
Feeders
Table 3.1
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 37/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Feeders
Table 23.1 [NEC 240.4(D); 310.12 ; Table 310.15(C)(1) ; Table 310.15(B)(2) ; Table 310.16 ; 690.8; 690.9; 705.30]
Table 23.2 [NEC 240.4(D); 310.12 ; Table 310.15(C)(1) ; Table 310.15(B)(2) ; Table 310.16 ; 690.8; 690.9; 705.30]
Table 23.3 [NEC 240.4(D); 310.12 ; Table 310.15(C)(1) ; Table 310.15(B)(2) ; Table 310.16 ; 690.8; 690.9; 705.30]
Feeder Interconnection
Generation source connected at the feeders of the Existing Main Service Panel No
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 38/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Feeder Interconnection
Are you connecting your power production sources to the Existing Main Service
Panel feeders at a location other than the downstream end of the feeder? [NEC
705.12 (B) (3) (6); 705.12 (B) (1) (a); 705.12 (B) (1) (b)]
N/A
Ground
Table 5 [NEC Table 250.122]
Interconnection compliance
Backfeed from Generation Sources at Point of Interconnection A at the Existing Main
Service Panel
95.87 A
Total backfeed at the Existing Main Service Panel 95.87 A
Maximum continous current at the Existing Main Service Panel 160 A
The Existing Main Service Panel is subject to backfeed.Yes
Compliance method for the Existing Main Service Panel Power Control System
Power Control System employed in busbar Existing Main Service Panel
The manufacturer's instructions shall be followed accurately and CTs shall be correctly installed to monitor all sources of
supply to the Existing Main Service Panel [NEC 705.13 (B)]
The PCS controller shall monitor all currents within the PCS. The sum of all PCS-controlled currents plus all monitored
currents from other sources of supply shall not exceed the ampacity of any busbar or conductor supplied by the power
production sources.
Is there a Main Breaker protecting the busbar from generation sources
interconnected at its feeders?
No
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 39/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Busbar 2
Busbar name Combiner Panel
Busbar name parameters passed to table 35.3 No,No,-,No,Yes,Yes,-,-
Is this a combiner panel?Yes
Relocated Loads Panel
Will you relocate one or more existing loads to the new busbar?No
Combiner Panel
Will you use this new busbar for combining generation sources output?Yes
Point of interconnection where the Combiner Panel is located Main Service Panel
The inverter 1 PV system is connected to the Combiner Panel Yes
The standalone Energy Storage System is connected to the Combiner Panel Yes
Do you have a dedicated OCPD protecting the Combiner Panel?Yes
Ratings
Combiner Panel busbar ampere rating 125 A
Rating of the OCPD protecting the Combiner Panel 125 A
Feeders
The length of the section of the Combiner Panel feeders that is inside a raceway is
less than or equal to 2 feet
Yes
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 40/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Feeders
Combined continous inverter output current on the Combiner Panel 95.87 A
See Table 3.1 for the minimum OCPD rating protecting the Combiner Panel 125 A
OCPD rating used to calculate the Combiner Panel feeders rating 125 A
Table 3.1
Based on Table 23, calculated conductor gauge for the Combiner Panel feeders 1 AWG
Table 23.1 [NEC 240.4(D); 310.12 ; Table 310.15(C)(1) ; Table 310.15(B)(2) ; Table 310.16 ; 690.8; 690.9; 705.30]
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 41/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Feeders
Table 23.2 [NEC 240.4(D); 310.12 ; Table 310.15(C)(1) ; Table 310.15(B)(2) ; Table 310.16 ; 690.8; 690.9; 705.30]
Table 23.3 [NEC 240.4(D); 310.12 ; Table 310.15(C)(1) ; Table 310.15(B)(2) ; Table 310.16 ; 690.8; 690.9; 705.30]
Ground
Equipment Grounding Conductor size for the Combiner Panel 6 AWG
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 42/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Ground
Table 5 [NEC Table 250.122]
Raceway
Raceway size for the new busbar feeders is compliant with 300.17 and Chapter 9
[NEC 300.17; Chapter 9]
Yes
Service
Service OCPD Location Existing Main Service Panel
Service OCPD Rating 200 A
The combined rating of the service disconnects is a minimum of 100A in one-family dwellings and 60A in all other
dwellings types. [NEC 230.79; 230.80]
Utility Service Rating 200 A
Point of Connection
Either the connected equipment is within line of sight and closer than 10ft to the point of interconnection or a
disconnect/isolation means are installed. [NEC 690.15 (A)]
Point of Connection at Service Feeders
Supply Side Connection
Are you connecting your power production sources in a supply side connection using
listed equipment in accordance with [NEC 705.11]?
No
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 43/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
Power Control System (PCS)
The Power Control System is listed to control one or more power production
sources, energy storage systems (ESS), and other equipment installed. [NEC
705.13, 705.13 (C)]
Yes
Largest power source OCPD rating 60
The rating of the OCPD of the largest power source controlled by the PCS does not exceed the rating of the busbar
protected by the PCS [NEC 705.13 (D)]
The access to settings of the PCS is restricted to qualified personnel. [NEC 705.13
(E), 240.6 (C)]
Yes
PCS setting [NEC 705.13 (A); 705.13 (B)]160 A
Supported Tie-Ins
A new backup load center is being installed No
A new sub panel is being installed No
The point of interconnection is at the existing subpanel No
A new non-backup load center is being installed No
A Main Panel Insert is being installed to relocate high demand loads from the
existing main service panel to a new main service panel outside of backup, reducing
the amount of loads that require relocation on projects with energy storage.
No
Main Service Panel type Regular
The busbar quantity per busbar category is aligned with the list of SolarAPP supported tie-ins.
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 44/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
A Main Service Panel has been found in the busbar inputs.
SolarAPP Supported Tie-Ins ID 1129
SolarAPP Supported Tie-Ins ID parameters PV+ST,Meter
Mounted,No,No,No,No,No,Main
Service Panel,Regular,No,No
Generation Sources Interconnection
Point of Interconnection Configuration Main Service Panel
Interconnection found at subpanel feeders No
Location A - Name Main Service Panel
Location A - Generation Sources (N) Inverter 1
(N) Energy Storage Systems
Location A - Total output current 95.87 A
Total output current from all generation sources 95.87 A
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 45/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
WORKERS' COMP
By applying for this permit, you represent and warrant that you (i) have (and will
have during the performance of the work) all valid approvals, certifications, and
licenses required for the performance of the work for which this permit is issued, (ii)
carry (and will carry during the performance of the work) all necessary insurance
required by law or governmental authority in the jurisdiction and (iii) will comply with
all applicable laws required in the performance of the work.
Yes
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 46/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
SolarAPP PV+ST Eligibility 10/29/2024
System
New residential energy storage systems (ESS)
New rooftop residential retrofit PV systems
Installed by contractor with all licenses required by jurisdiction
Lithium Ion batteries
Each residence must have a unique utility meter
Electrical
The project must comply with the applicable National Electric Code
600V maximum series string voltage
Single phase 240V or 208V residential utility services only
Aluminum wires are only allowed for backup initiation device feeders
Must use 600V rated PV wire, or equivalent, for exposed, rooftop DC conductors
Must use 90 deg C rated insulated wire
Max 2 DC strings in parallel
Inverter output circuit conductors must be THWN-2, or listed NM
Terminals must be rated to 75 deg C, labeled for use with Cu wires, and accept minimum 8 AWG wire
Microinverters or AC Modules branch circuit overcurrent protection device must be rated for a maximum of 20A
Permitted to install on up to or equal to 400A service
Permitted to install on up to or equal to 200A service disconnect
Permitted to install on up to or equal to 225A busbars
May include an existing PV system with one (1) module type and multiple PV inverters
May install only 1 PV module model
May install up to 2 inverters for string inverters
May install up to 1 inverter model for microinverters and AC modules
Conduit may not be schedule 80 PVC
Modules and inverters must be listed in the California Energy Commission’s database of approved equipment
Energy storage systems and batteries must be listed in the California Energy Commission’s database of approved equipment
Rapid shutdown cannot be satisfied using the method: No exposed wiring or conductive parts [690.12(B)(2)(3)]
No trenching allowed
May include up to two (2) points of interconnection to premises wiring systems
No new loads, only new monitoring circuits are allowed
Equipment listed for continuous use at 100% of its rating is not considered
ESS must be paired with new PV
May install only 1 racking system model
Height of rooftop conduit > = 7/8"
Flat plate PV modules only
Structural
Detached one- and two-family dwellings and townhomes not more than three stories above grade plane in height with a separate means of egress
Accessory structures to one- and two-family dwellings and townhomes not more than three stories above grade plane in height
Penetrations within 4 ft of the fire-rated property line on the roof of a townhome shall not be permitted.
Installations in multi-family structures or R-2 occupancies shall not be permitted.
Installations on mobile homes governed by Heath and Safety Code and/or Housing and Urban Development regulations shall not be permitted.
The project must comply with the applicable International Residential Code
PV system + hardware weight is less than or equal to 4.0 psf
No ground mounted systems
No carports or non-permanent structures
No modifications, alterations, or upgrades to the structure
At least 20% of each tilt-up mounted array must be contained under 2 feet above the roof
The new system must be installed on a permitted structure
ESS must be less than 400lbs and its center of mass shall be located less than 4ft from the floor in high seismic areas (Seismic Design Category D,E,F)
No wood shake or wood shingle roofing allowed with a new rooftop PV system
Limit of 10" above the roof for flush mount PV arrays on pitched (>2/12) roof surfaces
Metal roof or low-slope roof installations in areas with > 15psf snow load are not supported
Fire
Page 1/2
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™Page 47/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)
SolarAPP PV+ST Eligibility 10/29/2024
The project must comply with the applicable International Residential Code
ESS shall not be installed within the habitable space of a dwelling unit.
Powered by TCPDF (www.tcpdf.org)
Page 2/2
Powered by TCPDF (www.tcpdf.org)
Approval ID: SA20241227-7142-109-2-A
Reviewed for Code compliance
12-27-2024
SolarAPP+™
Page 48/48
NEC 2020 IRC 2021 PV+ST (v2.7.0-1733912986 - prod)