B-2017-0824CITY OF CUPERTINO BUILDING PERMIT
BUILDING ADDRESS: CONTRACTOR: PERMIT NO: B-2017-0824
1265 POPPY WAY CUPERTINO, CA 95014-5355 (366 18 018) KENT ROOFING
OWNER'S NAME: LEW YUEH-MEI
OWNER'S PHONE: 408-996-9000
License Class QM- Lic. #957398
Contractor KENT ROOFING COMPANY INC Date 05/31/2019
I hereby affirm that I am licensed under the provisions of Chapter 9 (commencing
with Section 7000) of Division 3 of the Business & Professions Code and that my
license is in full force and effect.
I hereby affirm under penalty of perjury one of the following two declarations:
t. I have and will maintain a certificate of consent to self -insure for Worker's
Compensation, as provided for by Section 3700 of the Labor Code, for the
performance of the work for which this permit is issued.
z. I have and will maintain Worker's Compensation Insurance, as provided for by
Section 3700 of the Labor Code, for the performance of the work for which this
permit is issued.
APPLICANT CERTIFICATION
I certify that I have read this application and state that the above
information is correct. I agree to comply with all city and county ordinances
and state laws relating to building construction, and hereby authorize
representatives of this city to enter upon the above mentioned property for
inspection purposes. (We) agree to save indemnify and keep harmless the
City of Cupertino against liabilities, judgments, costs, and expenses which
may accrue against said City in consequence of the granting of this permit.
Additionally, the applicant understands and will comply with all non -point
source regulations per the Cupertino Municipal Code, Section 9.18.
Date 5/24/2017
COMPANY INC
CAMPBELL, CA 95008
DATE ISSUED: 05/24/2017
PHONE NO: (408) 971-4042
BUILDING PERMIT INFO:
BLDG —ELECT —PLUMB
MECH X RESIDENTIAL _ COMMERCIAL
JOB DESCRIPTION:
REROOF; TEAR OFF; INSTALL OSB; COMP SHINGLES (26 SQ)
Sq. Ft Floor Area: I Valuation: $16000.00
APN Number: Occupancy Type:
36618 018
PERMIT EXPIRES IF WORK IS NOT STARTED
WITHIN 180 DAYS OF PERMIT ISSUANCE OR
180 DAYS FROM LAST CALLED INSPECTION.
Issued by: Abby Apende
Date: 05/24/2017
I hereby affirm that I am exempt from the Contractor's License Law for one of the RE -ROOFS,
following two reasons: All roofs shall be inspected prior to any roofing material being installed. If a roof is
t. I, as owner of the property, or my employees with wages as their sole installed without first obtaining an inspection, I agree to remove all new materials for
compensation, will do the work, and the structure is not intended or offered for inspection.
sale (Sec.7044, Business & Professions Code)
z. I, as owner of the property, am exclusively contracting with licensed
contractors to construct the project (Sec.7044, Business & Professions Code).
I hereby affirm under penalty of perjury one of the following three declarations:
r. I have and will maintain a Certificate of Consent to self -insure for Worker's
Compensation, as provided for by Section 3700 of the Labor Code, for the
performance of the work for which this permit is issued.
2. I have and will maintain Worker's Compensation Insurance, as provided for by
Section 3700 of the Labor Code, for the performance of the work for which this
permit is issued.
3. I certify that in the performance of the work for which this permit is issued, I
shall not employ any person in any manner so as to become subject to the
Worker's Compensation laws of California. If, after making this certificate of
exemption, I become subject to the Worker's Compensation provisions of the
Labor Code, I must forthwith comply with such provisions or this permit shall
be deemed revoked.
APPLICANT CERTIFICATION
I certify that I have read this application and state that the above information is
correct. I agree to comply with all city and county ordinances and state laws
relating to building construction, and hereby authorize representatives of this city
to enter upon the above mentioned property for inspection purposes. (We) agree
to save indemnify and keep harmless the City of Cupertino against liabilities,
judgments, costs, and expenses which may accrue against said City in
consequence of the granting of this permit. Additionally, the applicant understands
and will comply with all non -point source regulations per the Cupertino Municipal
Code, Section 9.18.
Date 5/24/2017
Signature of Applicant:
Date: 5/24/2017
BE CLASS "A" OR BETTER
HAZARDOUS MATERIALS DISCLOSURE
I have read the hazardous materials requirements under Chapter 6.95 of the
California Health & Safety Code, Sections 25505, 25533, and 25534. I will
maintain compliance with the Cupertino Municipal Code, Chapter 9.12 and the
Health & Safety Code, Section 25532(a) should I store or handle hazardous
material. Additionally, should I use equipment or devices which emit hazardous
air contaminants as defined by the Bay Area Air Quality Management District I
will maintain compliance with the Cupertino Municipal Code, Chapter 9.12 and
the Health & Safety Code, Sections 25505, 25533, and 25534.
CTION L
Owner or authorize a
Date: 5/24/2017
CO
.�� � ENDINGAGENCY
I hereby affirm that there is a construction lending agency for the performance
of work's for which this permit is issued (Sec. 3097, Civ C.)
Lender's Name
Lender's Address
ARCHITECT'S DECLARATION
I understand my plans shall be used as public records.
Licensed
e
CUPERTINO
P) -W [�- - N2 -,q
REROOF PERMIT APPLICATION
COMMUNITY DEVELOPMENT DEPARTMENT • BUILDING DIVISION
10300 TORRE AVENUE • CUPERTINO, CA 95014-3255
(408) 777-3228 • FAX (408) 777-3333 • building(d)cupertino.orct
ReroofApp_201].doe revised 03/16/11
CUPERTINO
REROOF TEAR -OFF POLICY
COMMUNITY DEVELOPMENT DEPARTMENT - BUILDING DIVISION
ALBERTSALVADOR, P.E., C.B.O., BUILDING OFFICIAL
10300 TORRE AVENUE • CUPERTINO, CA 95014-3255
(408) 777-3228 • FAX (408) 777-3333 • buildinaCacupertino.or4
PROJECT ADDRESS
APN k
OWNER NA- — yf W
'r lam'/
r I
P
A �Q
E-MAIL
STREET.ADDRESS
CITY, ST E, ZIP
e10 CA.. c'so
FAX
o
CONTRACTOR NAI^
Uva
I
LICENSE NUMB!
LICENSEPE
BUS. LIC. 4
a7
r
COMPANY NAM
aQ
E-MAILFAX
C S 6
CZ"ID
f
Q,t
STREET ADDRESS 1
—f"1'1
CITY, STATE, ZIP
C���
�l C,�
R �
P
lft i — qcqfl
s
;
I UNDERSTAND AND AGREE TO THE FOLLOWING:
1. The re -roof project shall comply with all applicable provisions of the 2016 California Codes.
2. An inspection request can be scheduled up to one business day before the requested inspection date.
Please schedule inspections online or call (408) 777-3228 from 7:30-3:30pm (Mon-Thurs) or 7:30-
2:30pm (Friday) to schedule inspection. For Tear -Off and Nailing Inspections, you must also call on the
day of the inspection only after that phase of the work is completed. The building inspector will be
available within one hour. The hours for this service are: 7:30-10:30am. and 12:30-3:30 (Mon-Thurs)
and 7:30-10:30am and 12:30-2:30 (Friday). Final Inspections will be given a two hour window.
3. Tear -Off Inspection is required. Any and all dry -rotted wood shall be replaced prior to this inspection.
Unless new plywood roof sheathing is proposed throughout, all the nails/fasteners shall be either
completely knocked -down or removed prior to this inspection.
4. If plywood is installed, a plywood Nailing Inspection is required.
5. Roofing shall not be applied without first obtaining all prior inspection and written approvals from the
building inspector. Any roofing which is applied without first obtaining an approved inspection will
require the removal of all new material down to the sheathing so a proper inspection can be performed.
6. A Final Inspection and approval shall be obtained from the building inspector when the re -roofing is
completed. To receive a final sign -off, the following items will be verified:
a. Flat roofs shall have a minimum of I/" per foot of slope and demonstrate there is no ponding.
b. Listings from approved testing agencies for all pre -manufactured products used shall be
available on-site to review at the time of the inspection.
Proper spark arrestor installation, vents painted, gutter/downspouts installed, debris removed.
7. NOTE: If you call for a tear -off or plywood nailing inspection and the work is not complete, you will be
charged a re -inspection fee. The re -inspection fee shall be paid before another inspection can be
scheduled.
By my signing below, I certify each of the following is true: I am the property owner or authorized agent to act on the
property owner's behalf I understand and agree to comply with the re -roof policy stated above. I also understand that
smoke detectors and carbon monoxide detectors are required to be installed in accordance with Sections R314 and R315 of
the 2016 California
Sienature of ADulicant/A2eritr-:';
Date:
ReroofPolicy_2014.doc revised 12115/16
CUPERTINO
SMOKE / CARBON MONOXIDE ALARMS
OWNER CERTIFICATE OF COMPLIANCE
COMMUNITY DEVELOPMENT DEPARTMENT • BUILDING DIVISION
10300 TORRE AVENUE • CUPERTINO, CA 95014-3255
(408) 777-3228 • FAX (408) 777-3333 • buildingacupertino.org
PURPOSE
This affidavit is a self -certification for the installation of all required Smoke and Carbon Monoxide Alarms for
compliance with 2016 CRC Section R314, R315, 2016 CBC Sections 420.6 and 907.2.11.2 where no interior access
for inspections are required.
GENERAL INFORMATION
Existing single-family and multi -family dwellings shall be provided with Smoke Alarms and Carbon
Monoxide alarms. When the valuation of additions, alterations, or repairs to existing dwelling units exceeds
$1000.00, CRC Section R314, R315, and CBC Sections 907.2.11.5 and 420.6 require that Smoke Alarms and/or
Carbon Monoxide Alarms be installed in the following locations:
AREA
SMOKE ALARM
CO ALARM
Outside of each separate sleeping area in the immediate vicinity of the
bedroom(s) — (Smoke alarms shall not be located within 3 feet of bathroom door)
X
X
On every level of a dwelling unit including basements and habitable attics
X
X
Within each sleeping room
X
Carbon Monoxide alarms are not required in dwellings which do not contain fuel -burning appliances and that
do not have an attached garage. Carbon monoxide alarms combined with smoke alarms shall comply with
CBC Section 420.6 and shall be approved by the Office of the State Fire Marshal.
Power Supply: In dwelling units with no commercial power supply, alarm(s) may be solely battery operated.
In existing dwelling units, alarms are permitted to be solely battery operated where repairs or alterations do
not result in the removal of wall and ceiling finishes or there is no access by means of attic, basement or crawl
space. Refer to CRC Section R314 and CBC Sections 907.2.11.4 and 420.6.2. An electrical permit is required for
alarms which must be connected to the building wiring.
As owner of the above -referenced property, I hereby certify that the alarm(s) referenced above has/have been
installed in accordance with the manufacturer's instructions and in compliance with the California Building
and California Residential Codes. The alarms specified below have been tested and are operational, as of the
date signed below. / _
Address: to J �. (� Q nt 2Cl/ %� �� C
Permit No.
Specify Number of Alarms: # Smoke Alarms: = # Carbon Monoxide Detectors: FT7771
Owner (or Owner Agent's) Name:
Name:
1 have read and agree to comply with the terms and conditions of this statement
nature
R
Sianature...................................................................... Lic.#........................................ Date:................
Smoke and COform.doc revised 01/10/2017
WATER -CONSERVING PLUMBING FIXTURES
OWNER CERTIFICATE OF COMPLIANCE
COMMUNITY DEVELOPMENT DEPARTMENT • BUILDING DIVISION
CUPRTINO I 10300 TORRE AVENUE • CUPERTINO, CA 95014-3255
(40 ) 777-3228 • FAX (408) 777-3333 • building(a)cupertino.org Li
Owner NameV (2APermit No. �- Lot? ? '- (59Z
Address t S Pu.th,
1. Is your real property a registered historical site?
❑ Yes Civil Code Sections 1101.1 through 1.101.8 do not apply. Skip the rest of the form and sign bottom of form.
No Go to Question 2.
2. Does your real property have a licensed plumber certifying that, due to the age or configuration of the property or its
plumbing, installation of water -conserving plumbing fixtures is not technically feasible?
❑ Yes Civil Code Sections 1101.1 through 1101.8 do not apply.
❑ The licensed plumber's certification has been provided to the Building Division.
Skip the rest of the form and sign bottom of form.
iA No Go to Question 3.
3. Is water service permanently disconnected for your building?
❑ Yes Civil Code Sections 1101.1 through 1101.8 do not apply. Skip the rest of the form and sign bottom of form.
X No Go to Question 4.
4. Is your real property built and available for use or occupancy on or before January 1, 1994?
❑ No My real property is built and available for use or occupancy after January 1, 1994.
Civil Code Sections 1101.1 through 1101.8 do not apply. Skip the rest of the form and sign bottom of form.
f2� Yes My real property is built and available for use or occupancy on or before January 1, 1994.
Civil Code Sections 1101.1 through. 110 1. 8 apply. Check one of the three following statements and sign
bottom. of form.,
Please check ONE of the following:
It My property is a single family residential real property. See Civil Code Section 1101.4.
On and after January 1, 2014, building alterations or improvements shall require all non-compliant plumbing fixtures
to be replaced with water-conservins plumbing fixtures throughout the building. On or before January 1, 2017, all non-
compliant plumbing fixtures shall be replaced with water -conserving plumbing fixtures (regardless of whether
property undergoes alterations or improvements).
❑ My property is a multifamily residential real property. See Civil Code Section 1101.5.
On and after January 1, 2014, specified building alterations or improvements shall require non- compliant
plumbing fixtures to be replaced with water -conserving plumbing fixtures.
On or before January 1, 2019, all non-compliant plumbing fixtures shall be replaced with water -
consenting plumbing fixtures throughout the building (regardless of whether property undergoes alterations or
improvements).
❑ My property is a c077777iercial real property. See Civil Code Section 1101.5.
On and after January 1, 2014, specified building alterations or improvements shall require non- compliant
plumbing fixtures to be replaced with water -conserving plumbing fixtures.
On or before January 1, 2019, all non-compliant plumbing fixtures shall be replaced with Nvater- conserving
plumbing fixtures throughout the building (regardless of whether property undergoes alterations or improvements).
I, as the owner or owner's agent of this property, certify under penalty of perjury that non-compliant plumbing fixtures will be
replaced prior to date specified above with water -conserving plumbing fixtures in accordance with Civil Code Sections 1101.1
through 1101.8, the current California Plumbing Code and California Green Building Standards Code, and manufacturer's
installation requirements, and that the water -conserving plumbing fixtures comply with the requirements as indicated in the
table on the following Uaue.
I Owner or Owner Agent's Signature: ' .% �eg,u `",fxy n&c,� Date: E'/ // .�
Upon completing and signing this Certificate, pleasfretu# it to th6e Building Division in order to final your building permit.
SB407 2015.doc revised 01/05/17
1. If the existing plumbing fixture water usage/flour rate is equal to or lower than the figure shown, it is not requirea to oe upgraaea.
SB407 2015.doe revised 08/26/15
Non -Compliant
Water -Conserving Plumbing Fixture
Plumbing Fixture/
(Fixture Complying with Current Code Applicable to New Construction)
Maximum
Water Usage/Flow
Rate
Fixture Type
2013 CPC Ch. 4
2013 CPC Ch. 4
2013 CPC Ch. 4
Water Usage
2013 CALGreen Div. 4.3
2013 CALGreen Div. 4.3
2013 CALGreen Div. 5.3
/Flow Rate
Single -Family
Multi -Family
Commercial
Residential
Residential
Water Closets
Exceed 1.6
Single flush toilets: 1.28 gallons/flush
(Toilets)
Gallons/flush
Dual flush toilets: 1.28 gallons/flush effective flush volume (the composite,
average flush volume of two reduced flushes and one full flush
Urinals
Exceed 1.0
0.5 gallons/flush
Gallons/flush
Showerheads
Exceed 2.5
2.0 gallons per minute @ 80 psi. Also certified to the performance criteria of
gallons per minute
U.S. EPA WaterSense Specification for Showerheads
(A hand-held shower is considered a showerhead.)
For multiple showerheads serving one shower, the combined flow rate of all
showerheads and/or other shower outlets controlled by a single valve shall not
exceed 2.0 gallons per minute @ 80 psi, or the shower shall be designed to
allow only one shower outlet to be in operation at a time. —
Faucets —
Exceed 2.2 gallons
Maximum 1.5 gallons per
Within units:
0.5 gallons per minute @ G0
Lavatory
per minute
minute @ 60 psi; minimum
Maximum 1.5 gallons
psi
Faucets
0.8 gallons per minute @
per minute @ 60 psi;
20 psi
minimum 0.8 gallons
per minute @ 20 psi
In common and public
use areas: 0.5 gallons
per minute @ 60 psi
1.8 gallons per minute
60 psi
Faucets —
Exceed 2.2 gallons
1.8 gallons per minute @
1.8 gallons per minute
1.8 gallons per minute @ 60
Kitchen
per minute
60 psi
@ 60 psi
psi
Faucets
May temporarily increase
May temporarily
up to 2.2 gallons per
increase up to 2.2
minute @ 60 psi, and must
gallons per minute @
default to maximum
60 psi, and must
1.8 gallons per minute @
default to maximum
60 psi
1.8 gallons per minute
Where faucets meeting
@ 60 psi
the above are unavailable,
Where faucets meeting
aerators or other means
the above are
may be used to achieve
unavailable, aerators or
reduction.
other means may be
used to achieve
reduction.
1. If the existing plumbing fixture water usage/flour rate is equal to or lower than the figure shown, it is not requirea to oe upgraaea.
SB407 2015.doe revised 08/26/15