DIR-2023-003 - DISH_Plans 12-22-2022Community Development Department
Planning Division — Cupertino
CUPLFTINO APPROVED
Ca e # DIR-2023-003
Application Number(s)
Ap rovaI Body: Director / Staff
Aprova I Date 02/23/23
Sigmaitrx1
IF USING 11"X17" PLOT, DRAWINGS WILL BE HALF SCALE
APPLICABLE CODES
ALL WORK AND MATERIALS SHALL BE PERFORMED AND INSTALLED IN
ACCORDANCE WITH THE CURRENT EDITIONS OF THE FOLLOWING CODES AS
ADOPTED BY THE LOCAL GOVERNING AUTHORITIES.
CALIFORNIA ADMINISTRATIVE CODE (INCL TITLE 24 & 25)
2019 CALIFORNIA BUILDING CODE
CITY/COUNTY ORDINANCES
BUILDING OFFICIALS & CODE ADMINISTRATORS (BOCA)
2019 MECHANICAL CALIFORNIA CODE
ANSI/EIA-222—F LIFE SAFETY CODE NFPA-101
2019 CALIFORNIA PLUMBING CODE
2019 CALIFORNIA ELECTRICAL CODE
LOCAL BUILDING CODE
I GENERAL NOTES
THE FACILITY IS UNMANNED AND NOT FOR HUMAN HABITATION.
HANDICAPPED ACCESS REQUIREMENTS ARE NOT REQUIRED
IN ACCORDANCE WITH THE 2019 CALIFORNIA BUILDING CODE. A
TECHNICIAN WILL VISIT THE SITE AS REQUIRED FOR ROUTINE MAINTENANCE.
THE PROJECT WILL NOT RESULT IN ANY SIGNIFICANT DISTURBANCE OR
EFFECT ON DRAINAGE; NO SANITARY SEWER SERVICE, POTABLE WATER, OR
TRASH DISPOSAL IS REQUIRED AND NO COMMERCIAL SIGNAGE IS
PROPOSED.
SITE INFORMATION
PROPERTY OWNER: PG&E
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
APPLICANT:
DISH WIRELESS
ADDRESS:
5701 S SANTA FE DR
LITTLETOWN, CO 80120
LATITUDE:
37.325142'
LONGITUDE:
—122.076758'
LAT/LONG TYPE:
NAD-83
GROUND ELEVATION:
±457.53' AMSL
ZONING JURISDICTION:
CITY OF CUPERTINO
CURRENT ZONING:
AGRICULTURAL (A)
ASSESSOR'S PARCEL NO.:
342-63-001
PROPOSED USE:
UNMANNED TELECOMMUNICATIONS
FACILITY
TYPE OF CONSTRUCTION:
TYPE V
OCCUPANCY GROUP:
U
EQUIPMENT LEASE AREA (SF):
±100 S.F.
I PROJECT TEAM I
APPLICANT:
DISH WIRELESS
5701 S SANTA FE DR
LITTLETOWN, CO 80120
SITE ACQUISITION:
QUALTEK WIRELESS
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
EMAIL: NCA_DISH@QUALTEKWIRELESS.COM
CONSTRUCTION MANAGER:
QUALTEK WIRELESS
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
CONTACT: JOSHUA ROBERSON
PH: (949) 505-4225
EMAIL: JROBERSON®QUALTEKWIRELESS.COM
ENGINEER:
M SQUARED WIRELESS
1387 CALLS AVANZADO
SAN CLEMENTE, CA 92673
CONTACT: MICHAEL MONTELLO
PH: (949) 391-6824
RE ENGINEER:
DISH WIRELESS
5701 S SANTA FE DR
LITTLETOWN, CO 80120
CONTACT: POOJA SHAH
wirehless`TM
DISH WIRELESS SITE ID: SFSFOO1041A
DISH WIRELESS SITE ADDRESS:
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
INSTALLATION OF TELECOMMUNICATION SITE
VICINITY MAP
SITE PHOTO
I
� r
mm~a
DRIVING DIRECTIONS
DIRECTIONS FROM SAN FRANCISCO INTERNATIONAL AIRPORT:
1. HEAD SOUTH
9. TURN LEFT
2. KEEP LEFT, FOLLOW SIGNS FOR US-101 S/SAN JOSE AND
10. TURN RIGHT
MERGE ONTO US-101 S
11. FOLLOW ACCESS ROAD TO SITE
3. KEEP RIGHT TO STAY ON US-101 S
12. DESTINATION WILL BE STRAIGHT AHEAD
4. TAKE EXIT 398B FOR CA-85 S TOWARD CUPERTINO/SANTA CRUZ
5. CONTINUE ONTO CA-85 S
6. TAKE EXIT 18 FOR STEVENS CREEK BLVD
7. TURN RIGHT ONTO STEVENS CREEK BLVD
8. TURN RIGHT ONTO CALIFORNIA OAK WAY
PROJECT DESCRIPTION
THIS IS NOT AN ALL INCLUSIVE LIST. CONTRACTOR SHALL UTILIZE SPECIFIED EQUIPMENT PART OR
ENGINEER APPROVED EQUIVALENT. CONTRACTOR SHALL VERIFY ALL NEEDED EQUIPMENT TO PROVIDE A
FUNCTIONAL SITE.
THE PROJECT GENERALLY CONSISTS OF THE FOLLOWING:
SECTOR SCOPE OF WORK:
INSTALL (3) NEW H—FRAMES (1 PER SECTOR)
INSTALL (3) NEW B139409 MOUNTS (1 PER SECTOR)
INSTALL (1) NEW 141415 MOUNT
INSTALL (3) NEW PANEL ANTENNAS (1 PER SECTOR)
INSTALL PROPOSED JUMPERS
INSTALL (6) NEW RR Us(2 PER SECTOR)
INSTALL (1) NEW SURGE SUPPRESSION DEVICE
INSTALL (1) NEW SPOOL CAN
INSTALL (1) NEW ±120' HYBRID CABLE
EQUIPMENT AREA SCOPE OF WORK:
INSTALL (1) NEW 10'X10' CONCRETE PAD
INSTALL (1) NEW H—FRAME
INSTALL (1) NEW CABINET
INSTALL (1) NEW NEMA 3 TELCO—FIBER BOX
REFERENCE RFDS REVISION 4, DATED 08/10/2022
DRAWING INDEX
SHEET NO:
SHEET TITLE
T-1
TITLE SHEET
PHOTOSIMS
T-2
T-3
PHOTOSIMS
T-4
PHOTOSIMS
LS-1
BOUNDARY DETAILS
LS-2
TOPOGRAPHIC SURVEY
A-1
OVERALL AND ENLARGED SITE PLAN
A-2
ANTENNA LAYOUT AND SCHEDULE
A-3
EQUIPMENT LAYOUT
A-4
ELEVATIONS
A-5
ELEVATIONS
A-6
EQUIPMENT DETAILS
A-7
EQUIPMENT DETAILS
A-8
EQUIPMENT DETAILS
A-9
EQUIPMENT DETAILS
E-1
ELECTRICAL DETAILS
E-2
SINGLE LINE DIAGRAM
E-3
UTILITY PLAN AND ENLARGED UTILITY PLAN
G-1
GROUNDING DETAILS (*PG&E GROUND GRID PENDING FROM PG&E)
G-2
GROUNDING DETAILS
RF-1
RF CABLE COLOR CODE
RF-2
PLUMBING DIAGRAM
GN-1
LEGEND AND ABBREVIATIONS
GN-2
GENERAL NOTES
GENERAL NOTES
GN-3
GN-4
GENERAL NOTES
APPROVALS
THE FOLLOWING PARTIES HEREBY APPROVE AND ACCEPT THESE DOCUMENTS & AUTHORIZE THE SUBCONTRACTOR
TO PROCEED WITH THE CONSTRUCTION DESCRIBED HEREIN. ALL DOCUMENTS ARE SUBJECT TO REVIEW BY THE
LOCAL BUILDING DEPARTMENT & MAY IMPOSE CHANGES OR MODIFICATIONS.
DISH WIRELESS RF ENGINEER: DATE:
DISH WIRELESS OPERATIONS: DATE:
SITE ACQUISITION: DATE:
CONSTRUCTION MANAGER: DATE:
PROPERTY OWNER: DATE:
ZONING: DATE:
PROJECT MANAGER: — DATE: —
d
wireless-
5701 S SANTA FE DR
LITTLETON, CO 80120
C7.U1.d*7M77f_
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
M SQIUAR60
WIRELESS
1387 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
DRAWN BY: EZG
CHECKED BY: MM
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S -JX COMMENT
C
06/29/2022
100% CD'S FOR REVIEW
B
1 02/09/2022
1 90% CD'S FOR REVIEW
01/14/2022
90%CD'S FOR REVIEW
rREAV
DATE
DESCRIPTION
DATE SIGNED: 12/22/2022
Loyal) A. Wb—., P.E.
Professional Engine: License: #C50547
Expiration Date: 06-30,2023
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
DO NOT SCALE DRAWINGS Q USA NORTH TITLE SHEET
G Know what's below.
SUBCONTRACTOR SHALL VERIFY ALL PLANS, Call before you dig.
EXISTING DIMENSIONS & FIELD CONDITIONS ON
THE JOB SITE & SHALL IMMEDIATELY NOTIFY SHEET NUMBER
THE ENGINEER IN WRITING OF ANY Call Two Working Days Before You Dig!
DISCREPANCIES BEFORE PROCEEDING WITH THE 811 / 800-227-2600 T-1
WORK OR BE RESPONSIBLE FOR SAME.
usanorth.org
Community Development Department
Planning Division — Cupertino
CUPEFTINO APPROVED
Ca e# DIR-2023-003
Appi" '° I NSQUAR
��� %;vlRl'iE5
Ap rova I Body: Director / Staff
02�23� J87 GAL CA AYARZA00
Apiprova I Date CLEMENTECA92613(914)3916824
Sig Ii ature Gian Paolo Martire
ICase Manager
SFSFOO1041 A
T R A N S M I S S I O N T O W E R
10110 CALIFORNIA OAK WAY CUPERTINO, CA 95014
v
.sh
wireless
VIEW 1 I SECTOR 'ALPHA' I LOOKING SOUTHEAST
wireless-
5701 S SANTA FE DR
LITTLETON, CO 80120
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
M SQUARK•J
WIRELESS
1387 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
DRAWN BY: EZG
CHECKED BY: MM
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S-JX COMMENT
C
06/29/2022
100%CD'S FOR REVIEW
B
02/09/2022
90%CD'S FOR REVIEW
A
01/14/2022
90%CD'S FOR REVIEW
REV
I DATE
I DESCRIPTION
DATE SIGNED: 12/22/2022
Loyal) A. Wb—., P.E.
Professional Engine: License: #C50547
Expiration Date: 06-30,2023
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
PHOTOSIMS
SHEET NUMBER
T-2
Community Development Department
Planning Division — Cupertino
CUPLFTINQ APPROVED
Ca e # DIR-2023-003
Application Number(s)
� E;n
Ap rovaI Body: Direc�o50SFb8Uff1?R L F S5
Apiproval Date 02/2-'EG ICALLE AVAN=AD4
Sig Ii ature Gian Paolo Martire
ICase Manager
SFSFOO1041A
TRANSMI SSI ON TOWER
1 0 1 1 0 CALIFORNIA OAK WAY C U P E R T I N O, CA 9 5 0 1 4
..
'sh
ar
.
wireless .
wireless-
5701 S SANTA FE DR
LITTLETON, CO 80120
C7.UlL
W/RLL L//
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
M SQUARK•J
WIRELESS
1307 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
DRAWN BY: EZG
CHECKED BY: MM
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S-JX COMMENT
C
06/29/2022
100%CD'S FOR REVIEW
B
02/09/2022
90%CD'S FOR REVIEW
A
01/14/2022
90%CD'S FOR REVIEW
REV
I DATE
I DESCRIPTION
DATE SIGNED: 12/22/2022
Loyal) A. Wb—., P.E.
Professional Engi — License: #C50547
Expiration Date: 06-30,2023
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
PHOTOSIMS
SHEET NUMBER
T-3
Community Development Department
Planning Division — Cupertino
CUPEFTINO APPROVED
Ca e# DIR-2023-003
Application Number(s)
Ap rovaI Body: DirX�30tYARErrcre'!
Apiprova I Date 0 vy I R r S 5
I _VI]O7CALLS AVANZADO
Sigi ature Gian Pac7�Nd4WATFeA 92673(949) 301 Aa24
ICase Manager
SFSF001041A
T R A N S M I S S I O N T O W E R
1 0 1 10 CALIFORNIA OAK WAY C U P E R T I N O, CA 9 5 0 1 4
f
■
Y
rr
d..sh
wireless..
VIEW 3 1 SECTOR 'GAMMA' 1 LOOKING NORTHEAST
wireless-
5701 S SANTA FE DR
LITTLETON, CO 80120
C7.U1.d*7M/7f-
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
M SQUARK•J
WIRELESS
1307 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
DRAWN BY: EZG
CHECKED BY: MM
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S-JX COMMENT
C
06/29/2022
100%CD'S FOR REVIEW
B
02/09/2022
90%CD'S FOR REVIEW
A
01/14/2022
90%CD'S FOR REVIEW
REV
I DATE
I DESCRIPTION
DATE SIGNED: 12/22/2022
Loyal) A. Wb—., P.E.
Professional Engi — License: #C50547
Expiration Date: 06-30-2023
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
PHOTOSIMS
SHEET NUMBER
T-4
C'
ISSUE STATUS
/ REV. DATE DESCRIPTION BY
Community Development Department / 0 11/19/21 PRELIMINARY SURVEY AB
\s
Planning Division — Cupertino
�ERTINO APPROVED / \�
se # DIR-2023-003 /
Application Numb YS / Ns2s �5e tiood \
/ ,S?6S o h, wr
proval Body: Directo fF -: / \
prova I Date 02/23/23
nature Gian Paolo Martire ' ' \ \ 23072 LAKE CENTER DR., SUITE 211
LAKE FOREST, 92630
Case Manager - / f ]14.624.90202]
PROPRIETARY INFORMATION
/ \ \ 699\ THE INFORMATION CONTAINED IN THIS SET OF
DRAWINGS IS PRDISH WIARLE CONFIDENTIAL TO
DISH WIRELESS
ANY USE OR DISCLOSURE OTHER THAN AS IT
\ RELATES TO DISH WIRELESS IS
\ STRICTLY PROHIBITED
VICINITY MAP
BASIS OF ELEVATIONS: (NAND 1988)
SITE ELEVATIONS ARE ESTABLISHED FROM THE GPS DERIVED ORTHOMETRIC HEIGHTS \ MONTA VISTA SUBSTATION
BY APPLICATION OF NGS "GEOID 12A" MODELED SEPARATIONS TO ELLIPSOID HEIGHTS 3139 O.R. 217 /
DETERMINED BY OBSERVATIONS OF THE "LEICA SMARTNET" REAL TIME NETWORK. ALL /
ELEVATIONS SHOWN HEREON ARE REFERENCED TO NAVD88. CALIFORNIA ZONE 3. \
FLOOD ZONE I \ /
SITE IS LOCATED IN FLOOD ZONE "D" AS PER F.I.R.M. MAP NO. 06085CO204H
EFFECTIVE DATE 05/18/2009
EASEMENT NOTE I \ / �� / •
ALL EASEMENTS SHOWN ON THE SURVEY WERE COMPILED FROM RECORD \
INFORMATION AS PER THE REFERENCE RECORD MAPS LISTED ON THE SURVEY.
REFERENCE MAP
1. RECORD OF SURVEY \ �
BOOK 376 PAGE 47
REC. DATE: AUG. 18, 1976 I
SEE SHEET LS-2
COORDINATES
LATITUDE: 37'19'30.51" N (37.325142')
LONGITUDE: 122'04'36.33" W (-122.076758')
o: �/ eROFESS/ON
O/ �40 EW J
No. 26571 rA m
Qe
Exp. 03/31 /22
\ 0�
ACCESS Q
/ C
342-63-001 �/ T— a
U
P.G.&E. �; o� </
O o
RECORD OF SURVEY
BOOK 376 PAGE 47 '�`6 A,
REC. DATE: AUG. 18, 1976 I„L ELLJ
lf
O LL
/ U
0 o!^o/� / V )
/ t SHEET TITLE:
100' so' o' 100' 200' BOUNDARY
DETAILS
,74 GRAPHIC SCALE: 1"=100'
N
W ~ 553
_ N 6230 LS-1
_%-
NOTES:
1. THIS IS NOT A BOUNDARY SURVEY. THIS IS A SPECIALIZED TOPOGRAPHIC MAP.
THE PROPERTY LINES AND EASEMENTS SHOWN HEREON ARE FROM RECORD
INFORMATION AS NOTED HEREON. AJK ENGINEERING AND SURVEY TRANSLATED
nt
TS NTSISHOWNNHEf�H LO E I�P ROXNI Eno
LY FOR THE DATE OF THIS SURVEY. THEY ARE PROVIDED AS A GENERAL
RT WfUENCE AND SHOULD NOT BE usAPP[�y1MFE)ES.
3. FIELD SURVEY COMPLETED ON �p�(E �-EaR�bt ,n-003
se # UI
COORDINATES Application Number(s)
LATIITTUDEpp ,,..�, 37'19'30.51" N (337..325142�/)7 j[
tune �.,. Gian Paolo Mart;,
Case Manager
ELEVATION
ELEVATION
592.50 A.M.S.L 137 -9 A.G.L
TMNSMISISON LINE
584.65 A.M.SL 129 -10 A.G.L
ELEVATION
577.45 A.M.SL 122 -8 A.G.L
TRANS3 A.M.SMIWISI .L LINE
569.7114 -I I A.G.L
ELEVATION
562.53 A.M.S.L 107 -9 A.G.L
TOWER HIP
558.62 A.M.S.L 103-10 A.G.L
TRANSMISISON LINE
554.79 A.M.SL 100 -0 A.G.L
y
f
TOP OF ANTENNAS
501.98 A.M.SL 47 -2 A.G.L f
ELEVATION \
501.29 A.M.S.L 46 -6 A.G.L
TOP OF ANTENNAS f
495.34 A.M.S.L 40 -7 A.G.L \
BOTT OF ANTENNAS f
487.45 A.M.S.L 32 -8 A.G.L
TOP OF CONC. BASE III
458.56 A.M.SL 3 -9 A.GL
10' 5' 0' 10' 20'
GRAPHIC SCALE: 1"=10'
GATE
f
f
4
4
t\
f\
f\
� STEEL LATTICE TOWER, P.I.Q.
/ (SEE PROFILE)
CONCRETE BASE
LEGEND
CENTER LINE
PROPERTY LINE
XX
CHAIN -LINK FENCE
WOOD FENCE
b--��
WROUGHT IRON FENCE
EASEMENT LINE
®
CMU WALL
TW
TOP OF WALL
TO
TOP OF CURB
BW
BACK -OF -WALK
FS
FINISHED SURFACE
a
EG
EXISTING GRADE
a
JB
JUNCTION BOX
4
VLT
VAULT
CAB
CABINET
WV
WATER VALVE
WM
WATER METER
-
SSMH
SANITARY SEWER MANHOLE
SDMH
STORM DRAIN MANHOLE
CZD--
EXISTING STREET LIGHT
�-
EXISTING SIGN
4
a
F-
GUY WIRE
®
CATCH BASIN
E
POWER POLE
'Cr
FIRE HYDRANT
TREE
MONUMENTS
Q
MONUMENT FD.
n\
(AS NOTED)
mP\
Q
\ Y
�e
UNDERGROUNI
WOODEN ENCLOSURE " AT FIBER
FIBER
i
Q
iWALE
4
tit
ISSUE STATUS
REV. DATE DESCRIPTION BY
0 11/19/21 PRELIMINARY SURVEY AS
t
23072 LAKE CENTER DR., SUITE 211
LAKE FOREST, CA 92630
714.624.9027
PROPRIETARY INFORMATION
THE INFORMATION CONTAINED IN THIS SET OF
DRAWINGS IS PROPRIETARY & CONFIDENTIAL TO
DISH WIRELESS
ANY USE OR DISCLOSURE OTHER THAN AS IT
RELATES TO DISH WIRELESS IS
STRICTLY PROHIBITED
H
eROFESS/ON
CFO Ew J KO/Tq��
TA z Q No. 26571
Exp. 03/31/22
`ST CIV\� Q
gr,,OF CA\-\F
O
C) Ln
r Q
O
O
Z
H
r L �
v )
U
rLL
v )
SHEET TITLE:
TOPOGRAPHIC
SURVEY
-2LJ
c
Community Developme , �epartme
Planning Division — Cup 0,�'
JPE IN0 (E) RESIDEN APTTYP. VED S; /
�a e # DIR-202 -00 oP�
ORMER;
Application Nu er( �� * (N) POWER P.O.C.
4p rov od ctor / to (N)PG&E PULLBOX
�p royal t
-3igi at re Gia aolo Martire
as Manager /
0
y
(E) CHAIN LINK FENCE; TYP.
(E) TRANSMISSION APN: 342-63-001
TOWER; TYP.
(E) PG&E POWER
FACILITY
Z + 3
m (E)
+\ COMPOUND +\
BY OTH(E) EQUIPMENT AREA
ERS
BY OTHERS; TYP.
SITE PLAN
(E)SHELTER
■ ■
i� FOR ENLARGED SITE PLAN ��
REFER TO: \
INN />
(E) ACCESS ROAD —
(E) TREE; TYP.
ft�
01`1' \ SSS
2
Q (E) TRAIN TRACKS
N
GtV i E ?�
Drv�"4
5
24"x36" SCALE: 1" = 80'-0" 0" 40' 80, 160'
11"x17' SCALE: 1" = 160'-0"
+\
(E) CHAIN LINK FENCE; TYP. g'
i�l r '0
Cy
W
o
(E) OVERHEAD POWER LINE; TYP.
(N) EQUIPMENT AREA & �
ANTENNA AREA, REFER TO:
1 1
♦
A-2 A-3
(E) PG&E FIBER OPTIC CABLE
(E) EQUIPMENT AREA BY OTHERS
(N) 6" UNDERGROUND CONDUITS;
(2) TOTAL W/ (N)±120' HYBRID TRUNK; (1) TOTAL
TO FOLLOW (N) CABLE ROUTE FROM (IN NET
IN (N) UNDERGROUND CONDUIT TO (E) TOWER
CLIMB LEG IN (N) 6" SPLIT DUCT RISER UP TO 10'
\
A-6 A$
♦
(N) 400A,120/240V, 1PHASE, 3WIRE WP DUAL METER
PEDESTAL WITH (2) METER SOCKETS COMPLETE WITH
TEST BYPASS FACILITIES AND 200A'T' FUSE PULLOUTS
MOUNTED TO (N) 4" CONCRETE HOUSEKEEPING PAD
CONCRETE FILLED BOLLARDS
(AS NEEDED)
(N) UTILITY PRECAST CONCRETE —
UNDERGROUND I2KVVAULT (TO
MEET UTILITY REQUIREMENTS)
ENLARGED SITE PLAN
NOTES:
1. THE WIRELESS COMMUNICATION FACILITY COMPLIES WITH FEDERAL STANDARDS FOR RADIO
FREQUENCY IN ACCORDANCE WITH THE TELECOMMUNICATION ACT OF 1996 AND SUBSEQUENT
AMENDMENTS AND ANY OTHER REQUIREMENTS IMPOSED BY STATE OR FEDERAL REGULATORY
AGENCIES.
2. NO EXISTING PARKING STALLS ARE BEING ADDED OR REMOVED AS PART OF THE NEW INSTALLATION.
3. THESE DRAWINGS WERE PRODUCED WITHOUT THE BENEFIT OF A CURRENT LAND SURVEY. ALL
PROPERTY LINES, EASEMENTS, SETBACKS, AND EXISTING CONDITIONS ARE APPROXIMATE AND
SHALL BE VERIFIED PRIOR TO START OF CONSTRUCTION.
4. NO GRADING WORK IS INCLUDED IN THIS SCOPE OF WORK ON THIS PAGE.
5. PROPOSED WORK IS COMPLIANT WITH 6409(A) ELIGIBILITY FACILITIES REQUEST CRITERIA
(E) TREE; TYP.'
APN: 342-63-001
(E) CONDUCTOR; TYP.
♦ A-4
♦
♦ BETA SECTOR
♦ ; AZIMUTH=90°
♦ Z
♦ O
♦ y0
♦ m
(E) CLIMBING LEG
(N) ±25' UNDERGROUND CONDUIT
♦ W/ POWER TRUNK FROM (E) POC
(FIELD VERIFY)
(N)±10' UNDERGROUND CONDUIT
..�10•• POCI(FIELD VERIFY)OM (E)7ELC0
��� • (E) FIBER HANDHOLE; FIBER P.O.C.
(N) UTILITY PAD MOUNTED TRANSFORMER, EC
TO PROVIDE (N) CONCRETE PRECAST PAD AND
GROUNDING GRID PER UTILITY REQUIREMENTS.
(E) T-MOBILE UNDERGROUND CONCRETE
PULLBOX TO BE ABANDONED ONCE (N)
SERVICE IS CUTOVER TO (N) SWITCHBOARD
N
\-QW
D �.A
s
24"x36" SCALE: 1/8" V-0" 0" 4' 8' 16'
11"x17" SCALE: 1/16"= V-0" 2
d .*sl
wireless-
5701 S SANTA FIE DR
LITTLETON, CO 80120 ,
li"'E/Ar
W/RLL L//
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
WIRELESS
1387 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
DRAWN BY: EZG
CHECKED BY: MM
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
1 07/22/2022
100%CD'S -JX COMMENT
C
06/29/2022
100% CD'S FOR REVIEW
B
02/09/2022
90% CD'S FOR REVIEW
A
01/14/2022
90% CD'S FOR REVIEW
REV
DATE
I DESCRIPTION
DATE SIGNED: 12/22/2022
LoyaO A. W6azron, P.E.
Professional Engine: License: #C50547
Expiration Date: 06-30,2023
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
SITE PLAN AND ENLARGED
SITE PLAN
SHEET NUMBER
A-1
ANTENNA
SECTOR POSITION EXISTING OR I MANUFACTURER — MODEL
PROPOSED NUMBER ., TECHNOLOGY
/CPO mum twDeve OtJPTI ent (Drt entG
BETA
GAMMA Cl
06'M n n I
5G
CX12044x I 5G
SIZE (HxW) AZIMUTH
72.4" x 26.7" 350'
72.4" x 26.7" 90'
72.4" x 26.7" 210'
TRANSMISSION CABLE
RAD FEED LINE TYPE
E-0"(1) HIGH —CAPACITY
—0" HYBRID CABLE
(t120' LONG)
84'—O"
CUPLF
TINQ
Ca
Apr
Ap[r
SIg
e
I
a
SECTOR
POSITION
RH
NOTES
1. CONTRACTOR TO REFER TO
FINAL CONSTRUCTION RFDS
FOR ALL RF DETAILS.
2. ANTENNA AND RRH
MODELS MAY CHANGE
DUE TO EQUIPMENT
EQUIPMENT CHANGES MUST
BE APPROVED AND REMAIN
IN COMPLIANCE WITH THE
PROPOSED DESIGN AND
STRUCTURAL ANALYSES.
_
(HxW)
ALPHA
val Body:
Al
jJ:l
FUJITSU TA08025—B605
N71
14.96" x 15.75"
�(,,
irL5IetbrTybt ffl04
N70/N66
14.96" x 15.75"
vaj D
1
021231213,s025—B605
N71
14.96" x 15.75"
B1
FUJITSU TA08025—B604
N70/N66
14.96" x 15.75"
GAMMA
x 15.75"
—
Cl
=UJITSU TAO8025-8604
N70/N66
14.96" x 15.75"
ANTENNA & EQUIPMENT SCHEDULE
(N) 6" UNDERGROUND CONDUITS;
(2) TOTAL W/ (N) ±120' HYBRID TRUNK;
5 3 (1) TOTAL TO FOLLOW (N) CABLE
A 6 A 8 ROUTE FROM (N) CABINET IN (N)
UNDERGROUND CONDUIT TO (E)
q TOWER CLIMB LEG IN (N) 6" SPLIT
DUCT RISER UP TO 10'
(E) TRANSMISSION TOWER
(E) PG&E FIBER OPTIC CABLE
1 q 5 (N) RRH'S MOUNTED TO (N) H-FRAME;
A-6 A-8 (2) PER SECTOR, (6) TOTAL
NOTES TO CONTRACTOR:
1. CONTRACTOR IS TO REFER TO DISH WIRELESS'S MOST CURRENT
RADIO FREQUENCY DATA SHEET (RFDS) PRIOR TO CONSTRUCTION.
2. CABLE LENGTHS WERE DETERMINED BASED ON VISUAL INSPECTION
DURING SITE -WALK. CONTRACTOR TO VERIFY ACTUAL LENGTH
DURING PRE -CONSTRUCTION WALK.
NOTES:
1. ANTENNA AZIMUTHS ARE ESTIMATED AND ARE TO BE VERIFIED BY RF.
2. ANTENNA BY OTHERS NOT SHOWN FOR CLARITY.
3. PRIOR TO ORDERING ANTENNAS VERIFY CORRECT MODEL NUMBER
WITH LATEST RFDS AND NOTIFY ENGINEER OF RECORD IMMEDIATELY
IF DISCREPANCY IS FOUND.
1. M SQUARED WIRELESS ACCEPTS NO LIABILITY FOR THE STRUCTURAL CAPACITY OF
THE STRUCTURE, MOUNTS, ANTENNAS, CABLES OR ANY OTHER APPURTENANCE ON
THE TOWER. THE CONTRACTOR AND SUBCONTRACTOR SHALL COORDINATE WITH
AND COMPLY WITH THE PROVISIONS OF THE STRUCTURAL ANALYSIS PREPARED FOR
THIS SITE AND PROJECT PRIOR TO THE INSTALLATION OF ANTENNAS AND CABLE ON
THE TSTRUCTURE. IMMEDIATELY REPORT ANY DISCREPANCIES BETWEEN THE
CONSTRUCTION DRAWINGS AND THE STRUCTURAL ANALYSIS TO DISH WIRELESS.
2. REFER TO THE STRUCTURAL ANALYSIS AND/OR STRUCTURAL LETTER FOR THE
APPROVAL OF ALL MODIFICATIONS TO AND ADDING EQUIPMENT OF NEW TOWER
APPURTENANCES.
3. REFER TO ADDITIONAL DRAWINGS SPECIFIC TO STRUCTURE REINFORCEMENT FOR
THIS SITE SHOULD THERE BE A REQUIREMENT FOR ANY STRUCTURE
REINFORCEMENT.
4. REFER TO STRUCTURAL ANALYSIS FOR COAXIAL AND OTHER CABLE SUPPORT AND
CONFIGURATION DETAIL.
5. REFER TO STRUCTURAL ANALYSIS FOR ALL CARRIERS APPURTENANCES AS THEY
MAY NOT BE SHOWN IN ELEVATION DETAIL.
6. PRIOR TO ORDERING ANTENNAS VERIFY CORRECT MODEL NUMBER WITH LATEST
RFDS AND NOTIFY ENGINEER OF RECORD IMMEDIATELY IF DISCREPANCY IS FOUND.
v
3x
y
4 d1
Ix
w
� Q (N) FIBER SPOOL CAN
o �J
�.� (E) OVERHEAD POWER LINE; TYP.
\ F (E) CONDUCTOR; TYP.
CLIMBING LADDER
0
sq BETA SECTOR
\ AZIMUTH=90°
Z"
(E) CLIMBING LEG
O O \ (N) OVP MOUNTED ON (N)141416 MOUNT; (1) TOTAL A 6
Q (N) PANEL ANTENNA MOUNTED TO (N) H-FRAME 13
Q� \ MOUNT; (1) PER SECTOR, (3) TOTAL A-6 \
PROPOSED ANTENNA LAYOUT
N
GW t'E®
D �4
S
24"x36" SCALE: 1/4" = T-0" 0' 2' 4' 8' 1
11"x17" SCALE: 1/8" =1.-0"
dl%W 4%0
wireless-
5701 S SANTA FE DR
LITTLETON, CO 80120
W/RLL L//
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
M SQIUAR•
WIRELESS
1367 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
DRAWN BY: EZG
CHECKED BY: MM
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S-JX COMMENT
C
06/29/2022
100%CD'S FOR REVIEW
B
02/09/2022
90%CD'S FOR REVIEW
A
01/14/2022
90%CD'S FOR REVIEW
REV
I DATE
DESCRIPTION
DATE SIGNED: 12/22/2022
Loyal) A. Wb—., P.E.
Professional Engine: License: #CS0547
Expiration Date: 06-30,2023
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEV
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
ANTENNA LAYOUT
SHEET NUMBER
A-2
1. TRANSMISSION TOWER NOT SHOWN FOR CLARITY.
Community Development Department
Planning Division — Cupertino
CUPS )No APPROVED
Ca e # DIR-2023-003
Application Number(s)
Api$rovaI Body: Director / Staff
Ap[ rova I Date 02/23/23
Sig li ature Gian Paolo Martire
ICase Manager
3-5 (N) NON-CONDUCTIVE COMPOSITE FENCE
A43 ENCLOSURE TO BE INSTALLED PER
MANUFACTURER'S RECOMMENDATIONS
A-9g (N) CONCRETE PAD
(N) PG&E EMERGENCY
SHUTDOWN SWITCH; (1) TOTAL
(N) PG&E METER; (1) TOTAL
(N) H-FRAME; (1) TOTAL W/
(N) PPC; (1) TOTAL
(N) CIENA BOX; (1) TOTAL
A-7 A-8 (N) DISCONNECT SWITCH; (1) TOTAL
(N) METER; (1) TOTAL
(N) GPS ANTENNA; (1) TOTAL
PROPOSED EQUIPMENT LAYOUT
A-9(N) MAW STOOP
(N) CABINET MOUNTED TO JJ6,7
(N) CONCRETE PAD; (1) TOTAL KtV
(N) 6" UNDERGROUND CONDUITS;
(2) TOTAL W/ (N) ±120' HYBRID TRUNK;
(1) TOTAL TO FOLLOW (N) CABLE 5 3
ROUTE FROM (N) CABINET IN (N) A 6 A$
UNDERGROUND CONDUIT TO (E)
TOWER CLIMB LEG IN (N) 6" SPLIT
DUCT RISER UP TO 10'
(N) 3' ACCESS GATE
N
S
24"z36" SCALE: 3/4" = V-0" 0" 6" 1' 2'
11 "z17" SCALE: 3/8" = V-0"
d .*sh
r
wireless
5701 S SANTA FE DR
LITTLETON, CO 80120
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
M SQUAR(•j
WIRELESS
1387 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
DRAWN BY: EZG
CHECKED BY: MM
3
12/27J2022
100% CD'S FOR SUBMITTAL
2
10/2W2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/27J2022
100%CD'S -JX COMMENT
C
06/29/2022
100% CD'S FOR REVIEW
B
02/09/2022
90% CD'S FOR REVIEW
A
01/14/2022
90% CD'S FOR REVIEW
REV
I DATE
I DESCRIPTION
DATE SIGNED: 12/22/2022
Loy.H A. Wbaz ., P.E.
Professions) Engineer License: #C50547
Exp-w. Date: 06-30-2023
R IS A VIDLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
EQUIPMENT LAYOUT
SHEET NUMBER
A-3
c
}� TOP OF EXISTING TRANSMISSION TOWER
12 Communi5y40evelopment Depa
Planning Division — Cupertir
JPE INo APPROVED
-a e # DIR-2023-003
Application Number(s)
gyp[ rova I Bo�y> ,QrWL;r / Staff
%p[Ipl rova I DateLEV,tIt-2?2�/23
3Ig Ii ature Gian Paolo Martire
ICase Manager
}� EXISTING POWER LINE
ELEV.:112'-3" A.G.L.
}� EXISTING POWER LINE
ELEV. 3100'-0"A.G.L.
(E)PANELANTENNAS
BY OTHERS; TYP
I D CENTER OF EXISTING PANEL ANTENNAS BY OTHERS
ELEV. t42'-2"A.G.L. -----
RAD CENTER_OF EXISTING PANEL ANTENNAS BY OTHERS
ELEV.t33'-10' A.G.L.
(E) TRANSMISSION TO
(E) EQUIPMENT AREA
BY OTHERS
}GROUND LEVEL
ELEV. 0'-0" A.G.L.
EXISTING NORTHEAST ELEVATION
NOTE:
1. PROPOSED EQUIPMENT TO BE PAINTED
— ft-- EVICTING STRUCTURE.
}� TOP OF EXISTING TRANSMISSION TOWER
ELEV. t150'3" A.G.L.
EXISTING POWER LINE
ELEV. x127'-2" A.G.L.
EXISTING POWER LINE
ELEV. t112'-3" A.G.L.
EXISTING POWER LINE
ELEV. 3100'-0" A.G.L.
RAD CENTER_OF NEW_PAN EL A_NTENNA_5
84
_
ELEV.'-0" A.G.L.
5 3
A-6 A-8
RAD CENTER OF EXISTING PANEL ANTENNAS BY OTI
ELEV.t42'-2" A.G.L.
RAD CENTER OF EXISTING PANEL ANTENNAS BY_ OTI
ELEV.333'-10" A.G.L.
}� GROUND LEVEL
ELEV. 0'-0" A.G.L.
(E) TRANSMISSION TOWER
(E) EQUIPMENT AREA BY Ol
3-5 (N) NON-CONDUCTIVE COM
ENCLOSURE TO BE INSTAL
A-9 MANUFACTURER'S RECOM
(N) UTILITY PAD MOUNTED
EC TO PROVIDE (N) CONCR
PAD AND GROUNDING GRIL
REQUIREMENTS.
(N) UTILITY PRECAST CONC
UNDERGROUND12KVVAUL
MEET UTILITY REQUIREMEP
24"x36"SCALE: 1/8-1'-0" 0" 4�8' I 1 1 PROPOSED NORTHEAST ELEVATION
11"x17" SCALE: 1/16"= 1'-0"
NOTE:
1. PROPOSED EQUIPMENT TO BE PAINTED
— KA—W —1—ING STRUCTURE.
d .*s'
wireless..
5701 S SANTA FE DR
LITTLETON, CO 80120
�4—EA---
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
M SQ,UAR
WIRELESS
1387 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
,UNTED TO (N) H-FRAME DRAWN BY: EZG
(3) TOTAL 1 3
A-6 CHECKED BY: MM
IN) H-FRAME;
AL
1 4,5,8
A-6 A-8
24"x36" SCALE: 1/8" V-0" 0" 4' 8' 16' I 2f�
11"x17" SCALE: 1/16"= V-0"
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S -JX COMMENT
C
06/29/2022
100% COS FOR REVIEW
B
02/09/2022
90%COS FOR REVIEW
A
01/14/2022
90%COS FOR REVIEW
REV
DATE
DESCRIPTION
DATE SIGNED: 12/22/2022
LoyO A. Wb—., P.E.
Professional Engine: License: #C50547
Expiration Date: 06-30-2023
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
ELEVATIONS
SHEET NUMBER
A-4
c
}� TOP OF EXISTING TRANSMISSION TOWER
12 Communi5y40evelopment Depa
Planning Division — Cuperti
JPE INo APPROVED
-a e # DIR-2023-003
Application Number(s)
gyp[ rova I Bo�y> , rWL;r / Staff
%p[Ipl rova I DateLEV,tIt-2?2�/23
3Ig Ii ature Gian Paolo Martire
ICase Manager
}� EXISTING POWER LINE
ELEV.:112'-3" A.G.L.
}� EXISTING POWER LINE
ELEV. 3100'-0"A.G.L.
(E) PANEL ANTEI
BY OTHERS; TYF
RAD CENTER OF EXISTING PANEL ANTENNAS BY OTHERS
ELEV. t42'-2" A.G.L.
AD CENTEROF EXISTING PANEL ANTENNAS BY OTHERS
E!LEV.t33'-10' A.G.L.
(E) TRANSMISSI(
(E) EQUIPMENT
AREA BY OTHEF
}GROUND LEVEL
ELEV. 0'-0" A.G.L.
EXISTING SOUTHEAST ELEVATION
NOTE:
1. PROPOSED EQUIPMENT TO BE PAINTED
— ft—W P—TING STRUCTURE.
INDUCTOR; TYP.
}� TOP OF EXISTING TRANSMISSION TOWER
ELEV. t150'-4" A.G.L.
EXISTING POWER LINE
4 ELEV. t 27'-2" A.G.L.
}� EXISTING POWER LINE
ELEV. t112'-3" A.G.L.
}� EXISTING POWER LINE
ELEV. i:100'-0" A.G.L.
RADCENTER_OF NEW PANEL ANTENNAS
ELEV.84'-0" A.G.L.
1,4 1 (N) OVP MO
A-6 A-9 B141415 MC
(E)PANEL ANTE
BY OTHERS; TYF
RAD CENTER OF EXISTING PANEL ANTENNAS BY OTHERS
ELEV.t42'-2" A.G.L.
RAD CENTER_OF EXISTING PANEL ANTENNAS BY OTHERS
ELEV.t33'-10' A.G.L.
}� GROUND LEVEL
ELEV. 0'-0" A.G.L.
(E)TRANSMISSII
(N) UTILITY PREi
UNDERGROUND
MEET UTILITY R
(E) EQUIPMENT
AREA BY OTHEF
24"x36"SCALE: 1/8"=1'-0" 0" 4-8' "I 1 1 PROPOSED SOUTHEAST ELEVATION
11"x17" SCALE: 1/16"= 1'-0" �
NOTE:
1. PROPOSED EQUIPMENT TO BE PAINTED
— KA—W PYInTING STRUCTURE.
1CTOR; TYP.
OUNTED
T; 3 8
,TAL A-6 A-8
1(N)
OR,
CONDUITS;
IYBRID TRUNK;
(N) CABLE
NET IN (N) 5 3
UIT TO (E) AE A-8
N) 6" SPLIT
TY PAD MOUNTED
ORMER, EC TO PROVIDE
-RETE PRECAST PAD
OUNDING GRID PER
REQUIREMENTS.
CONDUCTIVE COMPOSITE
:NCLOSURE TO BE
.ED PER MANUFACTURER'S
AENDATIONS
24"x36" SCALE: 1/8" = V-0" 0" 4' 8' f�
11"x17" SCALE: 1/16"= V-0" 2
d .*s'
wireless..
5701 S SANTA FE DR
LITTLETON, CO 80120
�4_EA_-_
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
M SQ,UAR
WIRELESS
1387 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
DRAWN BY: EZG
CHECKED BY: MM
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S -JX COMMENT
C
06/29/2022
100% COS FOR REVIEW
B
02/09/2022
90%COS FOR REVIEW
A
01/14/2022
90%COS FOR REVIEW
REV
DATE
DESCRIPTION
DATE SIGNED: 12/22/2022
LoyO A. Wb—., P.E.
Professional Engine: License: #C50547
Expiration Date: 06-30-2023
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
ELEVATIONS
SHEET NUMBER
A-5
I CHARLES 6" PLINTH FOR
PM639 5N4 SERIES
pa_
MATERIAL _ STEEL
' rtl
TOTAL W G S D 71
ISO VIEW
ment
o
C1 o
CELLMAX
CX12044X
I vv
s h
�wrirolo��
DIMENSIONS (HxWxD)(mm/in)
1840x680x196/
72.4"x26.7"x7.7"
TOTAL WEIGHT (kg/lb)
48Kg/1051b
RF CONNECTOR INTERFACE
4.3-10 FEMALE
vr�
111vv Arr mum CU
'
"-
NEW EQUIPMENT
Ca
444/,,
e {+fIT INSTALLATION: D I R-2023-003
CABINET
5701SSANTA RE DR
LITTLETON, CO 80120
CUBE
2. FOLLOW THE THIP HAT S
WITH THE CUBE FOR PREPARING THE CONCRETE PAD.
3/4" CHAMFER
A
p
Ap�rQ�S��
SIg
3. PLACE THE GASKET ON THE CONCRETE PAD. PLACE THE
G MOUNTING HOLES
rc�r AL€iN�/�
4 THE PI�Iy `� PAD USING FOUR
S�PLIEDy RR�RESISTANT. 1 /2"-1.3 HEX
HEAD BOLTS WITH ANCHORS. SEE THE INSTRUCTIONS THAT
F� �q p ,I ,IAA ,,F
aPi[OTH THWE TIPRAr f�NTN SWhFI,r�„ BAP,"
THE MOUNTING HOLES ONCTtFQ K4I�a ALIGNED WITH THE
HOLES ON TOP OF THE PLINTH.
6. SECURE THE CUBE TO THE PLINTH USING HARDWARE
°0o
9 0
KIT
SLOPE
WEED BARRIER Z
WEED BARRIER
oa
#4 @ 12" O.C. E.W.
4"COMPACTED
o 0 0 0 0 0 0 o
o0 00 00 00
BOTTOM
wiwsc sii
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
THAT SHIPS WITH THE PLINTH.
GASKET
INCLUDED
(80-005300—A,
W/ CUBE)
B" (2)#4 BASE COURSE
M SQUARI ED
WIRELESSJLE AIVA—A—
FRONT
SIDE
N36" SCALE: SITS 14:x36
6" CABINET PLINTH 11"x17"SCALE: NTS
9
SCALE: NITS
EQUIPMENT ANCHORAGE 21 17"SCALE: NTS
6
24'x36" SCALE: SITS
CELLMAX CX12044X 11"x17"SCALE: NTS
3
B2211 (ANDREW'S BANJO CLUSTER) HOISTING GRIPS
BJ09 (VALMONT BANJO BOX): FOR INNER DUCT
MANUFACTURER: CUI
MODEL No.12PAIR HYBRID ASSEMBLY 8AWG
XXX
CELLMAX ANTENNA BRACKET
�•
o®�'e MOUNTING
A
SAN CLEMENTE CA 92673 (949)391-6824
ANTENNAS
12044x / 12045x
BRACKET PART #
CA325482 CA325484
/
DRAWN BY: EZG
36" 72"
TILT BRACKET WEIGHT
6.61 Ibs
CHECKED BY: MM
11 I'l— �\� — 32" — — — _ g®— - UKA(:KLI I
211"
INSTALLATION TORQUE:
ANTENNA
CABLE GLAND
7/16": 34 ET—LBS
W/ LOCKS
PLAN ISO
MOUNTING
TOP
END
BOTTOM
END
BRACKET
CABLE, 24F, SM, 9
10 1/4"
PAIR CONDUCTOR
WIRES,BLACK
9/1 6"
HEAT SHRINK,
2 3/4'
UNSHRUNK
HEAT SHRINK,
NON -ADHESIVE
7/16"4 GALV.
THREADED ROD
s
O O ® ®
SUBUNIT, BLACK,
(NP)
®®
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S -JX COMMENT
C
06/29/2022
100% CD'S FOR REVIEW
B
02/09/2022
90% CD'S FOR REVIEW
A
01/14/2022
90%CD'S FOR REVIEW
REV
DATE
DESCRIPTION
BOTH ENDS ® MOUNTING
®�" PIPE
SIDE FRONT 9 (, U), 18XCOPPER CONDUCTOR, SAW., ®®" OFESS/O
01
PAIRS 1 BLACK1 BLUE), BOTH ENDS V
5/16" 3/4" DIA. THRU
TYP. 9 PLACES TYP. 9 PLACES
BANJOS 24"x36"SCALE: NTS"x17"SCALE: IN NTS 5 ANTENNA MOUNTING DETAIL 24"x36"SCALE: NTS 505
11"x17" SCALE: SITS 8 HYBRID TRUNK (01 TO 120') 11"x17" SCALE: NTS 2
RFRTIC)N R S'x. —A
EQUIPMENT CABINET
CHARLES CUBE PM639155N4
RAYCAP RDIDC-9181 —PF-48
SURGE PROTECTION DEVICE
DIMENSIONS (HxWxD) 16.58" x 14.58" x 8.46"
WEIGHT 21.85 LBS
PLAN
--
B ELEVATION
A
4-4
B L2X2X1/4" X T-6"
LONG TYP.
:�
FCA
DATE SIGNED: 12/22/2022
Loyall A. Wb—., P.E.
Professional Engineez Licence:#C50547
Expuzrion Dare: 06-30.2023
IT IS VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
ENCLOSURE DIM (HxWxD)
74.1 "x32.0"x32.0"
TOTAL WEIGHT W/ NO BATTERIES
559.14 LBS
TOTAL WEIGHT W/ 4 BATTERIES
1067.14 LBS
0
I I
I I
1/2"0 U-BOLT, TYP.
cl
SFSF001041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
PIPE 2 STD (2-3/8" OD) —
LENGTH VARIES
SHEET TITLE
DETAILS
A
SECTION A
P �-1I FRONT
1.5L'•
1.s"
SHEET NUMBER
SIDE BACK FRONT24"x36"
A-"
SCALE: SITS
EQUIPMENT CABINET 11"x17"SCALE: NTS 7
SURGE PROTECTION DEVICE 24"x36" SCALE: NITS 11"xl7"SCALE: NTS 4
B144796 H-FRAME
DETAIL 24"x36"SCALE: NTS
1"x17" SCALE: NTS 1
Vh
7'-0"
LEASE AREA
„ 2'-0" 1'-2" 2'-91,
•
1-0"
Community Development Department j
Planning Divisio,n,a�Ed0upertino
APPROVED CPS UNIT
PROPOSED FLOODLIGHT
o WITH TIMER
wireless -
JPLFTINQ
Ca
PROPOSED H-FRAME
e # DIR-202FJ-IFIJ'JSHDT OFF
PROPOSED °
EQUIPMENT CABINET a
O ETAL
LITTLETON, CO 011 0
Application Num POWER
PROTEC I E CABINET
AET
p
royal Bod ,}aTrTr _I
y' Director / S40PDSED
w
a
PROPOSED 200AMP
METER
Ap f[�yrova
Slg
EQUIPMENT PLATFORM
I Date 02/23/23
I REQUIRED BY LOCAL UTILITY COMPANY
ature Gian Paolo Mal�yc�aSEL�aoc^""� ""EZE� SOC ET
Case Man 2r
PROPOSED CIENA BOX. SPACED
RESERVED IF REQUIRED
o
-
'�
-
a
I
w
EMERGENCYSHUTOFF
Oo
o d PROPOSED o PROPOSED H-FRAME
POWER
i.1 PROTECTIVERD,
_ CABINET
o
W/RLL L//
1200 DEL PASO ,C 95843
SACRAMENTO, CA 95843
`
PROPOSED TELCO FIBER ENCLOSURE
PROPOSED
SAFETY SWITCH.
o
INSTALL IF
-I REQUIRED BY
LOCAL UTILITY
COMPANY
S UAR E;
�WIRELESSJ
PLATFORM EQUIPMENT PLAN
24"x36"SCALE:NIS
11'x17' SCALE: NTS
4
MANUFACTURER:
EATON
MODEL NO.:
U224MTB
MAIN DISCONNECT:
(1) 200A 2P CB
AIC RATING:
10K
AMPACITY:
200 (MAX)
VOLTAGE:
120/240
SERVICE TYPE:
10 3W
NUMBER OF JAWS:
4
HUB PROV.:
AW
PHASE CONDUCTOR LINE:
6 AWG - 250 KCMIL
PHASE CONDUCTOR LOAD:
MAIN CIRCUIT BREAKER
NEUTRAL CONDUCTOR:
6AWG-250 KCMIL
HEIGHT (H):
30"
WIDTH (W):
22"
DEPTH (D):
6"
W
R\—
O
RAYCAP RDIAC-6152—P-240—MTS
AC POWER PROTECTION CABINET
TOTAL WEIGHT77 124 LBS
DIMENSIONS 40" X 20" X 10"
PVC CONDUIT (TYR)
1387 CALLE AVANZADO
SAN CLEMENTE CA 92673(949) 391-6824
��
FINISHED GRADE "=
DRAWN BY: EZG
CONCRETE PAD
CHECKED BY: MM
FRONT ELEVATION
<
x
• a
— PROPOSED FLOODLIGHT
WITH TIMER
10"
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S -JX COMMENT
C
06/29/2022
100% CD'S FOR REVIEW
B
02/09/2022
90% CD'S FOR REVIEW
A
01/14/2022
90% CD'S FOR REVIEW
REV
I DATE
I DESCRIPTION
FRONT VIEW SIDE VIEW 11.1' 20"(1-PHASE)
2s"
PROPOSED H-FRAME O O
SIDE FRONT A' W
VyTy��rD
24"x36"SCALE: NTS 24'x36' SCALE: NTS _eS� _ ¢ 5D5 T
200AMP METER 11"x17"SCALE: SITS 6 RAYCAP PPC RDIAC-6512-P-240-MTS 11"x17'SCALE:NTS PROPOSED
CIENA BOX.
SQUARE D SAFETY SWITCH
D324NRB
ENCLOSURE DIM (HxWxD)
29.25"x17.25"x8.25"
TOTAL WEIGHT (EMPTY)
45.33 LBS
MAX VOLTAGE/AMPS/WATT
240V/20OA/48000W
ENCLOSURE RATING
OUTDOOR NEMA 3R
KENWOOD T1701 KT5-5S
H—FRAME
52"
-
o
n
o
RESERVED
ED IF
REQUIRED.
p
PROPOSED
EQUIPMENT CABINET
FGf1 �f
DATE SIGNED: 12/22/2022
LnyO A. Wb—., P.E.
Pmf—i—d Engine:License:#c50547
Expireuon Dare: o6-3a2023
UNISTRUT/SUPPORT RAIL
5
PLAN
WEIGHT/ VOLUME
173.6 LBS
I IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
PLAN PROPOSED ARE ACTING UNDER THE DIRECTION OF A LICENSED
QQ TELCO FIBER PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
PIPE CAP ENCLOSURE
a
'T
G
SFSFOO1041A
WELDMENT, PIPE--,,,,10110
CALIFORNIA OAK WAY
CUPERTINO, CA 95014
y
TRANSMISSION TOWER
SUPPORT RAIL
FINISHED GRADE'
GAIN U-BOLTS
- -
SHEET TITLE
8"X8" BASE
PVC CONDUIT (TYP) CONCRETE PAD
DETAILS
PLATE
BACK ELEVATION
SHEET NUMBER
SIDE BACK FRONT
SIDE FRONT
SAFETY SWITCH 5
H-FRAME DETAIL �x17"SCALE: 2
H-FRAME ELEVATION 24"x36"SCALE: NTS 1
A_7
11"x17"SCALE: NTS
NTS
11"x17" SCALE: NTS
PARTS LIST
MAR% DESCRIPTCk+ I OTT
TRENCHING NOTES:
V9401 SRIR rELDMENT 1 - 1. CONTRACTOR SHALL RESTORE
179402 TI.W STMI _ - THE TRENCH TO ITS ORIGINAL
9PKT +.B.i71�jT 0 p 9 CONDITIONS BY EITHER SEEDING OR `✓
I unity D velopment DepartrYfie;nt SODOING GRASS AREAS, OR
1 REPLACING ASPHALT OR CONCRETE
81'S94 FOP>•EO PLATE - 96w AREAS TO ITS ORIGINAL CROSS -
,, } SECTION. SEE TRENCHING NOTE 1 ' -
.*sh
HARE I I O n — C U pe I lI I1 O _ 2. TRENCHING SAFETY: INCLUDING, BACKFILL FOR SITE WORK
SYM SILT DESORPTION .-� RED BUTTON BUT NOT LIMITED TO SOIL •
UPE IN CLASSIFICATION,SLOPING,AND SPECIFICATIONS (SEE GENERAL NOTES) �nnreless,.,
A5 R Vb t 1 VI SET ROVED SECTION A -A 31/8 SLOPE TO SUIT SOIL CONDITION IN
.7 2 L8• x 1 W4 LS BOLT ASSf, SHORING, SHALL BE GOVERNED BY
2 S/M x2 Gfieq� THE CURRENT OSHA TRENCHING AND ACCODRANCE WITH LOCAL REGULATIONS 5701 SSANTA BE DR
Ca e A5 1 wft k(58 � 2§00 �=H 3XCAALL CONDUITS SHALL
BEARDS. SEE TRENCHING NOTE 2 LITTLETON, CO 80120
rq5 2 5!B• NUT TTP. INSTALLED IN COMPLIANCE WITH THE z
Iication Num a TrP CURRENT NATIONAL ELECTRICAL �w
CODE (NEC) OR AS REQUIRED BY THE _ H
LOCAL JURISDICTION, WHICHEVER IS p w
THE MOST STRINGENT.
Ap ro aI body: Dire / t
ww
Apiproval Date 0 23 oz m=
MEETS EN418 NEMA 4 oZ o w7wsc sii
51 at re Gian Paolo Marti STANDARD p #B22-SC1-50D iris
MAINTAINED TWIST >LU
Ca se Marla e RELEASE OPERATOR y �� UTILITY WARNING TAPE 1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
SAND BEDDING PER SITE
TO K, WORK SPECIFICATIONS
LEG RF DISCONNECT BUTTONES/HANDLES 124".36' SCALE: NITS
1"xl7"SCALE: NTS 24"x36"SCALE: NTS 3 M S�UARKEE,-
6 TYPICAL UNDERGROUND TRENCH DETAIL 11"x17"SCALE: NTS �
WIRELESS
//_
C1i6TND PARTS
NCTE, ME 140" ADA*" T9
Rr AAIrLE T7rER LEGS FRDN
2 rI TO w AT gp ES OF
10 To 5 DODFM FVAN VEIIIWA
FUJITSU TRIPLE BAND
TA08025-6605
DIMENSIONS (HxWx D)
14.9"x15.7"x9
WEIGHT
74.95 Ibs
CONNECTOR TYPE
4.3-10 RF CONNECTOR
POWER SUPPLY
DC-58--36V
o
MINIMUM OF 75%OR
270° IN ANY DIRECTION
GPS
1387 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
DRAWN BY: EZG
CHECKED BY: MM
G 71,1115 PRODUCT 0 RATED T9
SLiMRT THE FCILL00114 LOADS GPS UNIT OBSTRUCTIONS MUST
Exr5lrM#j PAR75 $00 LIL DEAD LOAD BE BELOW 10°
WO La LATERAL ww LOAD
PFCMT m 08%09
F MODFTCATM FOR B VO9
P
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S-JX COMMENT
C
06/29/2022
100%CD'S FOR REVIEW
B
02/09/2022
90%CD'S FOR REVIEW
A
01/14/2022
90%CD'S FOR REVIEW
%REV
I DATE
I DESCRIPTION
[S PIPE MOUNT -SS L I
FOR 4-LEG ANGLE TOWERS
o
�-i 5gPLg
; BACK SIDE FRONT ��X W1QN+Q���
B139409 BRACKET DETAIL 11"x17"SCALE: NTS 8 FUJITSU TA08025-B605 VX17"SCALE: NTS 5 GPS MINIMUM SKY VIEW REQUIREMENTS 11x17 505 "SCALE: NTS 2
FUJITSU DUAL BAND
TA08025-B604
DIMENSIONS (HxWx D)
14.9"X15.7"X7.8"
WEIGHT
63.9 Ibs
CONNECTOR TYPE
4.3-10 RF CONNECTOR
POWER SUPPLY
DC -58--36V
"
MANUFACTURER:
MODEL NO.:
ROSENBERG
GPSGLONASS-36-N-S
LABEL
GROUNDING KITS,
INCLUDING NUTS, BOLT
AND CABLE CLAMP END
%,q CF W�
F CA
DATE SIGNED: 12/22/2022
Loyall A. Wb—., P.E.
Professional Engmn License: #C50547
Expt fio Daze: 06-10-2021
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
CONNECTOR:
N-FEMALE
RADOME COLOR:
WHITE
DIMENSION:
0 2.72" x H 3.88"
TOTAL WEIGHT:
1.14lbs
POLE DIAMETER:
1.18"4.92"
HEIGHT W/ BRACKET:
7.05"
PLAN
N TYPE CONNECTOR S FS FOO 1041 A
10110 CALIFORNIA OAK WAY
- CUPERTINO, CA 95014
TRANSMISSION TOWER
MODEL # A8R86 MODEL # A14128CHORFOW
NEMA TYPE 3R ENCLOSURE, FIBERGLASS, QUICK RELEASE GROUNDING
INCLUDDINGING NUTS, BOLT MOUNTING BRACKET SHEET TITLE
SCREW COVER LATCH W/ STANDARD COVER AND CABLE CLAMP END
(GENERATOR DOCUMENT BOX)
DETAILS
MOUNTING BRACKET
BACK SIDE FRONT TOP VIEW SIDE VIEW
SHEET NUMBER
RF DISCONNECT & GENERATOR DOC.BOX 11"x17"SCALE:NTS 7 FUJITSU TA08025-B604 24"x36"SCALE: NTS 24"x36"SCALE: NTS A'8
11"x17"SCALE: NTS 4 GPS ANTENNA 11"x17"SCALE: NTS 1
(N) CONCRETE PAD PER PLAN NOTE: •
1. ALL CONCRETE SHALL CONTAIN #4 REBAR
Community velopment Department WITH A I2"MAXIMUM GRID SPACING. ALLPW
(N) N N-CONDUCTIVE REBAR INTERSECTIONS MUST BE TIED.
Planningivision—Cuper`unTE o"CE `/ i ,6-
_ MI @ 12"DEPTH,
O.C., L WAY @ I wireless -
EACH
IN4 PPROV #4 REBAR@18"O.C. SHALL BE 3" ALLREBAR
MIN.
EACH WAY SHALL BE 3" CLR. MIN. Z
Ca e # I -2023- 03 FROM EDGE OF CONCRETE a 5701 S SANTA FE DR
K LITTLETON, CO 80120
� a
A p Ic tion Nu De SLOPE a
I I w
2500 PSI CONCRETE PAD I
Ap roval Body: Dii.,eclort tam--------------------
2/ /2 °
Apiprova I Date
I 3" CLR.,
Sigature Gian to Martire #4 NOSING BAR; TYP. (N)GRAVELBASE TYR wiws�sii
I I
ase Manager
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
3 0" 4
CONCRETE STOOP II x36"SCALE: NTS 6 CONCRETE PAD PLAN 24"x36"SCALE: NTS M UAR('v
11"x17"SCALE: NTS 11 "x17" SCALE: NTS L
WIRELESS i
PARTS LIST�519 1387 CALLE AVANZADO
MARK OESCRIPTON Or' _ SAN CLEMENTE CA 92673 (949) 391-6824
'AI419 WKT V4LQ"&NT Y yT t39LD7
•M402 TUBE STE& 7
•�9lOB w*T 1.ELOMFhT 7
3" X 3" FIBERGLASS POST - 1 ,4%b PLATE 7 %%1�
3" X 3' FIBERGLASS POST 'SU FAD Arc 1 "9411 00 O O
CONCRETE BASE. FLUSH WITH
(E) FINISH GRADE
4" PICKET
(E) FINISH GRADE
Q 2" X 3/4" RAIL
rr
DRAWN BY: EZG
SECTION A -A CHECKED BY: MM
n TTP- n6
A w.,l., OF 7 SCI
COVER PICKET (2) 1" GRIP ALUMINUM RIVET; TYP. -Cj wS 14ST BE Tr uum
-:*IT►CT WITH PART A
INSTALLATION RAIL 10 ' "40r
Tro, tlLT NIS rS
TO POST DETAIL
SECTION 77B4tt E9405
Jd
UNDISTURBED NATIVE SOIL
DETAIL 3" X 3" COMPOSITE CAP 4" PICKET; TYP.
4" OC
HARDWARE LIST
•. "q
CITY
DESCRPTON
AS
0
iris A 1 V2 SET 5LAE1w
.7
4
sr" x 1714 .'A IXXT ASST,
A
4
5,ft a 2 G5 EIOLT ASST
ro
2
SJ6 X 4 GS BOLT ASV.
OLT
c
57EE K 8 BOLT WIV THREAD
N5
4
SJ41'A1T
Lwr
4Lp"wAVER
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S -JX COMMENT
C
06/29/2022
100% CD'S FOR REVIEW
B
02/09/2022
90% CD'S FOR REVIEW
A
01/14/2022
90% CD'S FOR REVIEW
REV
DATE
DESCRIPTION
1 TYP.
4"PICKET II �
LEC. i0 �O„GLwoom O s�Ol�,Qi
12"MIN. _________ _ _ _ [
THS PADOMT 6 trim TO
FENCE POST FOOTING 24"x36"SCALE: NTS M 9 MIk 0' 40eOF 505
11"x17" SCALE: NTS 5 3" X 3" FIBERGLASS POST I [i TpyEfO I[ H45 !' OF 7 � PPE
►DAsSTMENT TO HOP CLEAR NOT "4111110 M EPT
_ ItTO'b+AL. 08t5T14ST7d4L
c
3" X 3" FIBERGLASS PRODUCT G RATED TO SUPPORT FNV
POST (BEYOND) 7W FOLLOWW� LDAD& F CA �Y
(Ol - -- -- - -- -- - -- -- - - -- - - = rA L8. LEAD LDW �jqp LATERAL MU LDAO DATE SIGNED: 12/22/2022
VARIES Loyall A. W6azmn, P.E.
2" X 3/4" RAIL (BEYOND); TYP. Professional Eng.—License: #C50547
Expuzuon Daze: 06-30-2023
2500 PSI #4 REBAR @ 12" O.C., EACH LAP 12" -
WAY @MID -DEPTH OF SLAB
CONCRETE SLAB TYR 1" CHAMFER IT IS RE OLATIOACTING
I OFUNDER
R THE D ANYREC PERSON, UNLESS THEY
@ 45" �.P ARE NAL ENGINEER,
THE DIRECTION HIS DLICENSEDUM
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
__ _ iOT OKLWT ADAMIT5 TO
__ __ _ __ __ _ _ __ _ -.0 TE V 2"X3/4"RAIL; TYP. ___ __ _ FIT A/YGLE Tp$1 LEGS FROM
+4%w
T''p-
(E)GRADE
r I
o '''' ' SFSF001041A
10110 CALIFORNIA OAK WAY
I CUPERTINO, CA 95014
Tw- OIL N5 W5 TRANSMISSION TOWER
6" CURBS @ 1lYp1 139L07 tlAi.
116
PERIMETER OF SLAB PRODUCT Fa B'41415
L— — — — — — — — — — — — — — — — — — — — — — — — — — — J
__. SHEET TITLE
IYSTALLATIDN DRAWING
r RE -COMPACT TO 90% UNDISTURBED NDISTUINSIDE MOUNT FOR RRM FOR 4-LEG ANGLE TOWES R'
a � DETAILS
RELATIVE COMPACTION EARTH FENCE SECTION FENCE FRONT ELEVATION _
�i By
e ° SHEET NUMBER
SECTION VIEW
7,r1 7ti*N �T�, x -�ATC 3TuRf3
CONCRETE PAD SECTION 11"x17"SCALE: NTS 4 NON-CONDUCTIVE COMPOSITE FENCE x17"SCALE: NTS 3 B141415 BRACKET DETAIL 24"x36"SCALE: NTS 1
1 Vx17" SCALE: NTS
PROPOSED •
DISH WIRELESS
Community Development Department CIENA BOX
�IIr
PROPOSED DISH WIRELESS
Planning Division — Cupertino DNISTRDT d.sh
APE .no APPROVED
wireless
Ca e# D I R-2023-003 IN IN OUT 5701 S SANTA FE DR
12
PROPOSED DISH WIRELESS LITTLETON, CO 80120
1-1/4" FLEX CONDUITS
Application Number(s) PROPOSED DISH WIRELESS
12 AWG WIRE (6' TAIL) PROPOSED DISH WIRELESS
TELCO FIBER ENCLOSURE
Ap rovaI Body: Director / Staff
A rova I Date 02/23/23 PROPOSED DISH WIRELESS
p 2 AMP DISTRIBUTION BREAKER PROPOSED DISH WIRELESS
FIBER DISTRIBUTION PANEL wiwsc sii
Sig ature Gian Paolo Martire PROPOSED DISH WIRELESS
RELESS
Case Manager 12 AWG WIRE �ROPOSED/22"FIBER TO (CABINET
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
1 0 T
PROPOSED DISH WIRELESS
1-1/2" POWER FROM CABINET - PROPOSED DISH WIRELESS 2" CONDUIT
FROM COMMERCIAL FIBER VAULT
NOT USED 9 NOT USED 6 LIT TELCO BOX WIRING LAYOUT 24"x36"SCALE: NTS 3 S UARICE
11'x17" SCALE: NTS Q ICE
WIRELESS
1387 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
PROPOSED DISH WIRELESS
UNISTRUT
DRAWN BY: EZG
PROPOSED DISH WIRELESS PROPOSED DISH WIRELESS CHECKED BY: MM
12 AWG WIRE (6' TAIL) TELCO FIBER ENCLOSURE
PROPOSED DISH WIRELESS 0
2 AMP DISTRIBUTION BREAKER PROPOSED DISH WIRELESS
FIBER DISTRIBUTION PANEL
IN 41NOU
PROPOSED DISH WIRELESS
12 AWG WIRE PROPOSED DISH WIRELESS
1-1/2" FIBER TO CABINET
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S -JX COMMENT
C
06/29/2022
100% CD'S FOR REVIEW
B
02/09/2022
90% CD'S FOR REVIEW
A
01/14/2022
90% CD'S FOR REVIEW
REV
DATE
DESCRIPTION
PROPOSED DISH WIRELESS
1-1/2" POWER FROM CABINET PROPOSED DISH WIRELESS
2" CONDUIT FROM dFEgg�Q
COMMERCIAL FIBER VAULT �Q� W 4(
NOT USED 8 NOT USED 5 DARK TELCO BOX WIRING LAYOUT 24"x36"SCALE: NTS 2 505
11"x17" SCALE: NTS
s'a CI-0-
CARLON EXPANSION FITTINGS
COUPLING
END PART#
MALE TERMINAL
ADAPTER END
PART #
SIZE
STD
CTN
QTY.
TRAVEL
LENGTH
E945D
E945DX
1/2"
20
4"
E945E
E945EX
3/4"
15
4"
E945F
E945FX
1"
10
4"
E945G
E945GX
1 1/4"
5
4"
E945H
E945HX
1 1/2"
5
4"
E945J
E945JX
2"
15
8"
E945K
E945KX
2 1/2"
10
8"
E945L
E945LX
3"
10
8"
E945M
E945MX
3 1/2"
5
8"
E945N
E945NX
4"
5
8"
E945P
E945PX
5"
1
8"
E945R
E945RX
6"
1
8"
FCA �
DATE SIGNED: 12/22/2022
VARIES PER
Loyal) A. Wb—., P.E.
PART NUMBER
Professional Engine: License: #C50547
y� Ir
Expimtm Date: 06-30,2023
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SLIP JOINT CHART SEE
(
r-1 FOR PART NUMBER)
I I
I I
I I
SFSFOO1041A
I I
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
NOTE:
SHEET TITLE
CONTRACTOR TO INSTALL EXPANSION
FITTING SLIP JOINT AT METER CENTER
CONDUIT TERMINATION, AS PER
ELECTRICAL DETAILS
LOCAL UTILITY POLICY, ORDINANCE
AND/OR SPECIFIED REQUIREMENT.
SHEET NUMBER
NOT USED 7 4 EXPANSION JOINT DETAIL 24"x36"SCALE: NTS 1 E-1
11"x17" SCALE: NTS
Community,Paval pm!jDr�NR�
artment
WITH PUULLLROPE TRENCH
�}��DPlanni '61)II no
APPROVED
TOO (E) PG&E 12KV
LJI F202T003
Application Number(s)
�p rovaI Body: Director / Staff
4prova I Date 02/23/23
3Ig ature Gian Paolo Martire
Case Manager
(N) MAIN ELECTRICAL SERVICE GROUND, -
5/8"X10'-0" COPPERCLAD STEEL GROUND,
BONDED WITH 192CU GND
RECONNECT FEEDERS, AS NEEDED PROVIDE
(N) 3#3/0 + 1#4 GND THHN CU ELECTRICAL
FEEDERS AS NEEDED
(N) PAD MOUNTED UTILITY TRANSFORMER, EC
TO PROVIDE (N) PRECAST CONCRETE PAD AND
GROUNDING GRID PER UTILITY REQUIREMENTS
(N) 4" PVC SCH 40 U/G CONDUIT WITH 3#500KCM + 1#2GND
THHN CU ELECTRICAL FEEDERS, TRENCH AND CONDUIT TO
MEET UTILITY STANDARDS, MINIMUM TRENCH DEPTH T-O"
(N) WP DUAL METER PEDESTAL WITH (2) 200AMP METER
SOCKETS WITH TEST BYPASS FACILITIES AND 4 JAW
M M METER SOCKETS WITH'T' FUSE PULLOUTS BUSMANN
TYPE JJN TO MEET UTILITY STANDARDS, MOUNT TO A
200AS 200AS (N) 4" CONCRETE HOUSE KEEPING PAD
200AF 200AF
2P 2P
REPLACE (E) BREAKER WITH FUSE SWITCH
UTILITY SERVICE ENTRANCE
120/240 VAC 1PH
BACKUP GENERATOR I
CAMLOCK GEN PLUG 200A
1
N
SURGE SUPPRESSION
DEVICE 100KA SAD/MOV
GFCI
03 04
15A
05 06
SPACE
07 08
SPACE
09 10
SPACE
11 12
SPACE
3 14
SPACE
15 16
SPACE
7 18
SPACE
19 20
SPACE
21 22
SPACE
24 26
(N) POWER PROTECTIVE CABINET 120/240V,
1 PH, SERVICE RATED, OVERALL UL LISTED
POWER CENTER, N3R, 65K/10K AIC
MAIN BREAKER WITH INTERLOCKED
GENERATOR FEED, 200A 65K AIC
a (N) 2 #10, 1 #10 CU GND.
(N) 2 #10
(N) (2) 0.75" EMT
CONDUITS
(N) (2) 0.75" EMT
CONDUITS
(N) (1) 0.5" EMT
CONDUITS
CHARLES NETWORK CABINET
FOR RECTIFIER 1
FOR RECTIFIER 2
FOR RECTIFIER 3
FOR RECTIFIER 4
d.v*sh
�r
wireless-
5701 S SANTA FE DR
LITTLETON, CO 80120
7 W/RLL
1200 DEL FASO RD, STE 150
SACRAMENTO, CA 95843
IVI SQUAR Lr
WIRELESS
1387 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
W (N) 3
CELL SITE " PVC SCH 40 U/G CONDUIT
WITH 3#3/0 + 1#4GND THHN CU (N) 2 #10, 1 #10 CU GND. FOR CONVENIENCE OUTLET
TO (E) T-MOBILE ELECTRICAL FEEDERS DRAWN BY: EZG
CHECKED BY: VIM
'r
NOTE:
BRANCH CIRCUIT WIRING SUPPLYING RECTIFIERS ARE TO BE RATED UL1015, 105°C, 600V, AND PVC INSULATED, IN THE SIZES SHOWN
IN THE ONE -LINE DIAGRAM, CONTRACTOR MAY SUBSTITUTE UL1015 WIRE FOR THWN-2 FOR CONVENIENCE OUTLET BRANCH CIRCUIT.
BREAKERS REQUIRED:
(4) 30A, 2P BREAKER - SQUARE D P/N:Q0230
(1) 15A, 1 P BREAKER - SQUARE D P/N:QO115
I SINGLE LINE DIAGRAM 1 2 1
PANEL SCHEDULE
LOAD SERVED
VOLT AMPS
(WATTS)
TRIP
CKKT
PHASE
CKT
TRIP
VOLT AMPS
(WATTS)
LOAD SERVED
L1
L2
L1
L2
PPC GFCI OUTLET
180
15A
1
A
2
30A
2880
ABB/GE INFINITY
RECTIFIER 1
CHARLES GFCI OUTLET
180
15A
3
B
4
2880
SPACE
5
A
6
30A
2880
ABB/GE INFINITY
RECTIFIER 2
SPACE
7
B
8
2880
SPACE
9
A
10
30A
2880
ABB/GE INFINITY
RECTIFIER 3
SPACE
11
B
12
2880
SPACE
13
A
14
30A
2880
ABB/GE INFINITY
RECTIFIER 4
SPACE
15
B
16
2880
SPACE
17
A
18
SPACE
SPACE
19
B
20
SPACE
SPACE
21
A
22
SPACE
SPACE
23
B
24
SPACE
VOLTAGE AMPS
1 180
180
1 11520
1 11520
200A MCB, 10, 24 SPACE, 120/240V
L1
L2
MB RATING: 65,000 AIC
11700
11700
VOLTAGE AMPS
98
98
AMPS
98
MAX AMPS
123
MAX 125%
PPC PANEL LOAD SCHEDULE
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S -JX COMMENT
C
06/29/2022
100% CD'S FOR REVIEW
B
02/09/2022
90%COS FOR REVIEW
A
01/14/2022
90%COS FOR REVIEW
%REV
I DATE
I DESCRIPTION
DATE SIGNED: 12/22/2022
Loyal) A. Wb—., P.E.
Professional Engine: License: #C50547
Expiration Date: 06-30,2023
IT IS AV LkTI F LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
SINGLE LINE DIAGRAM
AND PANEL SCHEDULE
SHEET NUMBER
E-2
1
NOTE: �
U LITY SERVICE PLAyNER T DESIGN W ERE AF�P
5� o F T e nt Department
Planning Division — Cupertino
,PE )No APPK) Q1Y9IQTYP.
-a e # / �R-2023-003 a
Number(s)
�pIroval136 Directo
4p�prov ale /23
-3igmature Gia .1.
UTILITY PLAN
Case M a7:)
Ise"
�O
Q
(E) TRANSMISSION —/
TOWER; TYP.
f
(E) PG&E TRNASFORMER;
(N) POWER P.O.C.
IN) PG&E PULLBOX
/ (E) CHAIN LINK FENCE; TYP.
/
/x
�x
/x
/x
�x
\
\ / APN: 342-63-001
\ /k
(E) PG&E POWER
\ / FACILITY
(E) TREE; TYP. \(/\
E, PVC SCH 40 CONDUIT ONLY WITH PULL
ROPE,
ROPE, MINIMUM TRENCH DEPTH 36" (CONDUIT
AND TRENCH TO MEET UTILITY REQUIREMENTS)
\ (E) \ \ FOR ENLARGED UTILITY
COMPOUND PLAN REFER TO:
BY OTHERS
e
� (E) EQUIPMENT AREA BY OTHERS; TYP.
x�
/x
(E)SHELTER N
s
III \
\r (E) TREE; TYP.
\
\ (N) U/G 4- PVC SCH 40 CONDUIT ONLY WITH PULL
/x \ ROPE, MINIMUM TRENCH DEPTH 36" (CONDUIT
/x AND TRENCH TO MEET UTILITY REQUIREMENTS)
/x \
/x \
(E) CHAIN LINK FENCE; TYP.
(N) W' U/G SCH 40 CONDUIT
FOR (N) ELECTRICAL SER%
TRENCH TO MEET UTILITY
(N) 400A, 120I240V, IPHASE, 3WIRE WP DUAL
METER PEDESTAL WITH (2) METER SOCKETS
COMPLETE WITH TEST BYPASS FACILITIES
AND 200A T' FUSE PULLOUTS MOUNTED TO
(N) 4" CONCRETE HOUSEKEEPING PAD
(N) UTILITY PRECAST CONCRETE UNDERGROUND
12KV VAULT (TO MEET UTILITY REQUIREMENTS)
24'x36"SCALE: 1-80'-0" 0" 40' 80, "'I 1 1 ENLARGED UTILITY PLAN
11"x17" SCALE: V = 160'-0"
Y
APN: 342-63-001
HANDHOLE ; FIBER P.O.C.
Y PAD MOUNTED TRANSFORMER, EC
...IDE (N) CONCRETE PRECAST PAD AND
GROUNDING GRID PER UTILITY REQUIREMENTS.
O
/ CONCRETE FILLED BOLLARDS (AS NEEDED)
(E) T-MOBILE UNDERGROUND CONCRETE
PULLBOX TO BE ABANDONED ONCE (N)
SERVICE IS CUTOVER TO (N) SWITCHBOARD
\ v
24"z36" SCALE: 1/8" V-0" 0" 4' 8' 16' 2
11"z17"SCALE: 1/16"=1'-0" �m ✓� 7i L
d .*s'
wireless-
5701 S SANTA FE DR
LITTLETON, CO 80120
clu.'am-7f
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
M SQ,UAR
WIRELESS
1387 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
DRAWN BY: EZG
CHECKED BY: MM
3
12/22/2022
100% COS FOR SUBMITTAL
2
10/28/2022
100% COS FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S -JX COMMENT
C
06/29/2022
100% CD'S FOR REVIEW
B
02/09/2022
90% CD'S FOR REVIEW
A
01/14/2022
90% CD'S FOR REVIEW
%REV
I DATE
I DESCRIPTION
DATE SIGNED: 12/22/2022
LoyaO A. Wb—., P.E.
Professional Engine: License: #C50547
Expiration Date: 06-30,2023
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
UTILITY PLAN AND
ENLARGED UTILITY PLAN
SHEET NUMBER
E-3
TO LOW NOISE AMPLIFIER UNITS
(LNA) (WHEN REQUIRED) ANDTO TRANSMIT ANTENNA 5 2
RECEIVE ANTENNA � 4 O •
2"
Community Development Department" �r
1. EXOTHERMIC WELD (2) TWO, 2 AWG BARE TINNED SOLID COPPER CONDUCTORS TO GROUND TX o
1 0 0 °° � �
W� �i_ iiSig'bMs�Pc�1�lED CLfreRihlf3,6NL PROVIDE PARALLEL EXOTHERMIC 0 0 0 .0 0 0 0 0 0
8 l.0 f T INLE RX1/RX2 RX1/RX2 o o ° ° o ° °
UPE INQ 2. ALL EXTERIOR GRO �Qij� j ALL BE STAINLESS STEEL 3/8" DIAMETER OR LARGER. - 3 �0 0 ° ° wireless -
ALL HARDWARE 18'STAINCL'L INCLUDING LOCK WASHERS, COAT ALL SURFACES WITH o
{�.}I. AN ANTI-OXI M EF TING. 1 SEE DETAIL 1
Ca e 1t �[ � 6 5TTLETONTA 812
'ii) E DR
LITTLETON, CO 80120
3 FOR GROI n n T NI c AT All SIIRFACFS WITH AN ANTI -OXIDANT COMPOUND COAX JUMPER REQUIRED PER
BEFORE MAT MANUFACTURER'S _ _
l ilplication Number(s) RECOMMENDATION OR FOR EASE STANDARD GROUNDING KIT, TYP. (SEE
4. DO NOT INSTALL CABLE GROUNDING KIT AT A BEND AND ALWAYS DIRECT GROUND CONDUCTOR OF CONNECTION (TYR) NOTE 7 ON SHEET G-2)
(DOO(�^j(N�/TO nGROrUUNN�D-INNGnBUS. Stp
Ap rova 15BSd &'WRS�€R'SF iSR rB/PLtP ON THE FRONT SIDE OF THE GROUND BAR AND BOLTED ON ANTENNA CABLE TO BTS, TYP. LEGEND:
THE BACK S CONNECTOR 1. COPPER GROUND BAR, 1/4"X 4"X 20", NEWTON INSTRUMENT CO. CAT. NO. B-6142 OR EQUAL. HOLE CENTERS
Apiprovaip�e� 6/23/23 WEATHERPROOFING TO MATCH NEMA DOUBLE LUG CONFIGURATION (ACTUAL GROUND BAR SIZE WILL VARY BASED ON NUMBER OF
II LLED BY CONTRACTOR. KIT, TYP. \ 6 AWG STRANDED COPPER GROUND CONNECTIONS) L,C�
\ CONDUCTOR WITH GREEN, 60OV, wiwsc sii
Sig atur'e7. THE fA�6 WNSIBLE FOR INSTALLING ADDITIONAL GROUND BAR AS 1 1' .,\ \ j THWN-2 INSULATION 2. INSULATORS, NEWTON INSTRUMENT CAT. NO. 3061-4 OR EQUAL
b Case IV)anamer FROM LNA (WHEN REQUIRED) \ \ \,\ \''1 GROUNDING BAR, ANDREW PART # 3. 5/8" LOCKWASHERS, NEWTON INSTRUMENT CO. CAT. NO. 3015-8 OR EQUAL WALL MOUNTING BRACKET, NEWTON
8. ENSURE THE WIRE INSULATION TERMINATION IS WITHIN 1/8" OF THE BARREL (NO SHINERS). '1 UGBKIT-0424-T (TINNED). A LOCKBOX INSTRUMENT CO. CAT NO. A-6056 OR EQUAL 1200 DEL PASO RD, STE 150
IS REQUIRED AT GRADE TASSCO PART # SACRAMENTO, CA 95843
351546. ANTENNA HEIGHT WILL 4. 5/8-11 X 1" HHCS BOLTS, NEWTON INSTRUMENT CO. CAT NO. 3012-1 OR EQUAL2 AWG `
CONDUCTOR TINNED,
EXOTHERMC COPPER
WED BARSDETERMINE
AND THEIIR LOCATION BER OF GROUNDING 5. INSULATORS SHALL BE ELIMINATED WHEN BONDING DIRECTLY TO TOWER/MONOPOLE STRUCTURE. CONNECTION TO
TO GROUNDING BUS TOWER/MONOPOLE STRUCTURE SHALL BE PER MANUFACTURERS RECOMMENDATIONS
TYPICAL GROUNDING NOTES 11x1TSCALE:SITS 9 GROUNDING BAR CONNECTION 24"x36"SCALE: NTS 6 GROUNDING BAR DETAIL 11x36"SCALE: NTS 1 M SQUARr•'
11"x17" SCALE: SITS 11'x17' SCALE: NTS 11'x17' SCALE: NTS WIRELESS €
NOTES:
1587 CALLE AVANZADO
1. DO NOT INSTALL CABLE GROUND KIT AT A BEND AND SAN CLEMENTE CA 92673 (949) 391-6824
ALWAYS DIRECT GROUND WIRE DOWN TO GROUND BAR.
ANTENNA (TYP.), NUMBER OF 2. GROUNDING KIT SHALL BE TYPE AND PART NUMBER AS
o ANTENNAS REPRESENTED IN SUPPLIED OR RECOMMENDED BY CABLE MANUFACTURER
THIS DETAIL ARE FOR SHOWING
CLARITY OF GROUND SYSTEM T&B CO. "C-TAP", CAT. #54730,
W 12"MIN REQUIREMENTS ONLY. CRIMP TYPE PARALLED TAP OR DRAWN BY: EZG
Q
EQUIVALENT
w
N CHECKED BY: MM
HYBRID CABLE In zf
MIN. #6 AWG STRANDED (GREEN T===9
1 /2" COAX JUMPER JACKET) COPPER GROUND WIRE
(BONDED TO GROUND BAR, TYP.)
WEATHERPROOFING KIT
(SEE NOTE 3) NEW RRU PER
PLAN (TYP)
CABLE GROUNDING KIT
#6 AWG STRANDED COPPER DIRECTION OF BOND TO TURN TO
CONDUCTOR WITH THWN-2 SHORTEST DISTANCE TO MGB
INSULATION GROUNDED TO GROUND
BAR (SEE NOTES 1 & 2)
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S -JX COMMENT
C
06/29/2022
100% CD'S FOR REVIEW
B
02/09/2022
90% CD'S FOR REVIEW
A
01/14/2022
90% CD'S FOR REVIEW
REV
DATE
DESCRIPTION
#2 AWG BARE COPPER
ANTENNA GROUND BAR GROUND CONDUCTOR TO #6 AWG GREEN INSULATED
MASTER GROUND BAR STRANDED COPPER WIRE (UNIT
BOND) dFrssloAI.�
ro��o� Tay �z
#2AWG GREEN STRANDED —
CONDUCTOR
CD
24'
GROUNDING KIT TO HYBRID TRUNK 11"x17"SCALE: SIT SCALE: NTS 8 ANTENNA GROUNDING PLAN 24"x36"SCALE: NTS 24"x36"SCALE: NTS 505
11"x17"SCALE: SITS 5 GROUNDING WIRE CONNECTION 11"x17"SCALE: SITS 2
s'a crV0-
NOTES: #6 AWG FROM ANTENNA FCA
CABLE GROUNDING NOT REQUIRED WHEN CABLE GROUND KIT
ANTENNA IS LESS THAN 10' FROM CABINET
DATE SIGNED: 12/22/2022
Loyal) A. Wb—., P.E.
Professional Engineez License: #CS0547
Expiration Date: 06-30,2023
GROUND BAR ON WALL,
FLOOR OR
ON ANTENNA ITISAVIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
TOWER SEE DETAIL 3 ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROPOSED CPS UNIT PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
#2 AWG GROUND ,I PROPOSED POST
CONDUCTOR TO GROUND
PROPOSED CPS UNITI MOUNT PROPOSED PIPE CLAMPS O DO O O DO SFSFOO1041A
OR APPROVED EQUIVALENT O O -O O 3 O O 10110 CALIFORNIA OAK WAY
o O CUPERTINO, CA 95014
TRANSMISSION TOWER
1/2" COAX CABLE 8" MIN O O
BENDING RADIUS PER CABLE
MANUFACTURER'S SPECIFICATIONS 1 ---GROUND WHENG CONDUCTOR SHALL ELIMINATED SHEET TITLE
*TWO HOLE LUG, OR EXOTHERMIC WELD TO WHEN GROUND BAR IS ELECTRIRI CALLY BONDED
f BE USED WITH #2 AWG BCW TO WATER TO METAL TOWER/MONOPOLE STRUCTURE
TO CABLE TRAY BAR
TO GROUND TANK WATER MAIN OR GROUND RING
BASE CONNECTION GROUND BUSS BAR GROUNDING DETAILS
# 2 GROUND
* —GROUND BARS AT THE BOTTOM OF TOWERS/MONOPOLES SHEET NUMBER
SHALL ONLY USE EXOTHERMIC WELDS. i w
OUTDOOR CABINET GROUNDING 24"x36"SCALE: NTS 7 TYPICAL GPS UNIT GROUNDING 24"x36" 4 WIRE TO GROUND BAR CONNECTION 24'x17'SCALE:NTS (v= 1 V x17" SCALE: NTS 11"x17" SCALE. NTS
EXISTING TOWER LEG
#2 TINNED SOLID IN 1/2" MIN
Community Development Department LIQUID TIGHT CONDUIT FROM
24" BELOW To 6R OF CADADE TO -WELD PIPE
ITHIN
TAMPER RESISTANT GROUND BAR S/S BOLT, TYP. TERMINATION POINT. EXPOSED
All
Plan�tii9 RD�Mgidh—Cup rtino ill NOTE: MIN OF 3 THREADS S/S SPLIT WASHER, TYP. END OF THE LIQUID TIGHT'
_ CODNUIT MUST BE SEALED W/ i
TAMPER RF.SI,$TP,jJT�ifjQ�NpB 1 TO BE VISIBLE, TYP. SILICONE CAULK U PE I N O HARDWA I FVoI�"3Vh�LL U S/S FLAT WASHER, TYP. GRADE
51701 S SANTA FIE DR
Ca e # GR U R 3 LITTLETON, CO 80120
MA' Vk&tion Number(s) 2 HOLE LONG BARREL
GROUND BAR MOUNTING TINNED SOLID COPPER
f1ACKET INC.W/ G 218- LUG, TYP. S/S FLAT WASHER, TYP.
p )
A rova I Body: Irec or % taf
TIN COATED SOLID -
UNIVERSAL T-BRACKET S/S NUT, TYP.
55��,/ I II COPPER BUS BAR GROUNDING ROD
S,-@Ff; !23 II III CADWEL, TYP.
Ap�rova I Date
° I Ill CHERRY INSULATOR _ u�iwsc sii
p SlgIll ature Gian Paolo Martire II II INSTALLED IF REQUIRED GROUNDOR RING 0 °u
Case Manager 0 ° 1200 DEL PASO RD, STE 150
10 10 SACRAMENTO, CA 95843
NEW 2"x12" GROUND BAR °
SITE PRO MG21218-K ° 0 0
0° °°
°° 0°
°° 0°
0°
®® ii LUG DETAIL 11"x17"SCALE: NTS 6 TRANSITIONING GROUND DETAIL 11"x17"SCALE: NTS 3 M SQUAB E
°° °° II WIRELESS
00
0° °° 1387 CALLE AVANZADO
6 ° ° ° SAN CLEMENTE CA 92673 (949) 391-6824
®® °° II 18"0 PRECAST WELL W/ 250 MCM BCW PIGTAIL FOR
°° 0 a I
NON-CONDUCTIVE LID EMERGENCY GENERATOR CONNECTION 12"0 X 24" DEEP INSPECTION
SLEEVE PVC OR SOIL PIPE W/
--
� EXISTING GRADE � CAP OR EQUIVALENT
NOTE: ° 0 FINISHED GRADE - DRAWN BY: EZG
()
ui
TOTAL OF 6 ROUND BARS TO BE INSTALLED: - DMC ? w
(1)GROUND BAR PER SECTOR LOCATED AT BASE CONNECTOR _ N� � CHECKED BY: MM
OF TOWER LEG (3 TOTAL) & (1) GROUND BAR PER 0
ix
SECTOR LOCATED AT ANTENNA LEVEL (3 TOTAL) rn
O¢
00 LU EXOTHERMIC CONNECTION
GROUNDING BAR ATTACHMENT 24"x36"SCALE: NTS _
Q �U
11"x17" SCALE: NTS v 3/4" CRUSHED STONE FILL p =
TEST WELL JUST BELOW THE 3 3/4" CRUSHED STONE OR EQUAL FILL
TOP OF T CONNECTOR 250 MCM BCW CONNECTED / -- TEST WELL TO WITHIN 2" OF TOP OF
BACK TO SITE GROUND GRID GROUNDING LOOP CONDUCTOR
NOTES: 10" X 5/8" COPPER
CLAD GROUND ROD
1. ANTENNA CABLES MUST BE CONTAINED IN CONDUIT.
2. VERTICAL CONDUIT RISERS AND BENDS CONNECTING THE UNDERGROUND CONDUITS TO
THE VERTICAL RISER SHALL BE INSTALLED IN ACCORDANCE WITH PG&E STANDARD, USING #2 AWG SOLID TINNED
PVC SCHEDULE 80 OR EQUIVALENT GALVANIZED STEEL MINIMUM 3INCHES IN DIAMETER
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S -JX COMMENT
C
06/29/2022
100% CD'S FOR REVIEW
B
02/09/2022
90%CD'S FOR REVIEW
01,14,2022
90%CD'S FOR REVIEW
VA
REV
DATE
DESCRIPTION
COPPER CONDUCTOR GROUNDING ROD, 1/2" MIN X
3. RISERS MUST BE INSTALLED TO THE HEIGHT OF THE CLIMBING BARRIER. EXTERIOR GROUND RING 8'-0" LONG COPPER CLAD
4. CUSTOM SHROUDS AND USE OF CONCRETE BLOCKS TO SUPPORT THE CONDUIT RISERS AT EMERGENCY GENERATOR GROUNDING TEST WELL STEEL (ERICO #625882) QE{dFess)o'�a
THE BASE OF THE TOWER FOOTING ARE NOT ALLOWED. $� x Wkw
5. FOR ADDITIONAL INFORMATION REFER TO PG&E MATERIAL AND HARDWARE BOOKLET.
CR
TYP.TEST WELL FOR EM. GEN. CONNECT. 14x17"SCALE: NTS 5 TYP. TEST GROUND ROD W/ INSP. SLEEVE 24"x36"SCALE:NTS 505
11"x17" SCALE: NTS 12
*NE
TOWER LEG t
srq crv(L �
R SUPPORT- ALL F CA
UST BE SUPPORTED
DATE SIGNED: 12/22/2022
EXISTING TOWERUND BAR (TYP.) CLOSED BARREL, FOR ALL EXTERIOR Loy.0 A. Wb—., P.E.
CROSS MEMBER TWO —HOLE CONNECTORS Professional Engi.e License:#CS0547
Expimtm Date: 06-30,2023
NE #2 AWG FROM GROUND EXTERNAL TOOTHED INCLUDE WARNING TAPE W/
O(N) TOWER GROUND BACKFILL PER SPECIFICATIONS IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
NEW 4"B1 CONDUIT RISER- 3/8"6 X 1 1 /2" ARE ACTING UNDER THE DIRECTION OF A LICENSED
ALL CABLES MUST BE INNG BOLT CONNECTION BLACK HEAT SHRINK UV RATED PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
THIS CONDUITWER LEG S/S NUT
S/S LOCK WASHER CONDUCTOR INSULATION TO BUTT OF w
NEW 6"0 PVCAGAINST THE CONNECTOR BARRELNEW CADWELD TO EXISTING —
CONDUIT STUB -UP 6"TOWER GROUND WIRE VISIBLE
ABOVE GRADE LEVELABOVE GROUND CONNECTION ---— — — — — — — p�
(SEE NOTE) LL c� S FS FOO 1041 A
S/S FLAT WASHER J11f11
EXISTING PG&E TOWER L Q � 10110 CALIFORNIA OAK WAY
GROUND TO EXISTING TINNED COPPER w w CUPERTINO, CA 95014
GROUND RING GRo I I _--— — — — — — — m rL GROUND RING, #2 AWG SOLID BARE TRANSMISSION TOWER
fO TINNED COPPER CONDUCTOR
II II S/S FLAT WASHER JJJff1, o
n n M
S/S BOLT
(1 OF 2) SHEET TITLE
n II
01 it 1/16" MIN SPACING
EXISTING TOWER GROUNDING DETAILS
FOOTING
7\
SHEET NUMBER
CONDUIT STUB -UP @TOWER 24"x36 SCALE: NTS 24"x36" SCALE: NTS 24"x36" SCALE: NTS G i2
11"x17"SCALE: NTS 7 TYPICAL EXTERIOR TWO HOLE LUG 11'x17"SCALE: NTS 4 TYPICAL GROUND RING TRENCH 11'x17' SCALE: NTS 1
CUPLFfTINO
NOTE:
C.prpMW0tyTPf-K gDepartment
"MaSTION$� RT.. .
"anninRUCTU*Tision—Cu ertino
APPROVED
Ca I
e # D I R-2023-003
Application Number(s) Alpha Sector
ApIrova I
Apiprova I
Sig (mature
Beta Sector
Gamma Sector
Y(r • + � _ RT • Y G HT • • c u M • Y G Y YLT w u • _ v, • Y G Y
Body: Director / Staff "N '°"'p^° F tawMW Md SwW
Date 02/23/23� j
Gian Paolo MartirManse
Mana
Case Manager
fMF O1C.OLC O�cdaar f W.r k.nlpxG ■ = ■ ■
r ■
- _---_'-_ %w m J- rn r n.rr1—IFhrr a.,-. � '� ■
■r rlr-6-i---------------------�-------.a '
1 f 1 ■
r�'nY in•ftrM0WMWMftW MMarw0rr-rrr-rrr- r.rrrrrrr-
pr G O►FIKE 1powear Fdw JU MPG"
r-60 Jr r%1ri-r-m fM-- -- -1• ww -- ----r - ---- --- --f -- -- -----f ---ai
IT■ �fl, F ■ f
� r
RR11 MCI` Iwnpela ■ ■ !
r
wnnau in :nis a.dla, 1acing f ■ ■ � ■ �
1heOVFs f ■ ± ; ��
ii i isi iF
NVbYrhWmrrk F ibrm Eann1
tc this side, painting away
fforn Cjvh
Span
Spam
Span
Span
Spare
Span
Middle tt—
T R Fmer
Tnmk Fibs-
lvr Floe-
71—& Aer b
7—F&K
T M Pips
t- Top
Pair+.2
Pmr 11
Par 79
Pair 9
Pas a
Pal, 7
Ci—aMid
6n—..Low
De1aMrd
D.A.L..
Alph.ftd
AV -Low
14+d RAu
Fiend MRIJ
band mw
F3and RRU
8en41Rrtu
B ww RRU
Borwn Raw
-hunk F-1w
Trw* FHwr
'rusk Flba•
Trunk Fiber
Trunk 17-
hunk Fbv
ralrb
Paw 3
PJNr a
Palr 3
Patl
Pair 1
GPSI Antenna
d.*sh
4a�
r
wireless
5701 S SANTA FE DR
LITTLETON, CO 80120
W/RLL L//
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
ill SQUARIEJ
WIRELESS
1387 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
DRAWN BY: EZG
CHECKED BV: MM
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S -JX COMMENT
C
06/29/2022
100% CD'S FOR REVIEW
B
02/09/2022
90% CD'9 FOR REVIEW
A
01/14/2022
90% CD'S FOR REVIEW
REV
I DATE
I DESCRIPTION
DATE SIGNED: 12/22/2022
Loyall A. Wb—., P.E.
Professional Engineer License: #C50547
Expiration Date: 06-30-2023
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
PLUMBING DIAGRAM
SHEET NUMBER
RF-1
EXOTHERMIC CONNECTION
ME//C^^HAANICAL CONNECTION
CHLi pLjUMjtyc QgiIIVlpAp.p nor nt De pa rt m e nt
�
e
AB
ABV
AC
ADDL
ANCHOR BOLT
ABOVE
ALTERNATING CURRENT
ADDITIONAL
IGR
IN
INT
LB(S)
INTERIOR GROUND RING
INCH
INTERIOR
POUND(S)
AFF
ABOVE FINISHED FLOOR
LF
LINEAR FEET
TEST CHEMIM g,p lie -s-ft pe rt i In o
e T
AFG
ABOVE FINISHED GRADE
LIE
LONG TERM EVOLUTION
OTHERMIC WITH INSPECTIO��}r'rCOVE D
)
❑�
AGL
AIC
ABOVE GROUND LEVEL
AMPERAGE INTERRUPTION CAPACITY
MAS
MAX
MASONRY
MAXIMUM
UPE
BAR
ALUM
ALUMINUM
MB
MACHINE BOLT
Ca
{GROUNDING
D I R-20233
a TGRO ROD
�
ALT
ALTERNATE
MECH
MECHANICAL
h-p003
ppnl��p-2 NuuND
TEST TNS'PE-CTfOIV-SL'EEVEF(S)
ANT
ANTENNA
MFR
MANUFACTURER
GROUND ROD WITH
— T
APPROX
APPROXIMATE
MGB
MASTER GROUND BAR
ARCH
ARCHITECTURAL
MIN
MINIMUM
Ap
ro hBodytrciDirector / Staff
ATS
AUTOMATIC TRANSFER SWITCH
MISC
MISCELLANEOUS
ApC
�/jP7p 02/23/23
�r(1ptJ�
AWG
AMERICAN WIRE GAUGE
MTL
METAL
'
nr��
BATT
BATTERY
MTS
MANUAL TRANSFER SWITCH
Sig
I
ature Gian Paolo Martire
G
BLDG
BUILDING
MW
MICROWAVE
DUPLEX
BLK
BLOCK
NEC
NATIONAL ELECTRIC CODE
Case Manager
BLKG
BLOCKING
NM
NEWTON METERS
r
FLUORESCENT LIGHTING FIXTURE i
F
BM
BEAM
NO.
NUMBER
(2) TWO LAMPS 48-T8 'i
BTC
BARE TINNED COPPER CONDUCTOR
#
NUMBER
BOF
BOTTOM OF FOOTING
NTS
NOT TO SCALE
SMOKE DETECTION (DC)
SD
CAB
CABINET
OC
ON -CENTER
CANT
CANTILEVERED
OSHA
OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
CHG
CHARGING
OPNG
OPENING
EMERGENCY LIGHTING (DC)
CLG
CEILING
P/C
PRECAST CONCRETE
SECURITY LIGHT W/PHOTOCELL LITHONIA ALXW
O
CLR
CLEAR
PCs
PERSONAL COMMUNICATION SERVICES
LED-1-25A400/51 K-SR4-120-PE-DDBTXD
COL
COLUMN
PCU
PRIMARY CONTROL UNIT
COMM
COMMON
PRC
PRIMARY RADIO CABINET
CHAIN LINK FENCE — x x x
x x x —
CONC
CONCRETE
PP
POLARIZING PRESERVING
0 0 0
WOOD/WROUGHT IRON FENCE 0 0
0 0 0 0 0 0 00
0 0 0 0 0 0 o
�o
CONSTR
CONSTRUCTION
PSF
POUNDS PER SQUARE FOOT
WALL STRUCTURE
DBL
DOUBLE
PSI
POUNDS PER SQUARE INCH
DC
DIRECT CURRENT
PT
PRESSURE TREATED
LEASE AREA
DEPT
DEPARTMENT
PWR
POWER CABINET
PROPERTY LINE (PL) ----------------------
DF
DOUGLAS FIR
QTY
QUANTITY
DIA
DIAMETER
RAD
RADIUS
SETBACKS
DIAG
DIAGONAL
RECT
RECTIFIER
ICE BRIDGE
DIM
DIMENSION
REF
REFERENCE
DWG
DRAWING
REINF
REINFORCEMENT
CABLE TRAY
DWL
DOWEL
REQ'D
REQUIRED
WATER LINE — . — . — . — .
— . — . — . — . — . — . —
EA
EACH
RET
REMOTE ELECTRIC TILT
EC
ELECTRICAL CONDUCTOR
RE
RADIO FREQUENCY
UNDERGROUND POWER
EL.
ELEVATION
RMC
RIGID METALLIC CONDUIT
UNDERGROUND TELCO W* — W* — W* — W* —
W* — W* — W* — W* — W* — W* — W*
ELEC
ELECTRICAL
RRH
REMOTE RADIO HEAD
EMT
ELECTRICAL METALLIC TUBING
RRU
REMOTE RADIO UNIT
OVERHEAD POWER
ENG
ENGINEER
RWY
RACEWAY
OVERHEAD TELCO
EQ
EQUAL
SCH
SCHEDULE
UNDERGROUND TELCO/POWER —„ 11 — „u/, — „u/, — „u/,
— „u/, — „u/, — „u/, — „u/, — „u/, —
EXP
EXPANSION
SHT
SHEET
EXT
EXTERIOR
SIAD
SMART INTEGRATED ACCESS DEVICE
ABOVE GROUND POWER
EW
EACH WAY
SIM
SIMILAR
ABOVE GROUND TELCO
FAB
FABRICATION
SPEC
SPECIFICATION
FF
FINISH FLOOR
SO
SQUARE
ABOVE GROUND TELCO/POWER
FG
FINISH GRADE
SS
STAINLESS STEEL
WORKPOINT
FIF
FACILITY INTERFACE FRAME
STD
STANDARD
W.P.
FIN
FINISH(ED)
STL
STEEL
SECTION REFERENCE X
FLR
FLOOR
TEMP
TEMPORARY
X-X
FDN
FOUNDATION
THK
THICKNESS
FOC
FACE OF CONCRETE
TMA
TOWER MOUNTED AMPLIFIER
DETAIL REFERENCE
X
X-X
FOM
FACE OF MASONRY
TN
TOE NAIL
FOS
FACE OF STUD
TOA
TOP OF ANTENNA
FOW
FACE OF WALL
TOC
TOP OF CURB
FS
FINISH SURFACE
TOE
TOP OF FOUNDATION
FT
FOOT
TOP
TOP OF PLATE (PARAPET)
FTG
FOOTING
TOS
TOP OF STEEL
GA
GAUGE
TOW
TOP OF WALL
GEN
GENERATOR
TVSS
TRANSIENT VOLTAGE SURGE SUPPRESSION
GFCI
GROUND FAULT CIRCUIT INTERRUPTER
TYP
TYPICAL
GLB
GLUE LAMINATED BEAM
UG
UNDERGROUND
GLV
GALVANIZED
UL
UNDERWRITERS LABORATORY
GPS
GLOBAL POSITIONING SYSTEM
UNO
UNLESS NOTED OTHERWISE
GND
GROUND
UMTS
UNIVERSAL MOBILE TELECOMMUNICATIONS SYSTEM
GSM
GLOBAL SYSTEM FOR MOBILE
UPS
UNITERRUPTIBLE POWER SYSTEM (DC POWER PLANT)
HDG HOT DIPPED GALVANIZED
VIE
VERIFIED IN FIELD
HDR
HEADER
W
WIDE
HGR
HANGER
W/
WITH
HVAC
HEATNENTILATION/AIR CONDITIONING
WD
WOOD
HT
HEIGHT
WP
WEATHERPROOF
WT
WEIGHT
LEGEND
ABBREVIATIONS
wireless-
5701 S SANTA FE DR
LITTLETON, CO 80120 ,
c7u.10.d7Am77f_
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
M SQIUARr•
WIRELESS
1367 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
DRAWN BY: EZG
CHECKED BY: MM
3
12/22/2022
100% CYS FOR SUBMITTAL
2
10/28/2022
100% CYS FOR SUBMITTAL
1
10/05/2022
100% CYS FOR SUBMITTAL
0
07/22/2022
100%CYS -JX COMMENT
C
06/29/2022
100%CD'S FOR REVIEW
B
02/09/2022
90%CD'S FOR REVIEW
A
01/14/2022
90%CD'S FOR REVIEW
REV
I DATE
DESCRIPTION
DATE SIGNED: 12/22/2022
Loyal) A. Wb—., P.E.
Professional Engine: License: #C50547
Expiration Date: 06-30,2023
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
LEGEND AND
ABBREVIATIONS
SHEET NUMBER
GN-1
Ca
SITE ACTIVITY REQUIREMENTS:
CoNOTICET M I%( WORK �'L�f UONOMM� NOTERING THE ST E YOU MUST CONTACT THE DISH WIRELESS AND TOWER RECEIVING A WRITTEN NOTICE TO PROCEED (NTP) AND THE
Off/ aERnNnOC &�7Ttp�I/5IH WIRELESS AND
]TpO�W' RR OWNER CONSTRUCTION MANAGER.
"L�rO++ KUP"I�II��WIppF�EppLDD9AN7T���W RU`NLQ AFETYCLIMBREQUIREMENT:
r1"IE INTEGRITY OF THE SPiFHi'r(A9R6Bi EDLL COMPONENTS OF THE CLIMBING FACILITY SHALL BE CONSIDERED DURING ALL STAGES OF DESIGN,
INSTAULAT
WER
FICATION, MOUNT
NFORCEMENTS, AND/OR
a # COMPROMI DiMTE�AIItOQR.FANCTIONALI USE OFT E BA SAFETY (CLIMB OR ANY COMPONENTS EQUIPMENT
OF THE CLIMBING FACILITY ON THE
: PINCHING OF THE WIRE ROPE, BENDING OF THE WIRE ROPE FROM ITS
SUPPORT , �t� I�Q l LOSE PROXIMITY TO THE WIRE ROPE WHICH MAY CAUSE FRICTIONAL WEAR, IMPACT TO THE ANCHORAGE
POINTS IN ANY WAY, OR TO IMPEDE/BLOCK ITS INTENDED USE. ANY COMPROMISED SAFETY CLIMB, INCLUDING EXISTING CONDITIONS MUST
rova I BA ETYCLIIG GIAIN�T�EfAND CONTRACTOR11DR;ff TO YOUR DISH WIRELESS
NOTICE TICKET.
DISHWIRELESS AND TOWER OWNER POC OR CALL THE NOC TO GENERATE
rovva I D43Fts�1 TO TQ?4S Pl' PCONSTRUCTION, ALL REQUIRED JURISDICTIONAL PERMITS SHALL BE OBTAINED. THIS INCLUDES, BUT IS NOT
LIMITED TO, BUILDING, ELECTRICAL, MECHANICAL, FIRE, FLOOD ZONE, ENVIRONMENTAL, AND ZONING. AFTER ONSITE ACTIVITIES AND
a t u re CONGj0nTftGkE ktUftWED, ALL REQUIRED PERMITS SHALL BE SATISFIED AND CLOSED OUT ACCORDING TO LOCAL JURISDICTIONAL
REQUIREMENTS. Case Manager
4. ALL CONSTRUCTION MEANS AND METHODS; INCLUDING BUT NOT LIMITED TO, ERECTION PLANS, RIGGING PLANS, CLIMBING PLANS, AND
RESCUE PLANS SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR RESPONSIBLE FOR THE EXECUTION OF THE WORK
CONTAINED HEREIN, AND SHALL MEET ANSI/ASSE A10.48 (LATEST EDITION); FEDERAL, STATE, AND LOCAL REGULATIONS; AND ANY
APPLICABLE INDUSTRY CONSENSUS STANDARDS RELATED TO THE CONSTRUCTION ACTIVITIES BEING PERFORMED. ALL RIGGING PLANS
SHALL ADHERE TO ANSI/ASSE A10.48 (LATEST EDITION) AND DISH WIRELESS AND TOWER OWNER STANDARDS, INCLUDING THE REQUIRED
INVOLVEMENT OF A QUALIFIED ENGINEER FOR CLASS IV CONSTRUCTION TO CERTIFY THE SUPPORTING Q O STRUCTURES IN ACCORDANCE
WITH ANSI/TIA-322 (LATEST EDITION).
5. ALL SITE WORK TO COMPLY WITH DISH WIRELESS AND TOWER OWNER INSTALLATION STANDARDS FOR CONSTRUCTION ACTIVITIES ON DISH
WIRELESS AND TOWER OWNER TOWER SITE AND LATEST VERSION OF ANSI/TIA-1019-A-2012 "STANDARD FOR INSTALLATION, ALTERATION,
AND MAINTENANCE OF ANTENNA SUPPORTING STRUCTURES AND ANTENNAS."
6. IF THE SPECIFIED EQUIPMENT CAN NOT BE INSTALLED AS SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALL PROPOSE AN
ALTERNATIVE INSTALLATION FOR APPROVAL BY DISH WIRELESS AND TOWER OWNER PRIOR TO PROCEEDING WITH ANY SUCH CHANGE OF
INSTALLATION.
7. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE CODES, REGULATIONS AND
ORDINANCES. CONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES AND COMPLY WITH ALL LAWS, ORDINANCES, RULES, REGULATIONS
AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY REGARDING THE PERFORMANCE OF THE WORK. ALL WORK CARRIED OUT SHALL COMPLY
WITH ALL APPLICABLE MUNICIPAL AND UTILITY COMPANY SPECIFICATIONS AND LOCAL JURISDICTIONAL CODES, ORDINANCES AND
APPLICABLE REGULATIONS.
8. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS UNLESS
SPECIFICALLY STATED OTHERWISE.
9. THE CONTRACTOR SHALL CONTACT UTILITY LOCATING SERVICES INCLUDING PRIVATE LOCATES SERVICES PRIOR TO THE START OF
CONSTRUCTION.
10. ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES WHERE ENCOUNTERED IN THE WORK, SHALL BE PROTECTED AT
ALL TIMES AND WHERE REQUIRED FOR THE PROPER EXECUTION OF THE WORK, SHALL BE RELOCATED AS DIRECTED BY CONTRACTOR.
EXTREME CAUTION SHOULD BE USED BY THE CONTRACTOR WHEN EXCAVATING OR DRILLING PIERS AROUND OR NEAR UTILITIES.
CONTRACTOR SHALL PROVIDE SAFETY TRAINING FOR THE WORKING CREW. THIS WILL INCLUDE BUT NOT BE LIMITED TO A) FALL
PROTECTION B) CONFINED SPACE C) ELECTRICAL SAFETY D) TRENCHING AND EXCAVATION E) CONSTRUCTION SAFETY PROCEDURES.
11. ALL SITE WORK SHALL BE AS INDICATED ON THE STAMPED CONSTRUCTION DRAWINGS AND DISH PROJECT SPECIFICATIONS, LATEST
APPROVED REVISION.
12. CONTRACTOR SHALL KEEP THE SITE FREE FROM ACCUMULATING WASTE MATERIAL, DEBRIS, AND TRASH AT THE COMPLETION OF THE
WORK. IF NECESSARY, RUBBISH, STUMPS, DEBRIS, STICKS, STONES AND OTHER REFUSE SHALL BE REMOVED FROM THE SITE AND DISPOSED
OF LEGALLY.
13. ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES, WHICH INTERFERE WITH THE EXECUTION OF THE WORK,
SHALL BE REMOVED AND/OR CAPPED, PLUGGED OR OTHERWISE DISCONTINUED AT POINTS WHICH WILL NOT INTERFERE WITH THE
EXECUTION OF THE WORK, SUBJECT TO THE APPROVAL OF DISH WIRELESS AND TOWER OWNER, AND/OR LOCAL UTILITIES.
14. THE CONTRACTOR SHALL PROVIDE SITE SIGNAGE IN ACCORDANCE WITH THE TECHNICAL SPECIFICATION FOR SITE SIGNAGE REQUIRED BY
LOCAL JURISDICTION AND SIGNAGE REQUIRED ON INDIVIDUAL PIECES OF EQUIPMENT, ROOMS, AND SHELTERS.
15. THE SITE SHALL BE GRADED TO CAUSE SURFACE WATER TO FLOW AWAY FROM THE CARRIER'S EQUIPMENT AND TOWER AREAS.
16. THE SUB GRADE SHALL BE COMPACTED AND BROUGHT TO A SMOOTH UNIFORM GRADE PRIOR TO FINISHED SURFACE APPLICATION.
17. THE AREAS OF THE OWNERS PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY THE TOWER, EQUIPMENT OR DRIVEWAY, SHALL
BE GRADED TO A UNIFORM SLOPE, AND STABILIZED TO PREVENT EROSION AS SPECIFIED ON THE CONSTRUCTION DRAWINGS AND/OR
PROJECT SPECIFICATIONS.
18. CONTRACTOR SHALL MINIMIZE DISTURBANCE TO EXISTING SITE DURING CONSTRUCTION. EROSION CONTROL MEASURES, IF REQUIRED
DURING CONSTRUCTION, SHALL BE IN CONFORMANCE WITH THE LOCAL GUIDELINES FOR EROSION AND SEDIMENT CONTROL.
19. THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS, LANDSCAPING AND STRUCTURES. ANY DAMAGED PART
SHALL BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE SATISFACTION OF OWNER.
20. CONTRACTOR SHALL LEGALLY AND PROPERLY DISPOSE OF ALL SCRAP MATERIALS SUCH AS COAXIAL CABLES AND OTHER ITEMS REMOVED
FROM THE EXISTING FACILITY. ANTENNAS AND RADIOS REMOVED SHALL BE RETURNED TO THE OWNER'S DESIGNATED LOCATION.
21. CONTRACTOR SHALL LEAVE PREMISES IN CLEAN CONDITION. TRASH AND DEBRIS SHOULD BE REMOVED FROM SITE ON A DAILY BASIS.
22. NO FILL OR EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUND. FROZEN MATERIALS, SNOW OR ICE SHALL NOT BE PLACED IN
ANY FILL OR EMBANKMENT.
GENERAL NOTES:
1.FOR THE PURPOSE OF CONSTRUCTION DRAWING, THE FOLLOWING DEFINITIONS SHALL APPLY:
CONTRACTOR: GENERAL CONTRACTOR RESPONSIBLE FOR CONSTRUCTION
CARRIER:DISH WIRELESS
1CUTi9:1YUTi9!1:1 ;TA I180N:1:1 1111Ti9il1:1V
2. THESE DRAWINGS HAVE BEEN PREPARED USING STANDARDS OF PROFESSIONAL CARE AND COMPLETENESS NORMALLY EXERCISED UNDER
SIMILAR CIRCUMSTANCES BY REPUTABLE ENGINEERS IN THIS OR SIMILAR LOCALITIES. IT IS ASSUMED THAT THE WORK DEPICTED WILL BE
PERFORMED BY AN EXPERIENCED CONTRACTOR AND/OR WORKPEOPLE WHO HAVE A WORKING KNOWLEDGE OF THE APPLICABLE CODE
STANDARDS AND REQUIREMENTS AND OF INDUSTRY ACCEPTED STANDARD GOOD PRACTICE. AS NOT EVERY CONDITION OR ELEMENT IS
(OR CAN BE) EXPLICITLY SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALL USE INDUSTRY ACCEPTED STANDARD GOOD PRACTICE
FOR MISCELLANEOUS WORK NOT EXPLICITLY SHOWN.
3. THESE DRAWINGS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE MEANS OR METHODS OF CONSTRUCTION. THE
CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, AND PROCEDURES.
THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY FOR PROTECTION OF LIFE AND PROPERTY DURING CONSTRUCTION. SUCH
MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO, BRACING, FORMWORK, SHORING, ETC. SITE VISITS BY THE ENGINEER OR HIS
REPRESENTATIVE WILL NOT INCLUDE INSPECTION OF THESE ITEMS AND IS FOR STRUCTURAL OBSERVATION OF THE FINISHED STRUCTURE
ONLY.
4. NOTES AND DETAILS IN THE CONSTRUCTION DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. WHERE
NO DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR WORK ON THE PROJECT, AND/OR AS PROVIDED FOR IN THE
CONTRACT DOCUMENTS. WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, GENERAL NOTES, AND SPECIFICATIONS, THE
GREATER, MORE STRICT REQUIREMENTS, SHALL GOVERN. IF FURTHER CLARIFICATION IS REQUIRED CONTACT THE ENGINEER OF RECORD.
5. SUBSTANTIAL EFFORT HAS BEEN MADE TO PROVIDE ACCURATE DIMENSIONS AND MEASUREMENTS ON THE DRAWINGS TO ASSIST IN THE
FABRICATION AND/OR PLACEMENT OF CONSTRUCTION ELEMENTS BUT IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO FIELD
VERIFY THE DIMENSIONS, MEASUREMENTS, AND/OR CLEARANCES SHOWN IN THE CONSTRUCTION DRAWINGS PRIOR TO FABRICATION OR
CUTTING OF ANY NEW OR EXISTING CONSTRUCTION ELEMENTS. IF IT IS DETERMINED THAT THERE ARE DISCREPANCIES AND/OR CONFLICTS
WITH THE CONSTRUCTION DRAWINGS THE ENGINEER OF RECORD IS TO BE NOTIFIED AS SOON AS POSSIBLE.
6. PRIOR TO THE SUBMISSION OF BIDS, THE BIDDING CONTRACTOR SHALL VISIT THE CELL SITE TO FAMILIARIZE WITH THE EXISTING
CONDITIONS AND TO CONFIRM THAT THE WORK CAN BE ACCOMPLISHED AS SHOWN ON THE CONSTRUCTION DRAWINGS. ANY DISCREPANCY
FOUND SHALL BE BROUGHT TO THE ATTENTION OF CARRIER POC AND TOWER OWNER.
7. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE CODES, REGULATIONS AND
ORDINANCES. CONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES AND COMPLY WITH ALL LAWS, ORDINANCES, RULES, REGULATIONS
AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY REGARDING THE PERFORMANCE OF THE WORK. ALL WORK CARRIED OUT SHALL COMPLY
WITH ALL APPLICABLE MUNICIPAL AND UTILITY COMPANY SPECIFICATIONS AND LOCAL JURISDICTIONAL CODES, ORDINANCES AND
APPLICABLE REGULATIONS.
8. UNLESS NOTED OTHERWISE, THE WORK SHALL INCLUDE FURNISHING MATERIALS, EQUIPMENT, APPURTENANCES AND LABOR NECESSARY
TO COMPLETE ALL INSTALLATIONS AS INDICATED ON THE DRAWINGS.
9. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS UNLESS
SPECIFICALLY STATED OTHERWISE.
10. IF THE SPECIFIED EQUIPMENT CAN NOT BE INSTALLED AS SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALL PROPOSE AN
ALTERNATIVE INSTALLATION FOR APPROVAL BY THE CARRIER AND TOWER OWNER PRIOR TO PROCEEDING WITH ANY SUCH CHANGE OF
INSTALLATION.
11. CONTRACTOR IS TO PERFORM A SITE INVESTIGATION, BEFORE SUBMITTING BIDS, TO DETERMINE THE BEST ROUTING OF ALL CONDUITS FOR
POWER, AND TELCO AND FOR GROUNDING CABLES AS SHOWN IN THE POWER, TELCO, AND GROUNDING PLAN DRAWINGS.
12. THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS, LANDSCAPING AND STRUCTURES. ANY DAMAGED PART
SHALL BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE SATISFACTION OF DISH WIRELESS AND TOWER OWNER
13. CONTRACTOR SHALL LEGALLY AND PROPERLY DISPOSE OF ALL SCRAP MATERIALS SUCH AS COAXIAL CABLES AND OTHER ITEMS REMOVED
FROM THE EXISTING FACILITY. ANTENNAS REMOVED SHALL BE RETURNED TO THE OWNER'S DESIGNATED LOCATION.
14. CONTRACTOR SHALL LEAVE PREMISES IN CLEAN CONDITION. TRASH AND DEBRIS SHOULD BE REMOVED FROM SITE ON A DAILY BASIS.
dl%W 4%0
wireless-
5701 S SANTA FE DR
LITTLETON, CO 80120
I L�
W/RLL L//
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
M S UARr•�-
�WIRELESS
1367 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
DRAWN BY: EZG
CHECKED BY: MM
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S-JX COMMENT
C
06/29/2022
100%CD'S FOR REVIEW
B
02/09/2022
90%CD'S FOR REVIEW
A
01/14/2022
90%CD'S FOR REVIEW
REV
I DATE
I DESCRIPTION
DATE SIGNED: 12/22/2022
Loyal) A. Wb-., P.E.
Professional Engine: License: #C50547
Expiration Date: 06-30,2023
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
GENERAL NOTES
SHEET NUMBER
GN-2
CONCRETE, FOUNDATIONS, AND REINFORCING STEEL:
1. ALL CONCRETE WORK
�SHALL
y BCE INAACCORDANCE WITH THE
tACI 301, ACI 318, ACI 336, ASTM A184, ASTM A185 AND THE DESIGN AND
Co �f11Ur1��lnl'ycl3TQC}V�/G�s6i5f ICfftCE rP�gWff& E ETE.
2. U3. ANS IS ASSUMED TO BE 1000 psf.
NONCRTED Ei1LSH�ALLIIT�(V�E�rA}MIINN, MPeOa:t@?SIVE STRENGTH (fc) OF 3000 jIjERWjSE, SOIL.EJEARING PRESSURE USED FOR DESIGN OF si AT 28 DAYS, UNLEBS AND ISS NOTED OTHERWISE. NO MORE THAN 90
C U PE I N O MINUTES CONCRETE SHALL IALppT NO nn�� ��EE6nny//�7°f��AT TIME E OF PLAOF CEMENT.
EMENT. PLACEMENT UNLESS APPROVED BY THE ENGINEER OF RECORD. TEMPERATURE OF
Ca e # CONCRETE DRr2CO�i3�83IS 3AW CYCLES SHALL CONTAIN AIR ENTRAINING ADMIXTURES. AMOUNT OF AIR ENTRAINMENT TO BE BASED ON
it RE). CEMENT USED TO BE TYPE II PORTLAND CEMENT WITH A MAXIMUM
WATER-T - VA
1 0.45.
5. AL STE REINFORCIN HA ONFORM TO ASTM A615. ALL WELDED WIRE FABRIC (WWF) SHALL CONFORM TO ASTM A185. ALL SPLICES SHALL
Ap rova I B A treagrN I UNLESS NOTED OTHERWISE. ALL HOOKS SHALL BE STANDARD 90 DEGREE HOOKS, UNLESS NOTED OTHERWISE.
Ap[prova I D YIfLLD STR61U6TF YM STANDARD DEFORMED BARS ARE AS FOLLOWS:
I #4 BARS ANDS V 40 Ksl
Sig at"6MRSAND Giia 8FROI O Martire
6. THE FOLLOWING(RIT&MMIMRCRETE COVER SHALL BE PROVIDED FOR REINFORCING STEEL UNLESS SHOWN OTHERWISE ON DRAWINGS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3"
CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 BARS AND LARGER 2"
#5 BARS AND SMALLER 1-1/2"
CONCRETE NOT EXPOSED TO EARTH OR WEATHER:
SLAB AND WALLS 3/4"
BEAMS AND COLUMNS 1-1/2"
7. A TOOLED EDGE OR A 3/4" CHAMFER SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE, UNLESS NOTED OTHERWISE, IN ACCORDANCE
WITH ACI 301 SECTION 4.2.4.
ELECTRICAL INSTALLATION NOTES:
1. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, NEC AND ALL APPLICABLE FEDERAL,
STATE, AND LOCAL CODES/ORDINANCES.
2. CONDUIT ROUTINGS ARE SCHEMATIC. CONTRACTOR SHALL INSTALL CONDUITS SO THAT ACCESS TO EQUIPMENT IS NOT BLOCKED AND TRIP
HAZARDS ARE ELIMINATED.
3. WIRING, RACEWAY AND SUPPORT METHODS AND MATERIALS SHALL COMPLY WITH THE REQUIREMENTS OF THE NEC.
4. ALL CIRCUITS SHALL BE SEGREGATED AND MAINTAIN MINIMUM CABLE SEPARATION AS REQUIRED BY THE NEC.
4.1. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OF APPROVAL, AND SHALL CONFORM TO REQUIREMENT OF THE
NATIONAL ELECTRICAL CODE.
4.2. ALL OVERCURRENT DEVICES SHALL HAVE AN INTERRUPTING CURRENT RATING THAT SHALL BE GREATER THAN THE SHORT CIRCUIT CURRENT
TO WHICH THEY ARE SUBJECTED, 22,000 AIC MINIMUM. VERIFY AVAILABLE SHORT CIRCUIT CURRENT DOES NOT EXCEED THE RATING OF
ELECTRICAL EQUIPMENT IN ACCORDANCE WITH ARTICLE 110.24 NEC OR THE MOST CURRENT ADOPTED CODE PRE THE GOVERNING
JURISDICTION.
5. EACH END OF EVERY POWER PHASE CONDUCTOR, GROUNDING CONDUCTOR, AND TELCO CONDUCTOR OR CABLE SHALL BE LABELED WITH
COLOR -CODED INSULATION OR ELECTRICAL TAPE (3M BRAND, 1/2" PLASTIC ELECTRICAL TAPE WITH UV PROTECTION, OR EQUAL). THE
IDENTIFICATION METHOD SHALL CONFORM WITH NEC AND OSHA.
6. ALL ELECTRICAL COMPONENTS SHALL BE CLEARLY LABELED WITH LAMICOID TAGS SHOWING THEIR RATED VOLTAGE, PHASE CONFIGURATION,
WIRE CONFIGURATION, POWER OR AMPACITY RATING AND BRANCH CIRCUIT ID NUMBERS (i.e. PANEL BOARD AND CIRCUIT ID'S).
7. PANEL BOARDS (ID NUMBERS) SHALL BE CLEARLY LABELED WITH PLASTIC LABELS.
8. TIE WRAPS ARE NOT ALLOWED.
9. ALL POWER AND EQUIPMENT GROUND WIRING IN TUBING OR CONDUIT SHALL BE SINGLE COPPER CONDUCTOR (#14 OR LARGER) WITH TYPE
THHW, THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
10. SUPPLEMENTAL EQUIPMENT GROUND WIRING LOCATED INDOORS SHALL BE SINGLE COPPER CONDUCTOR (#6 OR LARGER) WITH TYPE THHW,
THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
11. POWER AND CONTROL WIRING IN FLEXIBLE CORD SHALL BE MULTI -CONDUCTOR, TYPE SOOW CORD (#14 OR LARGER) UNLESS OTHERWISE
SPECIFIED.
12. POWER AND CONTROL WIRING FOR USE IN CABLE TRAY SHALL BE MULTI -CONDUCTOR, TYPE TC CABLE (#14 OR LARGER), WITH TYPE THHW,
THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
13. ALL POWER AND GROUNDING CONNECTIONS SHALL BE CRIMP -STYLE, COMPRESSION WIRE LUGS AND WIRE NUTS BY THOMAS AND BETTS (OR
EQUAL). LUGS AND WIRE NUTS SHALL BE RATED FOR OPERATION NOT LESS THAN 75° C (90° C IF AVAILABLE).
14. RACEWAY AND CABLE TRAY SHALL BE LISTED OR LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, UL, ANSI/IEEE AND NEC.
15. ELECTRICAL METALLIC TUBING (EMT), INTERMEDIATE METAL CONDUIT (IMC), OR RIGID METAL CONDUIT (RMC) SHALL BE USED FOR EXPOSED
INDOOR LOCATIONS.
16. ELECTRICAL METALLIC TUBING (EMT) OR METAL -CLAD CABLE (MC) SHALL BE USED FOR CONCEALED INDOOR LOCATIONS.
17. SCHEDULE 40 PVC UNDERGROUND ON STRAIGHTS AND SCHEDULE 80 PVC FOR ALL ELBOWS/90s AND ALL APPROVED ABOVE GRADE PVC
CONDUIT.
18. LIQUID -TIGHT FLEXIBLE METALLIC CONDUIT (LIQUID-TITE FLEX) SHALL BE USED INDOORS AND OUTDOORS, WHERE VIBRATION OCCURS OR
FLEXIBILITY IS NEEDED.
19. CONDUIT AND TUBING FITTINGS SHALL BE THREADED OR COMPRESSION -TYPE AND APPROVED FOR THE LOCATION USED. SET SCREW FITTINGS
ARE NOT ACCEPTABLE.
20. CABINETS, BOXES AND WIRE WAYS SHALL BE LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, UL, ANSI/IEEE AND THE NEC.
21. WIREWAYS SHALL BE METAL WITH AN ENAMEL FINISH AND INCLUDE A HINGED COVER, DESIGNED TO SWING OPEN DOWNWARDS (WIREMOLD
SPECMATE WIREWAY).
22. SLOTTED WIRING DUCT SHALL BE PVC AND INCLUDE COVER (PANDUIT TYPE E OR EQUAL).
23. CONDUITS SHALL BE FASTENED SECURELY IN PLACE WITH APPROVED NON -PERFORATED STRAPS AND HANGERS. EXPLOSIVE DEVICES (i.e.
POWDER -ACTUATED) FOR ATTACHING HANGERS TO STRUCTURE WILL NOT BE PERMITTED. CLOSELY FOLLOW THE LINES OF THE STRUCTURE,
MAINTAIN CLOSE PROXIMITY TO THE STRUCTURE AND KEEP CONDUITS IN TIGHT ENVELOPES. CHANGES IN DIRECTION TO ROUTE AROUND
OBSTACLES SHALL BE MADE WITH CONDUIT OUTLET BODIES. CONDUIT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. PARALLEL
AND PERPENDICULAR TO STRUCTURE WALL AND CEILING LINES. ALL CONDUIT SHALL BE FISHED TO CLEAR OBSTRUCTIONS. ENDS OF CONDUITS
SHALL BE TEMPORARILY CAPPED FLUSH TO FINISH GRADE TO PREVENT CONCRETE, PLASTER OR DIRT FROM ENTERING. CONDUITS SHALL BE
RIGIDLY CLAMPED TO BOXES BY GALVANIZED MALLEABLE IRON BUSHING ON INSIDE AND GALVANIZED MALLEABLE IRON LOCKNUT ON OUTSIDE
AND INSIDE.
24. EQUIPMENT CABINETS, TERMINAL BOXES, JUNCTION BOXES AND PULL BOXES SHALL BE GALVANIZED OR EPDXY -COATED SHEET STEEL. SHALL
MEET OR EXCEED UL 50 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND NEMA 3 (OR BETTER) FOR EXTERIOR LOCATIONS.
25. METAL RECEPTACLE, SWITCH AND DEVICE BOXES SHALL BE GALVANIZED, EPDXY -COATED OR NON -CORRODING; SHALL MEET OR EXCEED UL
514A AND NEMA OS 1 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED (WP OR BETTER) FOR EXTERIOR
LOCATIONS.
26. NONMETALLIC RECEPTACLE, SWITCH AND DEVICE BOXES SHALL MEET OR EXCEED NEMA OS 2 (NEWEST REVISION) AND BE RATED NEMA 1 (OR
BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED (WP OR BETTER) FOR EXTERIOR LOCATIONS.
27. THE CONTRACTOR SHALL NOTIFY AND OBTAIN NECESSARY AUTHORIZATION FROM THE CARRIER AND/OR DISH WIRELESS AND TOWER OWNER
BEFORE COMMENCING WORK ON THE AC POWER DISTRIBUTION PANELS.
28. THE CONTRACTOR SHALL PROVIDE NECESSARY TAGGING ON THE BREAKERS, CABLES AND DISTRIBUTION PANELS IN ACCORDANCE WITH THE
APPLICABLE CODES AND STANDARDS TO SAFEGUARD LIFE AND PROPERTY.
29. INSTALL LAMICOID LABEL ON THE METER CENTER TO SHOW "DISH WIRELESS".
30. ALL EMPTY/SPARE CONDUITS THAT ARE INSTALLED ARE TO HAVE A METERED MULE TAPE PULL CORD INSTALLED.
wireless-
5701 S SANTA FE DR
LITTLETON, CO 80120
�ulL�
W/RLL L//
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
M SQIUARr•
WIRELESS
1367 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
DRAWN BY: EZG
CHECKED BY: MM
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD's FOR SUBMITTAL
0
07/22/2022
100%CD'S-JX COMMENT
C
06/29/2022
100%CD's FOR REVIEW
B
02/09/2022
90%CD's FOR REVIEW
A
01/14/2022
90%CD's FOR REVIEW
REV
I DATE
I DESCRIPTION
DATE SIGNED: 12/22/2022
Loyal) A. Wb-., P.E.
Professional Engine: License: #C50547
Expiration Date: 06-30,2023
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
GENERAL NOTES
SHEET NUMBER
GN-3
GROUNDING NOTES:
1. ALL GROUND ELECTRODE SYSTEMS (INCLUDING TELECOMMUNICATION, RADIO, LIGHTNING PROTECTION AND AC POWER GES'S) SHALL BE
Co Mh i yEDtV At ii( ��R®1� wRYa-RMLIWE COPPER BONDING CONDUCTORS IN ACCORDANCE WITH THE NEC.
2. TVA CONT�F ACT0A,MN $HA11, PNEIRIFORfy, IEEE FALL -OF -POTENTIAL RESISTANCE TO EARTH TESTING (PER IEEE 1100 AND 81) FOR GROUND
E IETItI�ITI&' IMIst9(n)mTFUttpeftm.®URNISH AND INSTALL SUPPLEMENTAL GROUND ELECTRODES AS NEEDED TO ACHIEVE A TEST
RESULT OF 5 OHMS
��ESPOOFR�LESS. C V PE I N . THE CONTRACTO S RNSIBnLE FOR PROPERLY SEQUENCING GROUNDING AND UNDERGROUND CONDUIT INSTALLATION AS TO PREVENT
Ca e # ANY LOSS CMR12LO23T OUNDING SYSTEM OR DAMAGE TO THE CONDUIT AND PROVIDE TESTING RESULTS.
4. t� ELECTRICALLY CONTINUOUS WITH LISTED BONDING FITTINGS OR BY BONDING
ACROSS +98OR�I I� I+ #6 COPPER WIRE UL APPROVED GROUNDING TYPE CONDUIT CLAMPS.
Ap rova I BQaW IAIBIJLV I�W�IZEruR CORDANCE WITH THE NEC, SHALL BE A D (INSTALLED WIED AS THE NEC REQUIRED EQUIPMENT GROUND CONDUCTOR. TH THE POWER CIRCUITS TO BTS
ANDED COPPER CONDUCTORS WITH
E UIPMENT
Ap[roval Da e 02/23/23
6. EACH eAllINEl FRAME and L DC Ul-I LI v1 HE MASTER GROUND BAR WITH GREEN INSULATED SUPPLEMENTAL EQUIPMENT
Sigature GROIINTjINdlbSWfflF9 COPPER OR LARGER FOR INDOOR BTS; #2 BARE SOLID TINNED COPPER FOR OUTDOOR BTS.
7. CONNECTIONS T�aTS}�EI1Rd Eger BUS SHALL NOT BE DOUBLED UP OR STACKED BACK TO BACK CONNECTIONS ON OPPOSITE SIDE OF THE
GROUND BUS ARE PERMITTE .
8. ALL EXTERIOR GROUND CONDUCTORS BETWEEN EQUIPMENT/GROUND BARS AND THE GROUND RING SHALL BE #2 SOLID TINNED COPPER
UNLESS OTHERWISE INDICATED.
9. ALUMINUM CONDUCTOR OR COPPER CLAD STEEL CONDUCTOR SHALL NOT BE USED FOR GROUNDING CONNECTIONS.
10. USE OF 90° BENDS IN THE PROTECTION GROUNDING CONDUCTORS SHALL BE AVOIDED WHEN 450 BENDS CAN BE ADEQUATELY SUPPORTED.
11. EXOTHERMIC WELDS SHALL BE USED FOR ALL GROUNDING CONNECTIONS BELOW GRADE.
12. ALL GROUND CONNECTIONS ABOVE GRADE (INTERIOR AND EXTERIOR) SHALL BE FORMED USING HIGH PRESS CRIMPS.
13. COMPRESSION GROUND CONNECTIONS MAY BE REPLACED BY EXOTHERMIC WELD CONNECTIONS.
14. ICE BRIDGE BONDING CONDUCTORS SHALL BE EXOTHERMICALLY BONDED OR BOLTED TO THE BRIDGE AND THE TOWER GROUND BAR.
15. APPROVED ANTIOXIDANT COATINGS (i.e. CONDUCTIVE GEL OR PASTE) SHALL BE USED ON ALL COMPRESSION AND BOLTED GROUND
CONNECTIONS.
16. ALL EXTERIOR GROUND CONNECTIONS SHALL BE COATED WITH A CORROSION RESISTANT MATERIAL.
17. MISCELLANEOUS ELECTRICAL AND NON -ELECTRICAL METAL BOXES, FRAMES AND SUPPORTS SHALL BE BONDED TO THE GROUND RING, IN
ACCORDANCE WITH THE NEC.
18. BOND ALL METALLIC OBJECTS WITHIN 6 ft OF MAIN GROUND RING WITH (1) #2 BARE SOLID TINNED COPPER GROUND CONDUCTOR.
19. GROUND CONDUCTORS USED FOR THE FACILITY GROUNDING AND LIGHTNING PROTECTION SYSTEMS SHALL NOT BE ROUTED THROUGH
METALLIC OBJECTS THAT FORM A RING AROUND THE CONDUCTOR, SUCH AS METALLIC CONDUITS, METAL SUPPORT CLIPS OR SLEEVES
THROUGH WALLS OR FLOORS. WHEN IT IS REQUIRED TO BE HOUSED IN CONDUIT TO MEET CODE REQUIREMENTS OR LOCAL CONDITIONS,
NON-METALLIC MATERIAL SUCH AS PVC CONDUIT SHALL BE USED. WHERE USE OF METAL CONDUIT IS UNAVOIDABLE (i.e., NONMETALLIC CONDUIT
PROHIBITED BY LOCAL CODE) THE GROUND CONDUCTOR SHALL BE BONDED TO EACH END OF THE METAL CONDUIT.
20. ALL GROUNDS THAT TRANSITION FROM BELOW GRADE TO ABOVE GRADE MUST BE #2 BARE SOLID TINNED COPPER IN 3/4" NON-METALLIC,
FLEXIBLE CONDUIT FROM 24" BELOW GRADE TO WITHIN 3" TO 6" OF CAD -WELD TERMINATION POINT. THE EXPOSED END OF THE CONDUIT MUST
BE SEALED WITH SILICONE CAULK. (ADD TRANSITIONING GROUND STANDARD DETAIL AS WELL).
21. BUILDINGS WHERE THE MAIN GROUNDING CONDUCTORS ARE REQUIRED TO BE ROUTED TO GRADE, THE CONTRACTOR SHALL ROUTE TWO
GROUNDING CONDUCTORS FROM THE ROOFTOP, TOWERS, AND WATER TOWERS GROUNDING RING, TO THE EXISTING GROUNDING SYSTEM, THE
GROUNDING CONDUCTORS SHALL NOT BE SMALLER THAN 2/0 COPPER. ROOFTOP GROUNDING RING SHALL BE BONDED TO THE EXISTING
GROUNDING SYSTEM, THE BUILDING STEEL COLUMNS, LIGHTNING PROTECTION SYSTEM, AND BUILDING MAIN WATER LINE (FERROUS OR
NONFERROUS METAL PIPING ONLY). DO NOT ATTACH GROUNDING TO FIRE SPRINKLER SYSTEM PIPES.
d .*s'
wireless-
5701 S SANTA FE DR
LITTLETON, CO 80120
Clu.lAwz'.Tvff_�?k._
1200 DEL PASO RD, STE 150
SACRAMENTO, CA 95843
M SQIUARrLcrEj
WIRELESS
1387 CALLE AVANZADO
SAN CLEMENTE CA 92673 (949) 391-6824
DRAWN BY: EZG
CHECKED BY: MM
3
12/22/2022
100% CD'S FOR SUBMITTAL
2
10/28/2022
100% CD'S FOR SUBMITTAL
1
10/05/2022
100% CD'S FOR SUBMITTAL
0
07/22/2022
100%CD'S -JX COMMENT
C
06/29/2022
100% COS FOR REVIEW
B
02/09/2022
90%COS FOR REVIEW
A
01/14/2022
90%COS FOR REVIEW
REV
I DATE
I DESCRIPTION
DATE SIGNED: 12/22/2022
LoyO A. W6azmn, P.E.
Professional Engine: License: #C50547
Expiration Date: 06-30,2023
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY
ARE ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT.
SFSFOO1041A
10110 CALIFORNIA OAK WAY
CUPERTINO, CA 95014
TRANSMISSION TOWER
SHEET TITLE
GENERAL NOTES
SHEET NUMBER
GN-4